Version: 01.02; Date: 18.11.2022
Note
Provisions of IEC 62368-1
Assembly and disassembly of the supply line to the plug is only permitted in a
de-energized state (e.g. by the primary-side line protection).
The supply lines must be adequately fused and dimensioned.
Connection cross-section: 1mm² - 2.5mm² (17 AWG - 13 AWG)
The device must be supplied via a suitable disconnecting device (switch). The
disconnecting device must be easily accessible, installed near the device and
marked as a disconnecting device for the device.
2 x voltage supply (redundant) - 3 pole
Conductor cross section
1mm²
– 2,5mm² (17 AWG – 13 AWG)
Note
An additional disconnecting device (protective contact socket / mains switch)
must be easily accessible.
9.3.4.2
Status LEDs of extension boards
All extension boards are equipped with status LEDs on their front panels. These are used
for quick identification of the operating status of the respective board on the system.
LED Status
Red
The PSU has detected an operating fault
e.g. missing supply voltage / defective board
Yellow
LED is currently without function
Green
The PSU is in full operational readiness