Multi-Source Function System 7001RC - V02.01 

hopf

 

Elektronik GmbH 

Nottebohmstr. 41 • D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: [email protected]

 

2.3.2   Adjustable Multi-Source Modes 

The sync. sources are connected to the synchronisation channels of the 7020RC control 
board. The selection and connection of the various synchronisation channels is described 
below. Only the described combinations of synchronisation channels are available. 

A re-configuration of these modes automatically triggers a RESET after configuration in the 
system. 

2.3.2.1  Multi-Source with GPS (Channel 1) and Master/Slave-String (Channel 3) 

The combination of GPS and Master/Slave-String can be selected via the following two bit 
combinations in the 

"Synchronisation Settings Byte"

. The primary and secondary sources 

can also be assigned. After the initial setting of one of the two bit combinations a System 
Reset is carried out automatically. When there is a changeover within this multi-source mode 
no System Reset is carried out and the system then continues with quartz system status. 

 

B3  B2  B1  B0  Abbreviation in Time Display 

Synchronisation Source 

1 0 0 1 

alternately

 >GPS_

 and 

SER_  

Primary source

: GPS 

Secondary source

:  

Master/Slave-String  

1 0 1 0 

alternately

 >SER_ 

and 

GPS_

 

 

Primary source

: Master/Slave-

String 

Secondary source

: GPS 

 

2.3.2.2  Multi-Source with DCF77 Pulse (Channel 2) and Master/Slave-String 

(Channel 3) 

The combination of DCF77 pulse and Master/Slave-String can be selected via the following 
two bit combinations in the 

"Synchronisation Settings Byte"

. The primary and secondary 

sources can also be assigned. After the initial setting of one of the two bit combinations a 
System Reset is carried out automatically. When there is a changeover within this multi-
source mode no System Reset is carried out and the system then continues with quartz 
system status. 

 

B3  B2  B1  B0 

Abbreviation in Time Display 

Synchronisation Source 

1 0 1 1 

alternately

 >DCF_ 

and 

SER_  

Primary source

: DCF77 pulse 

Secondary source

Master/Slave-String 

1 1 0 0 

alternately

 >SER_ 

and 

DCF_

 

 

Primary source

: Master/Slave-

String 

Secondary source

: DCF77 pulse 

 

Summary of Contents for 7001RC

Page 1: ...Technical Manual System 7001RC Multi Source Function ENGLISH Version 02 01 29 11 2006 _____________________________________________________________ Valid for Control Board 7020RC with FIRMWARE Versio...

Page 2: ...2 31 Multi Source Function System 7001RC V02 01 hopf Elektronik GmbH Nottebohmstr 41 D 58511 L denscheid Tel 49 0 2351 9386 86 Fax 49 0 2351 9386 93 Internet http www hopf com E Mail info hopf com...

Page 3: ...THIS MANUAL PLEASE SEE TECHNICAL MANUAL OF SYSTEM 7001RC SEE CHAPTER MULTI SOURCE SYSTEMS Downloading Technical Descriptions All current descriptions of our products are available free of charge via...

Page 4: ...bel The device should only be operated by qualified staff or employees who have received specific instruction If a device must be opened for repair this should only be carried out by employees with ap...

Page 5: ...urces 13 2 2 Display of the Synchronisation Status in the 7001RC System Display 15 2 3 Configuration of the Multi Source System 16 2 3 1 Automatic Manual Source Changeover 16 2 3 1 1 Status Table for...

Page 6: ...27 3 1 Data String Master Slave 27 3 1 1 Local Time as Time Base in Master Slave String Standard 27 3 1 2 UTC as Time Base in Master Slave String 27 3 1 3 Structure of the Master Slave String 27 3 1 4...

Page 7: ...These systems are only able to recognise from the type of signal emitted by the clock system whether the clock system is synchronised or is running in internal quartz mode The internal quartz mode of...

Page 8: ...me difference between local time and UTC Coordinated Universal Time The time base is defined from The time zone time difference from local time to UTC and the hour offset due to Summer Wintertime chan...

Page 9: ...on status of the sync source and the system status Multi source with manual changeover between the sync sources The user can decide which sync source should be selected to synchronise the system In th...

Page 10: ...information of the available sources is compared and is only used to synchronise the system if a defined time difference between the time data is not exceeded If the permissible difference is exceeded...

Page 11: ...flow Control of switchover manual or automatic between sync channels 1 2 and 3 When the channel is changed the system re synchronises to the selected channel beginning with the system reception statu...

Page 12: ...e multi source system is displayed alternately on the upper line of the 7001RC system display for each sync source can accept the conditions invalid and R radio synchronous with control of the interna...

Page 13: ...wer for 3 days System operates with system quartz time All time and date information begin with zeros in all positions 2 Manual setting of a valid time date C Primary source Internal quartz base Syste...

Page 14: ...ync status change after sync fail timer expired Loss of synchronisation via small r system status System operates with internal quartz base 14 C Primary source Internal quartz base No synchronisation...

Page 15: ...DCF_ Channel 2 DCF77 pulse SER_R SER_ Channel 3 Master Slave String The position of these characters in the display is highlighted in white in the following picture L T 0 3 4 5 4 8 T U 2 3 F E B 2 0 0...

Page 16: ...over The source changeover takes place automatically as standard factory setting If not required this automatic changeover can be prevented using Bit 3 of the Control Bytes function This may be necess...

Page 17: ...nge after sync fail Timer System switches or remains on C Primary source R r running Remains on last sync source with system quartz time until timer expires R C r R Synchronised with primary source R...

Page 18: ...omatically When there is a changeover within this multi source mode no System Reset is carried out and the system then continues with quartz system status B3 B2 B1 B0 Abbreviation in Time Display Sync...

Page 19: ...he system then continues to run demonstrably more accurately using this control value than if it were to be re synchronised via the secondary source For this reason it is sensible to prevent a prematu...

Page 20: ...ynchronisation via the Master Slave String Function Control Byte Bit 2 set to 0 The received time is local time The system UTC time is calculated In the event that UTC time is received when in this se...

Page 21: ...ch as e g RS232 TTY or LWL to the level required by the internal system To transform time transfer formats such as e g IRIG B to the formats required by the internal system When planning a multi sourc...

Page 22: ...status quartz the new active sync source synchronises the clock system and controls the internal quartz base Multi source modes with channels 1 3 Channel 1 Channel 3 or Channel 3 Channel 1 Multi sour...

Page 23: ...announcement hour the announcement bit continues to be set even if the second sync source transmits completely different time information from the first sync source The ST WT changeover then takes pl...

Page 24: ...n Process 2 8 1 Synchronisation via GPS Channel 1 With satellite reception 1 satellite in Fixed Position mode or at least 4 satellites in 3D mode see technical specification of the 7001RC system the r...

Page 25: ...ble before the sync source status changes from to R As soon as the sync source status reaches R synchronisation of the system begins The system status synchronises from quartz operation C via radio sy...

Page 26: ...n ERROR 2 DCF77 pulse ERROR 0 1 Bit 2 changes from 0 to 1 when the system in DCF77 pulse mode Synchronisation Channel 2 is set as sync source for the system but is not receiving DCF77 pulses or they a...

Page 27: ...r 2 3 5 Configuration of the Master Slave String Time Base By the UTC time and the system internal values for difference time UTC local time such as the status information for summer and winter time t...

Page 28: ...0 39 15 unit year 30 39 16 difference time tens hour sign 30 31 38 39 17 difference time unit hour 30 39 18 difference time tens minutes 30 35 19 difference time unit minutes 30 39 20 LF line feed 0A...

Page 29: ...dio operation no announcement standard time It is Wednesday 03 Jan 1996 12 34 56 h The difference to UTC is 2 30 hours 3 1 6 Settings The following settings are required for the synchronisation of the...

Page 30: ...system 7001RC calculates the exact UTC time of the local time from the set difference time 3 2 1 Structure of the Data String DCF77 Signal Every second of a minute a particular time information is tra...

Page 31: ...uncement of a leap second S initial bit of the coded time information P1 P2 P3 check bits DCF77 D German C Long wave signal F Frankfurt 77 frequency 3 2 2 DCF77 Pulse 1Hz The DCF77 pulse uses the same...

Reviews: