COMPACT I/O MODULE

5

95-7716—1

Fig. 6. Wiring example XIO-8AI with sensor.

SOFTWARE DESCRIPTION

The Node Object monitors and controls the functions of the 

different objects in the device. It supports the basic functions 

Object-Status and Object-Request required by LonMark.

 

Refer to Fig. 7 for a basic illustration of Node Objects. The 

following objects are monitored by the Node Object.

nviRequest

NVT_obj_request

nvoStatus

SNVT_obj_status

nvoFileDirectory

SNVT_address

Fig. 7. XIO-8AI Node Object.

SCPTmaxSendTime

 SNVT_time_sec

All output variables described below will be issued at the 

latest at the end of the preset period even without status 

change.

Time settings:

0 timer function off-state

6553,8 s (factory setting 60 s)

UCPTHyst

SNVT_temp_p

Setting of the hysteresis; the output variables nvoHigh and 

nvoLow switch over when the hysteresis is expired (factory 

setting 2 Kelvin).5; 1. counted measurand = 1.

Fig. 8. XIO-8AI Temp Objects.

nvoTemp_1...8

SNVT_temp

The output variable supplies a value with format ° C 

depending on the input signal of 0 to 10.0 V and the settings in 

UCPTTempHigh and UCPTTempLow and/or the resistance of 

the selected temperature sensor.

nvoTemp_1...8

SNVT_temp_p

See Temp_1...8 but with 0.01° C format.

nvoPercent_1...8

SNVT_lev_percent

The output variable supplies a value with format 0 to 100.0% 

for voltage measurements depending on the input signal of 0 

to 10.0 Volt.

nvoVoltage_1...8

SNVT_volt_f

The output variable supplies a value with format 0 to 10.0 Volt 

for voltage measurements depending on the input voltage.

nvoResistance_1...8

SNVT_res_f

The output variable supplies a value with format Ohm 

depending on the input signal of 40 Ohm to 4 MOhm.

M25070

24V

24V

XIO-8AI

SERVICE

+24V

GND

E1

E2

SERVICE

RESET

ON

+24V

GND

E1

E2

8 C 7

C 6

C 5

C

S

1 C 2

C 3

C 4

C

S

Out

GND

+10 to +20V

Sensor

connectors

Jumper

15V Standard

M25045

Node Object

nviRequest

SNVT_obj_request

nvoStatus

SNVT_obj_status

nvoFileDirectory

SNVT_address

SCPTmaxSendTime

UCPTHyst

M25046

Temp_1- 8 Objects

nvoTemp_1 - 8

SNVT_temp

nvoTempp_1 - 8

SNVT_temp_p

UCPTTemp_Offset

UCPTSensor_tab

UCPTTempMax

UCPTTempMin

UCPTHighT

UCPTLowT

SCPTinvrtOut

SCPTminSendTime

SCPTminDeltaTemp

nvoPercent_1 - 8

SNVT_lev_percent

nvoVoltage_1 - 8

SNVT_volt_f

nvoResistance_1 - 8

SNVT_res_f

nvoHigh_1 - 8

SNVT_switch

nvoLow_1 - 8
SNVT_switch

Summary of Contents for XIO-8AI

Page 1: ...Terminal block and strapping plug included in packing Analog Inputs 14 AWG 2 5 mm2 LON Interface Transceiver FTT10A free topology Neuron 3150 64k Flash Data format standard network variables SNVT Transmission rate 78 kBit s Maximum Length line topology 8858 ft 2700 m 64 nodes free topology 1640 ft 500 m 64 nodes Cabling twisted pair Temperature Ratings Operating 23 F to 131 F 5 C to 55 C Storage 4...

Page 2: ...ut application and use of the device within the equipment system BEFORE INSTALLATION 1 Unpack the XIO 8AI Universal LON Analog Input Module 2 Check the equipment and report any damage to a Honeywell representative 3 Read all of these instructions and ensure they are understood MOUNTING Mount the XIO 8AI Universal LON Analog Input Module on standard DIN rail per DIN EN 50022 1 35 x 0 3 in 35 x 7 5 ...

Page 3: ...without interspace The maximum number of modules connected in series is 15 with each group needing an external power supply TERMINATION Fig 1 shows the termination points of the XIO 8AI Fig 1 Termination diagram for XIO 8AI Fig 2 XIO 8AI Termination example 4a 0 3 in 7 mm M25041 24V 24V SERVICE 4b M25065 24V SERVICE 2 5a M25066 24V GND E1 E2 5b M25067 24V GND E1 E2 8 1 C C 7 2 C C 6 3 C C 5 4 C C ...

Page 4: ...setting 24V 24V GND E1 E2 24V GND E1 E2 24V GND E1 E2 24V GND E1 E2 24V XIO 8AI SERVICE SERVICE RESET ON Jumper below the faceplate Jumper in top position contacts S A1 24V AC DC 24V 24V XIO 8AI SERVICE SERVICE RESET ON Jumper below the faceplate M25068 24V 24V XIO 8AI SERVICE 24V GND E1 E2 SERVICE RESET ON 24V GND E1 E2 M25069A XIO 8AI Analog Input 24V GND E bus 1 E bus 2 S S 24V FTT 10A Inputs V...

Page 5: ... 0 V and the settings in UCPTTempHigh and UCPTTempLow and or the resistance of the selected temperature sensor nvoTemp_1 8 SNVT_temp_p See Temp_1 8 but with 0 01 C format nvoPercent_1 8 SNVT_lev_percent The output variable supplies a value with format 0 to 100 0 for voltage measurements depending on the input signal of 0 to 10 0 Volt nvoVoltage_1 8 SNVT_volt_f The output variable supplies a value ...

Page 6: ...p_Offset SNVT_temp The respective measurand can be readjusted in steps of 0 1 K UCPTSensor_tab Factory setting NTC20k in the range 22 F to 266 F 30 C to 130 C UCPTTempMax SNVT_temp Werk 302 F 150 C UCPTTempMin SNVT_temp Werk 58 F 50 C The temperature output variables are calculated during voltage measurings according to a 0 to 10 Volt input signal and the here selected range UCPTHighT SNVT_temp We...

Page 7: ...COMPACT I O MODULE 7 95 7716 1 ...

Page 8: ...ed Trademark 2006 Honeywell International Inc 95 7716 1 C H Rev 02 06 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting f...

Reviews: