background image

COMPACT I/O MODULE

95-7716—1

4

JUMPER POSITIONS

Fig. 3 illustrates the two jumper positions for the voltage 

supply of active sensors.

Fig. 3. XIO-8AI Jumper positions.

WIRING

Wiring of the XIO-8AI must be accomplished in accordance 

with federal, state, and local requirements. Figures 4 through 

6 show sample diagrams of wiring of the XIO-8AI.

Fig. 4. Front panel diagram of XIO-8AI.

Fig. 5. Side panel diagram of XIO-8AI.

M25043

Jumper in
bottom position
contacts S
= 15 VDC
(factory setting)

+24V

24V

GND

E1

E2

+24V

GND

E1

E2

+24V

GND

E1

E2

+24V

GND

E1

E2

24V

XIO-8AI

SERVICE

SERVICE

RESET

ON

Jumper below
the faceplate

Jumper in
top position
contacts S = A1
(24V AC/DC)

24V

24V

XIO-8AI

SERVICE

SERVICE

RESET

ON

Jumper below
the faceplate

M25068

24V

24V

XIO-8AI

SERVICE

+24V

GND

E1

E2

SERVICE

RESET

ON

+24V

GND

E1

E2

M25069A

XIO-8AI

Analog Input

+24V
GND

E-bus 1
E-bus 2

S
S

24V

FTT-10A

Inputs:
Voltage 0-10V

Universal-

40 Ohm - 4 MOhm

Outputs:
    Voltage 15VDC
    or 24VAC/DC

Neuron 3150

A

D

S
S

1

JUMPER IN BOTTOM POSITION (FACTORY DEFAULT),
15 VDC OUTPUT.

1

2

2

JUMPER IN TOP POSITION, 24 VDC OUTPUT.

C

C

C

C

C

C

C

C

1

2

3

4

5

6

7

8

0

2

8 5 2 6 7 2 7 0 7 6

Temp. Sensor

24V

AC/DC

Summary of Contents for XIO-8AI

Page 1: ...Terminal block and strapping plug included in packing Analog Inputs 14 AWG 2 5 mm2 LON Interface Transceiver FTT10A free topology Neuron 3150 64k Flash Data format standard network variables SNVT Transmission rate 78 kBit s Maximum Length line topology 8858 ft 2700 m 64 nodes free topology 1640 ft 500 m 64 nodes Cabling twisted pair Temperature Ratings Operating 23 F to 131 F 5 C to 55 C Storage 4...

Page 2: ...ut application and use of the device within the equipment system BEFORE INSTALLATION 1 Unpack the XIO 8AI Universal LON Analog Input Module 2 Check the equipment and report any damage to a Honeywell representative 3 Read all of these instructions and ensure they are understood MOUNTING Mount the XIO 8AI Universal LON Analog Input Module on standard DIN rail per DIN EN 50022 1 35 x 0 3 in 35 x 7 5 ...

Page 3: ...without interspace The maximum number of modules connected in series is 15 with each group needing an external power supply TERMINATION Fig 1 shows the termination points of the XIO 8AI Fig 1 Termination diagram for XIO 8AI Fig 2 XIO 8AI Termination example 4a 0 3 in 7 mm M25041 24V 24V SERVICE 4b M25065 24V SERVICE 2 5a M25066 24V GND E1 E2 5b M25067 24V GND E1 E2 8 1 C C 7 2 C C 6 3 C C 5 4 C C ...

Page 4: ...setting 24V 24V GND E1 E2 24V GND E1 E2 24V GND E1 E2 24V GND E1 E2 24V XIO 8AI SERVICE SERVICE RESET ON Jumper below the faceplate Jumper in top position contacts S A1 24V AC DC 24V 24V XIO 8AI SERVICE SERVICE RESET ON Jumper below the faceplate M25068 24V 24V XIO 8AI SERVICE 24V GND E1 E2 SERVICE RESET ON 24V GND E1 E2 M25069A XIO 8AI Analog Input 24V GND E bus 1 E bus 2 S S 24V FTT 10A Inputs V...

Page 5: ... 0 V and the settings in UCPTTempHigh and UCPTTempLow and or the resistance of the selected temperature sensor nvoTemp_1 8 SNVT_temp_p See Temp_1 8 but with 0 01 C format nvoPercent_1 8 SNVT_lev_percent The output variable supplies a value with format 0 to 100 0 for voltage measurements depending on the input signal of 0 to 10 0 Volt nvoVoltage_1 8 SNVT_volt_f The output variable supplies a value ...

Page 6: ...p_Offset SNVT_temp The respective measurand can be readjusted in steps of 0 1 K UCPTSensor_tab Factory setting NTC20k in the range 22 F to 266 F 30 C to 130 C UCPTTempMax SNVT_temp Werk 302 F 150 C UCPTTempMin SNVT_temp Werk 58 F 50 C The temperature output variables are calculated during voltage measurings according to a 0 to 10 Volt input signal and the here selected range UCPTHighT SNVT_temp We...

Page 7: ...COMPACT I O MODULE 7 95 7716 1 ...

Page 8: ...ed Trademark 2006 Honeywell International Inc 95 7716 1 C H Rev 02 06 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting f...

Reviews: