COMPACT I/O MODULE

95-7717—2

2

This includes, for example:

• Qualification to connect the device according to applicable 

specifications and regulations, and a qualification to put 

this device into operation, to power it down, or to activate it 

by respecting the internal directions.

• Knowledge of safety rules.

• Knowledge about application and use of the device within 

the equipment system.

BEFORE INSTALLATION

1.

Unpack the XIO-10HUB Extension Module.

2.

Check the equipment and report any damage to a Hon-

eywell representative.

3.

Read all of these instructions and ensure they are 

understood.

MOUNTING

Mount the XIO-10HUB Extension Module on standard DIN rail 

per DIN EN 50022 (1.35 x 0.3 in. [35 x 7.5 mm]), in junction 

boxes and/or on distribution panels.

INSTALLATION

CAUTION

Electrical installation and device termination shall 

be accomplished by qualified persons only, by 

respecting all applicable specifications and 

regulations.

1.

Power down the equipment. Mount the Extension mod-

ule on the DIN rail.

2.

Plug in the terminal block for bus connection.

3.

Prepare the cable for bus connection:

a. Remove about 0.75 in. (2 cm) of the plastic cable 

sheath.

b. Strip 0.2 in. (5 mm) insulation from each wire. Put a 

wire end sleeve on stranded wires.

c. Insert the wire to the respective contact and secure 

it by screwing down the contact screw.

d. Wire cross section of the 4 pole terminal block bus/

mains connection:

(1) Maximum 16 AWG (1.5 mm

2

) single wire.

(2) Maximum 18 AWG (1.0 mm

2

) stranded wire.

(3) Wire diameter minimum 28 AWG (0.3 mm) up to 

16 AWG (1.4 mm).

4.

Prepare cable for module connections.

a. Strip the wires by 0.3 in. (7 mm). Put a wire end 

sleeve on stranded wires.

b. Insert the wire into the respective module contact 

and secure it by screwing down the contact screw 

with a screwdriver.

c. Wire cross section of the 4 pole terminal block

bus/mains connection:

(1) Maximum 12 AWG (4.0 mm

2

) single wire.

(2) Maximum 14 AWG (2.5 mm

2

) stranded wire.

(3) Wire diameter: minimum 28 AWG (0.3 mm) up to 

maximum 10 AWG (2.7 mm).

5.

The module can be aligned without interspace. Use the 

strapping plug to connect bus and supply voltage when 

the modules are mounted in series. The modules can 

be mounted in series without interspace. The maximum 

number of modules connected in series is 15, with each 

group needing an external power supply.

1a

M25060

SERVICE

RESET

ON

1b

M25061

SERVICE

ON

RESET

SERVICE 24V

24V

E2

E1

E2

E1

GND

+24V

2b

M25063

RESET

ON

SERVICE

24V

24V

E2

E1

GND

+24V

E2

E1

2a

M25062

RESET

SERVICE

SERVICE

24V

3b

M25064

SERVICE

24V

3a

0.2 in.

(5 mm)

M25040

4b

M25065

24V

SERVICE

2

4a

0.3 in.

(7 mm)

M25041

24V

24V

SERVICE

5a

M25066

+24V
GND
E1
E2

5b

M25067

+24V
GND
E1
E2

Summary of Contents for XIO-10HUB

Page 1: ...y Construction Material Housing and Terminal Blocks Polyamide 6 6 V0 Faceplate Polycarbonate Protection IP40 housing DIN 40050 IP20 terminal blocks DIN 40050 Approvals UL 916 Standard for Energy Management Equipment European Community Mark CE Listed SAFETY INSTRUCTIONS NOTES REGARDING DEVICE DESCRIPTION These instructions include indications for use and mounting of the device In case of questions ...

Page 2: ... stranded wires c Insert the wire to the respective contact and secure it by screwing down the contact screw d Wire cross section of the 4 pole terminal block bus mains connection 1 Maximum 16 AWG 1 5 mm2 single wire 2 Maximum 18 AWG 1 0 mm2 stranded wire 3 Wire diameter minimum 28 AWG 0 3 mm up to 16 AWG 1 4 mm 4 Prepare cable for module connections a Strip the wires by 0 3 in 7 mm Put a wire end...

Page 3: ... 3 9 4 10 5 11 6 12 24 V GND E1 E2 24 V GND E1 E2 E2 E1 GND 24V E2 E1 GND 24V 7 8 9 10 11 12 1 2 3 4 5 6 BUS Ub 10 A Max 60 V Bus Stecker max 3 A M25071 24V 24V GND E1 E2 24V 24V GND E1 E2 24V GND 1 7 2 8 3 9 4 10 5 11 6 12 XIO 10HUB M25072A E2 E1 GND 24V 7 8 9 10 11 12 1 2 3 4 5 6 BUS Ub 10 A Max 60V Bus Plug max 3A E2 E1 GND 24V XIO 10HUB 0 4 8 5 2 6 7 2 7 0 7 2 1 1 Each switch has two 14 AWG 2 ...

Page 4: ...ed Trademark 2006 Honeywell International Inc 95 7717 2 C H Rev 02 06 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting f...

Reviews: