EXCEL 10 W7761A INPUT/OUTPUT DEVICE
65
74-2699
Table C4. Configuration Parameters (Left Continued).
Engineering Units:
English (Metric) or
Digital
State
or
Value
of
User Address
NvName
Field Name
States plus Range
State
Default
AIUpperLimit
nciEUConvrtRes
UpperLimitS7
degrees F -40 to 240
degrees C (-40 to 116)
0
DeltaC
nciDelta
deltacurrent
mA
0 to 256
0
DeltaCO2
nciDelta
deltaCO2
PPM 0 to 2000
0
DeltaH
nciDelta
deltahum
percent 0 to 163
0
DeltaP
nciDelta
deltapres
inw 0 to 32
kPa (0 to 7.97)
0
DeltaT1
nciDelta
deltatemp(0)
degrees F 0 to 256
degrees C (0 to 124)
0
DeltaT2
nciDelta
deltatemp(1)
degrees F 0 to 256
degrees C (0 to 124)
0
DeltaT3
nciDelta
deltatemp(2)
degrees F 0 to 256
degrees C (0 to 124)
0
DeltaT4
nciDelta
deltatemp(3)
degrees F 0 to 256
degrees C (0 to 124)
0
DeltaV
nciDelta
deltaVolt
0 to 10.5 volts
0
DO1FlSpeed
nciFloatConfig
DO0
seconds
0 to 900
90
DO2FlSpeed
nciFloatConfig
DO1
seconds
0 to 900
90
DO3FlSpeed
nciFloatConfig
DO2
seconds
0 to 900
90
DO4FlSpeed
nciFloatConfig
DO3
seconds
0 to 900
90
(continued)