EXCEL 10 W7761A INPUT/OUTPUT DEVICE
53
74-2699
Table C1. Input/Output Points (Left Continued).
Engineering Units:
English (Metric) or
Digital
State
or
Value
of
User Address
NvName
Field Name
States plus Range
State
Default
SrcDigIn2Sts
nvoRemoteDigIn(1)
DI2Value
0 to 255
0
nvoRemoteDigIn(1)
DI2State
Refer to the DI1State enumerated list
shown in the Eng. Units/States column.
ST_NUL
SrcDigIn3Sts
nvoRemoteDigIn(2)
DI3Value
0 to 255
0
nvoRemoteDigIn(2)
DI3State
Refer to the DI1State enumerated list
shown in the Eng. Units/States column.
ST_NUL
SrcDigIn4Sts
nvoRemoteDigIn(3)
DI4Value
0 to 255
0
nvoRemoteDigIn(3)
DI4State
Refer to the DI1State enumerated list
shown in the Eng. Units/States column.
ST_NUL
SrcHumidAI5
nvoRemoteHum(0)
percent
-163 to 163
0
SrcHumidAI6
nvoRemoteHum(1)
percent
-163 to 163
0
SrcPressAI5
nvoRemotePres(0)
inw -131.5 to 131.5
kPa (-32.768 to 32.767)
0
SrcPressAI6
nvoRemotePres(1)
inw -131.5 to 131.5
kPa (-32.768 to 32.767)
0
SrcTempAI1
nvoRemoteTemp(0)
degrees F -40 to 240
degrees C (-40 to 116)
0
SrcTempAI2
nvoRemoteTemp(1)
degrees F -40 to 240
degrees C (-40 to 116)
0
SrcTempAI3
nvoRemoteTemp(2)
degrees F -40 to 240
degrees C (-40 to 116)
0
SrcTempAI4
nvoRemoteTemp(3)
degrees F -40 to 240
degrees C (-40 to 116)
0
SrcVoltageAI
nvoRemoteVolt
Volts
0.0 to 10.5
0
)