background image

VR9105V, F AND VR9205V, F DIRECT IGNITION GAS CONTROL WITH INTEGRATED 1:1 REGULATOR

7

69-2471EF—01

IMPORTANT

Adjustments must be made in the final gas valve 
mounting position to avoid shift caused by the 
orientation.

• Turn offset adjustment screw counter clockwise 

to increase or clockwise to decrease outlet pres-
sure.

• Replace and tighten cap screw and pressure tap 

plugs.

Check Safety Shutdown 
Performance

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death, or property 
damage.

Perform the safety shutdown test any time work is 
done on a gas system.

NOTE: Read steps 1 through 7 before starting, and 

compare to the safety shutdown or safety 
lockout tests recommended for the direct ignition 
(DI) module. Where different, use the procedure 
recommended for the module.

1.

Turn off gas supply.

2.

Set thermostat or controller above room 
temperature to call for heat.

3.

Watch for ignition spark or for glow at hot surface 
igniter either immediately or following prepurge. 
See DI module specifications.

4.

Time the length of spark operation. See the DI mod-
ule specifications.

5.

After the module locks out, connect the plug to the 
coil connector and make sure no gas is flowing to 
the main burner.

6.

Set the thermostat below room temperature and 
wait one minute.

7.

Operate system through one complete cycle to 
make sure all controls operate properly.

MAINTENANCE

Under normal circumstances no maintenance or service 
is required.

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury, 
or death.

Do not disassemble the gas control; it contains no 
replaceable components. Attempted disassembly, 
repair, or cleaning can damage the control, 
resulting in gas leakage.

SERVICE

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death, or property 
damage.

Do not disassemble the gas control; it contains no 
replaceable components. Attempted disassembly, 
repair, or cleaning can damage the control, 
resulting in gas leakage.

CAUTION

Equipment Damage Hazard.
Can burn out thermostats or other 
components in the control string.

Never apply a jumper across (or short) the valve 
coil terminals, even temporarily.

IMPORTANT

These gas controls are shipped with protective 
seals over the inlet and outlet ports. Do not 
remove the seals until ready to install adapters 
or connect the piping.

After servicing, verify proper system operation.

If Main Burner Does Not 
Come On With Call For Heat

1.

Confirm the plug is connected to the coil connector.

2.

Adjust thermostat several degrees above room
temperature.

3.

Using an AC voltmeter, measure across terminals 1 
and 5 on the gas valve. See Fig. 7.

4.

If voltage is incorrect or not present, check control 
circuit for proper operation.

5.

If proper voltage is present, replace gas control.

Fig. 7. Coil connection.

PIN NUMBER   1    2    3     4    5

V1

V2

M32196

Summary of Contents for VR9105F

Page 1: ...uctions 69 2484EF Valve capacities are shown in Table 1 For suffix letter designation see Table 2 a Capacity based on 1000 Btu ft3 0 64 sp gr natural gas at 1 in wc pressure drop 37 3 MJ m3 0 64 sp gr natural gas at 0 25 kPa pressure drop b Minimum and Maximum regulation is at the max fire Minimum regulation at low fire is 18 KBtu h at 0 7 in WC outlet pressure a For detailed information about Ven...

Page 2: ...cial steps may be required to prevent nuisance shutdowns and control failure due to frequent cycling severe environmental conditions related to moisture corrosive chemicals dust or excessive heat These applications require Honeywell Combustion Engineering review contact your Honeywell Sales Representative for assistance Review the following conditions that can apply to your specific installation a...

Page 3: ... shielding should be provided by the appliance manufacturer verify proper air circulation is maintained when the appliance is installed INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for y...

Page 4: ...to Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe that is free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe...

Page 5: ...former and other controls as required 3 Connect the control circuit to the gas control terminals 4 Ensure combustion chamber is free of gas before startup 5 Adjust thermostat heat anticipator to the rating stamped on valve operator Electrical Connection VR9105V F and VR9205V F can be connected to any standard direct ignition control with 110 Vac output by using rectifier plug 45900441 039 or 24 Va...

Page 6: ...er than to the appliance being checked Other appliances must remain off with the pilots extinguished or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOME TER Make sure the plug is not connected to the coil connector before removing o...

Page 7: ...one complete cycle to make sure all controls operate properly MAINTENANCE Under normal circumstances no maintenance or service is required WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do not disassemble the gas control it contains no replaceable components Attempted disassembly repair or cleaning can damage the control resulting in gas leakage SERVICE WARNING F...

Page 8: ...formation below describes a typical control application but the specific controls used and the procedures outlined in your appliance manufacturer instructions can differ requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting sequence on this appliance is automatic do not attempt to manually light the main burner 2 If the appliance does not...

Page 9: ...sont illustrées dans le Tableau 1 Pour le suffixe de référence consulter le Tableau 2 a Capacité basée sur 1000 Btu pied3 gravité spécifique de 0 64 gaz naturel chute de pression de 1 po c e 37 3 MJ m3 gravité spécifique 0 64 gaz naturel et chute de pression de 0 25 kPa b Régulation minimum et maximum à combustion maximum La régulation minimum à basse combustion est de 18 KBtu h à une pression de ...

Page 10: ...pes spéciales sont requises pour éviter les coupures intempestives et les pannes de régulateur dues à des mises en marche et arrêts fréquents des conditions environnementales rigoureuses liées à l humidité des produits chimiques corrosifs de la poussière et une chaleur excessive Ces applications nécessitent d être révisées par le département d ingénierie de la combustion de Honeywell contacter le ...

Page 11: ...ante maximum autour du régulateur ne dépasse pas les conditions de température de fonctionnement du régulateur Si l appareil fonctionne à de très hautes températures utiliser un isolant une protection et assurer une circulation d air adéquate pour protéger le régulateur Une isolation ou une protection adéquate doit être fournie par le fabricant de l appareil vérifier qu une circulation d air adéqu...

Page 12: ...n ventilée Monter le régulateur suffisamment haut au dessus du bas de l armoire pour éviter l exposition à des déversements ou des éclaboussures d eau Veiller à ce que la température ambiante ne dépasse pas les valeurs de température ambiante nominales pour chaque organe Couvrir le régulateur à gaz si l appareil est nettoyé à l eau à la vapeur ou avec des produits chimiques et pour éviter l accumu...

Page 13: ...structions générales ci dessous Si ces instructions diffèrent de celles du fabricant de l appareil suivre celles du fabricant RÉGULATEUR À GAZ RÉGULATEUR À GAZ HORIZONTAL COLONNE DESCENDANTE ALIMENTATION EN GAZ TUYAU ALIMENTATION EN GAZ TUYAU ALIMENTATION EN GAZ TUYAU 76 MM 3 PO MINIMUM 76 MM 3 PO MINIMUM COLONNE MONTANTE RÉGULATEUR À GAZ HORIZONTAL COLONNE DESCENDANTE 76 MM 3 PO MINIMUM COLONNE M...

Page 14: ...pourraient causer un retour de flamme dans le vestibule de l appareil 4 Avec le brûleur principal allumé appliquer une solution savonneuse épaisse sur les joints du tuyau y compris les douilles et l entrée et la sortie du régulateur 5 Si une autre fuite est détectée éteindre le régulateur à gaz et serrer les joints et les raccords du tuyau 6 Remplacer la pièce si la fuite ne peut pas être réparée ...

Page 15: ... allumeur à incandescence immédiatement ou suite au prébalayage Voir les spécifications du module d allumage direct 4 Minuter la durée de l étincelle Voir les spécifications du module d allumage direct 5 Après le verrouillage du module connecter l obturateur au connecteur de serpentin et s assurer qu il n y a pas de débit de gaz vers le brûleur principal 6 Régler le thermostat à une température in...

Page 16: ... chauffage Les informations ci dessous décrivent une application typique mais les régulateurs spécifiques utilisés et les procédures décrites dans les instructions du fabricant de l appareil peuvent différer nécessitant des instructions spéciales Pour mettre l appareil en marche STOP Lire les avertissements ci dessus avant de continuer 1 La séquence d allumage de cet appareil est automatique ne pa...

Reviews: