Honeywell VR8215S Installation Instructions Manual Download Page 5

VR8215S,T TRADELINE DIRECT IGNITION COMBINATION GAS CONTROLS

5

34-00006EF—01

Fig. 4. Proper use of wrench on gas control.

Fig. 5. Top view of gas control.

Wiring

Follow the wiring instructions furnished by the appliance 

manufacturer, if available, or use the general instructions 

provided below. When these instructions differ from the 

appliance manufacturer, follow the appliance 

manufacturer instructions.

IMPORTANT

All wiring must comply with applicable electrical 

codes and ordinances. 

WARNING

Electrical Shock Hazard or Equipment Damage 

Hazard.

Can cause serious injury, death or equipment 

damage.

Disconnect power supply before making wiring 

connections to prevent electrical shock or 

equipment damage.

1.

Check the power supply rating on the gas control 

and make sure it matches the available supply. 

Install a transformer and other controls as required.

2.

Connect the control circuit to the gas control 

terminals. See Fig. 6 and 7.

3.

Adjust thermostat heat anticipator to 0.50A rating 

stamped on valve label.

 

Fig. 6. Typical wiring connections for 24 volt 

control in S87 Direct Ignition System.

Fig. 7. Typical wiring connections with 24 volt 

control in S89 Direct Ignition System.

STARTUP AND CHECKOUT

On-Off Switch

The on-off switch settings are as follows:

• OFF: Prevents main gas flow through the control.

M27669

M27670A

ON 

OFF

PRESSURE REGULATOR

ADJUSTMENT (UNDER 

CAP SCREW)

INLET

INLET 

PRESSURE

TAP 1/8 IN. 

NPT

OUTLET

ON/OFF SWITCH

OUTLET

PRESSURE

TAP 1/8 IN. 

NPT

24V

24V (GND)

S87B CONTROL MODULE

ALARM

VALVE

VALVE

GND

TEMPERATURE 

CONTROLLER

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 

PROTECTION AS REQUIRED.  

ALTERNATE LIMIT CONTROLLER LOCATION.

MAXIMUM IGNITER-SENSOR CABLE LENGTH:  3 ft. (0.9 m) OR LESS.

3A REPLACEABLE FUSE.

ALARM TERMINAL PROVIDED ON SOME MODELS.

M27697

L1

(HOT)

L2

1

2

1

2

3

DUAL VALVE

COMBINATION

GAS CONTROL

Q347 IGNITER-SENSOR

BURNER

4

4

5

IGNITER-SENSOR AND 

BURNER GROUND

3

5

ALARM, IF USED

WHITE
BLUE
BLACK
BLUE

HOT 

SURFACE

IGNITER-

SENSOR

VALVE

VALVE (GND)
24V

TH-W

24V (GND)

GND (BURNER)

S89C,G,J/S890C,G,J 

HOT SURFACE 

IGNITION CONTROL

L2

HSI

L1

HSI

LIMIT

CONTROLLER

BURNER 

GROUND

THERMOSTAT

OR CONTROLLER

DUAL VALVE 

COMBINATION

GAS CONTROL

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 

PROTECTION AS REQUIRED.  MAKE SURE L1 AND L2 ARE NOT 

REVERSED; THIS WOULD PREVENT FLAME DETECTION.

ALTERNATE LIMIT CONTROLLER LOCATION.

SEN TERMINAL AND Q354 FLAME SENSOR ON D MODELS ONLY.

M27628

L1

(HOT)

L2

VENT 

DAMPER PLUG

1

2

1

2

3

3

SEN

Q354 FLAME

SENSOR

Summary of Contents for VR8215S

Page 1: ...IFICATIONS Body Pattern Straight through see Table 1 for inlet and outlet size Electrical Ratings Voltage and Frequency 24 Vac 50 60 Hz Current Draw 0 5A Field Wiring 2 1 4 in spade quick connect terminals Capacity See Table 1 Conversion Use conversion factors in Table 2 to convert capacities for other gases Regulation Range See Table 7 Natural LP Gas Conversion Kits See Table 4 Approvals CSA Desi...

Page 2: ...et wet during normal cleaning procedures High Humidity or Dripping Water Dripping water can cause the control to fail Never install an appliance where water can drip on the control In addition high ambient humidity can cause the control to corrode and fail If the appliance is in a humid atmosphere make sure air circulation around the control is adequate to prevent condensation Also regularly check...

Page 3: ...r attempted repair may result in fire or explosion 5 Gas will leak if installed backwards CAUTION Equipment Damage Hazard Can burn out thermostat or transformer Applying a jumper across or shorting the valve coil terminals even temporarily can burn out the thermostat or transformer Follow the appliance manufacturers instructions if available otherwise use these instructions as a guide IMPORTANT Th...

Page 4: ...ed standards and practices 1 Use new properly reamed pipe that is free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe or tubing to the control If tubing is used obtain a tube to pipe coupling to connect the tubing to the control 3 Install a sediment trap in the supply line to the control See Fig 3 Ins...

Page 5: ... volt control in S89 Direct Ignition System STARTUP AND CHECKOUT On Off Switch The on off switch settings are as follows OFF Prevents main gas flow through the control M27669 M27670A ON OFF PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW INLET INLET PRESSURE TAP 1 8 IN NPT OUTLET ON OFF SWITCH OUTLET PRESSURE TAP 1 8 IN NPT 24V 24V GND S87B CONTROL MODULE ALARM VALVE VALVE GND TEMPERATURE CONTROLLER...

Page 6: ...eing checked Other appliances must remain off with the pilots extinguished or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOMETER Make sure the gas control is in the OFF position before removing outlet pressure tap plug to connect m...

Page 7: ...embly repair or cleaning can damage the control resulting in gas leakage Regular preventive maintenance is important in applications in the commercial cooking and agricultural and industrial industries that place a heavy load on system controls because In many such applications particularly commercial cooking the equipment operates 100 000 to 200 000 cycles per year Such heavy cycling can wear out...

Page 8: ...e heating appliance manufacturer The information below describes a typical control application but the specific controls used and the procedures outlined in your appliance manufacturer instructions can differ requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting sequence on this appliance is automatic do not attempt to manually light the ...

Page 9: ...VR8215S T TRADELINE DIRECT IGNITION COMBINATION GAS CONTROLS 9 34 00006EF 01 ...

Page 10: ...AS CONTROLS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2014 Honeywell International Inc 34 00006EF 01 M S 11 14 Printed in United States ...

Page 11: ...éro de modèle CARACTÉRISTIQUES Configuration du corps Passage direct voir le Tableau 1 pour la taille d entrée et de sortie Caractéristiques électriques Tension et fréquence 24 V c a 50 60 Hz Appel de courant 0 5 A Câblage sur site Bornes rapides à cosse de po 6 mm Capacité Voir le Tableau 1 Conversion Utiliser les facteurs de conversion du Tableau 2 pour convertir les capacités pour d autres gaz ...

Page 12: ...les n ont lieu que trois ou quatre fois par heure durant la saison de chauffage Pour les applications sur l année entière avec des cadences plus importantes le régulateur peut s user plus rapidement Effectuer une vérification mensuelle Nettoyage à l eau ou à la vapeur Si le régulateur se mouille le remplacer Si l appareil est susceptible d être lavé à l eau ou à la vapeur protéger couvrir le régul...

Page 13: ...ou d explosion Peut causer des dégâts et des blessures graves voire mortelles Respecter ces avertissements avec précision 1 Débrancher l alimentation avant le câblage pour éviter les chocs électriques et les dégâts de l équipement 2 Pour éviter une accumulation dangereuse de gaz combustible couper l alimentation au niveau de la vanne de service de l appareil avant de commencer l installation et ef...

Page 14: ...uivre ces instructions Placer le régulateur de gaz dans une zone bien ventilée Monter le régulateur suffisamment haut au dessus du bas de l armoire pour éviter l exposition à des déversements ou des éclaboussures d eau Veiller à ce que la température ambiante ne dépasse pas les valeurs de température ambiante nominales pour chaque organe Couvrir le régulateur à gaz si l appareil est nettoyé à l ea...

Page 15: ...s dégâts de l équipement 1 Vérifier la tension électrique du régulateur et s assurer qu elle correspond à l alimentation disponible Installer un transformateur et d autres dispositifs si nécessaire 2 Brancher le circuit du régulateur sur les bornes du régulateur Voir les Fig 6 et 7 3 Régler l anticipateur de chaleur du thermostat à 0 50 A la valeur indiquée sur l opérateur de la vanne Dimension de...

Page 16: ...achées qui pourraient causer un retour de flamme dans le vestibule de l appareil 4 Avec le brûleur principal allumé badigeonner les joints du tuyau y compris les douilles et l entrée et la sortie du régulateur avec une solution savonneuse épaisse 5 Si une autre fuite est détectée éteindre le régulateur à gaz et serrer les joints et les raccords du tuyau 6 Remplacer la pièce si la fuite ne peut pas...

Page 17: ...ction de la pression nominale de l appareil Voir le Tableau 7 pour la pression de sortie nominale réglée en usine et la plage de réglage a Retirer la vis d obturation de réglage du régulateur de pression b Avec un tournevis tourner la vis de réglage interne de pression élevée Fig 5 dans le sens des aiguilles d une montre pour l augmenter ou dans le sens contraire des aiguilles d une montre pour ré...

Page 18: ... dans la documentation du fabricant de l appareil La fréquence de l entretien doit être déterminée pour chaque application sur une basse individuelle Voici quelques considérations à prendre en compte Fréquence des cycles Les appareils dont les cycles peuvent avoir lieu 20 000 fois par an doivent être vérifiés mensuellement Utilisation intermittente Les appareils utilisés de manière saisonnière doi...

Page 19: ...uvent différer nécessitant des instructions spéciales Pour mettre l appareil en marche ARRÊTER Lire les avertissements avant de continuer 1 La séquence d allumage de cet appareil est automatique ne pas tenter d allumer le brûleur prin cipal manuellement 2 Si l appareil de chauffage ne s allume pas lorsque le thermostat est réglé à plusieurs degrés au dessus de la température de la pièce régler le ...

Page 20: ... de régulation et d automatisation Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com Marque de commerce déposée aux États Unis 2014 Honeywell International Inc Tous droits réservés 34 00006EF 01 M S 11 14 Imprimé aux États Unis ...

Reviews: