Honeywell VR4200A Manual Download Page 6

68-0046—4

6

VR8200, VR4200

INSTALLATION

3. Insert bushing in gas control and thread pipe carefully

into bushing until tight.

Complete the instuctions below for piping, installing

control, connecting pilot trubing, thermocouple and wiring.
Make certain the leak test you perform on the control after
completing the installation includes leak testing the adapters
and screws. If you use a wrench on the valve after flanges are
installed, use the wrench only on the flange, not on the
control.

USING ADAPTERS TO SOLVE SWING RADIUS
PROBLEMS

In some field service applications, it is difficult or

impossible to thread the gas control onto the gas supply
pipe because of space limitations. Usually this problem can
be resolved by using an adapter. The adapter is installed on
the end of the supply pipe in place of the gas control,
following the same precautions and instructions that are
used for installing the gas control. After the adapter is
installed, the gas control is attached to the adapter as
outlined above. Note that using an adapter increases the
overall length of the gas control.

CHOOSE GAS CONTROL LOCATION

Do not locate the gas control where it may be affected by

steam cleaning, high humidity, dripping water, corrosive
chemicals, dust or grease accumulation, or excessive heat. To
ensure proper operation, follow these guidelines:

• Locate gas control in a well-ventilated area.
• Mount gas control high enough above cabinet bottom

to avoid exposure to flooding or splashing water.

• Ensure the ambient temperature does not exceed the

ambient temperature ratings for each component.

• Cover gas control if the appliance is cleaned with

water, steam, or chemicals to avoid dust and grease
accumulation.

• Avoid locating gas control where exposure to corro-

sive chemical fumes or dripping water are likely.

Locate the gas control in the appliance vestibule on the

gas manifold. In replacement applications, locate the gas
control in the same location as the old gas control.

Install Piping to Gas Control

All piping must comply with local codes and ordi-

nances or with the National Fuel Gas Code (ANSI  Z223.1
NFPA No. 54), whichever applies. Tubing installation must
comply with approved standards and practices.

1. Use new, properly reamed pipe free from chips. If

tubing is used, ensure the ends are square, deburred and clean.
All tubing bends must be smooth and without deformation.

2. Run pipe or tubing to the gas control. If tubing is

used, obtain a tube-to-pipe coupling to connect the tubing
to the gas control.

3. Install sediment trap in the supply line to the gas

control. See Fig. 6.

Install Gas Control

1. Mount the gas control 0-90 degrees, in any direction,

from the upright position of the gas control knob, including
vertically.

2. Mount the gas control so gas flow is in the direction

of the arrow on the bottom of the gas control.

3. Thread pipe into gas control. Do not thread pipe too far.

Valve distortion or malfunction can result if the pipe is inserted
too deeply into the gas control. Refer to Table 4.

4. Apply a moderate amount of good quality pipe com-

pound (Do not use Teflon tape) to pipe only, leaving two end
threads bare. On LP installations, use compound resistant to
LP gas. (See Fig. 7.)

Fig. 7—Use moderate amount of pipe compound.

Fig. 6—Install sediment trap.

GAS
CONTROL

GAS
CONTROL

HORIZONTAL

DROP

PIPED
GAS
SUPPLY

PIPED
GAS
SUPPLY

3 INCHES
[76]
MINIMUM

3 INCHES
[76]
MINIMUM

RISER

GAS
CONTROL

TUBING
GAS
SUPPLY

HORIZONTAL

DROP

3 INCHES
[76]
MINIMUM

RISER

M3077

2

1

2

2

1

2

ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.

CAUTION:  SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING
END CAP TO PREVENT GAS FROM FILLING THE WORK AREA.  TEST 
FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.

TABLE 4—NPT PIPE THREAD LENGTH IN INCHES.

Maximum Depth

Pipe

Thread Pipe

Pipe can be Inserted

Size

This Amount

into Control

3/8

9/16

3/8

1/2

3/4

1/2

3/4

13/16

3/4

TWO IMPERFECT 
THREADS

GAS CONTROL

THREAD PIPE THE AMOUNT 
SHOWN IN TABLE FOR 
INSERTION INTO GAS CONTROL 

APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).

M3075A

PIPE

Summary of Contents for VR4200A

Page 1: ... be pushed down only in PILOT position All adjustments wiring connections and pilot out let are accessible from the top of the gas control Compact size Straight through body pattern right angle adapters available for inlet and outlet 1 2 in inlet and 1 2 inch outlet adapters available for 3 8 or 3 4 inch Adjustable servo regulator effectively maintains almost constant gas output pressure under wid...

Page 2: ...n request POWER UNIT Hold in current 300 mA maximum Drop out current 250 to 90 mA THERMOCOUPLE Nominal output 30 mV 0 018 ohms Open Circuit Turndown Voltage 2 mV ELECTRICAL CONNECTIONS 2 1 4 inch male quick connects Two convenience terminals on top of control optional Terminal block color coded beige THERMOSTAT HEAT ANTICIPATOR SETTING VR4200 0 1A VR8200 0 5A TYPE OF GAS VR8200 and VR4200 set up f...

Page 3: ...as 5 5 as 1 37 as 8 12 2 to 3 ordereda ordereda ordereda ordereda Full Rate Full Rate Full Rate Full Rate 10 2 5 8 to 12 2 to 3 VR8200H Slow Natural 3 5 0 9 3 to 5 0 7 to 1 2 3 to 5 0 7 to 1 2 VR4200H opening LP 10 0 2 5 8 to 12 2 to 3 8 to 12 2 to 3 VR8200J Delayed and Natural 3 5 0 9 3 to 5 0 7 to 1 2 3 to 5 0 7 to 1 2 Slow opening LP 10 0 2 5 8 to 12 2 to 3 8 to 12 2 to 3 a Step pressure not ad...

Page 4: ...ment damage 2 To avoid dangerous accumulation of fuel gas turnoffgassupplyattheapplianceservicevalve before starting installation and perform Gas Leak Test after completion of installation 3 Do not bend pilot tubing at gas control or pilot burner after compression fitting has been tight ened or gas leakage at the connection may result 4 Always install sediment trap in gas supply line to prevent co...

Page 5: ...ING TERMINALS 2 INLET PRESSURE TAP PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW PILOT OUTLET PILOT ADJUSTMENT UNDER CAP SCREW GAS CONTROL KNOB M2916 RED RESET BUTTON THERMOCOUPLE CONNECTION SCREW TERMINALS 2 for LP regulator and 3 5 in wc 0 9 kPa for natural gas regulator 6 Check the regulator setting either with a manometer or by clocking the gas meter Refer to Startup and Check out section 7 In...

Page 6: ... gas control in the same location as the old gas control Install Piping to Gas Control All piping must comply with local codes and ordi nances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubingisused ensuretheendsaresquare deburredandclean All tubi...

Page 7: ...ntroluntilitbottoms Whileholdingtubingall the way in slide compression fitting into place and engage threads turn until finger tight Then tighten one more turn with wrench Do not overtighten Refer to Fig 9 5 Connect the other end of tubing to pilot burner according to pilot burner manufacturer instructions 7 68 0046 4 5 Remove seals over gas control inlet and outlet if necessary 6 Connect pipe to ...

Page 8: ...ctions furnished by the appli ance manufacturer if available or use the general instruc tions provided below Where these instructions differ from the appliance manufacturer follow the appliance manufacturer instructions All wiring including 1 4 in quick connect terminals must comply with applicable electrical codes and ordi nances Disconnect power supply before making wiring con nections to preven...

Page 9: ... DEATH 1 Do not force the gas control knob Use only your hand to push down the reset button or turn the gas control knob Never use any tools 2 If the gas control knob or reset button will not operate by hand or if the reset button stays depressed after it is released the gas control should be replaced by a qualified service technician GAS CONTROL KNOB SETTINGS The gas control knob has three settin...

Page 10: ...t rating stamped on the appliance nameplate or manufacturer recom mended burner orifice pressure for the size orifice s used Assure the main burner primary air supply is properly adjusted for complete combustion refertotheappliancemanufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING THE GAS METER Assure that the only gas flow through the meter is that of the appliance being tested Assure ...

Page 11: ... Standard NATURAL 1 2 1 7 0 9 0 7 1 2 Slow LP 2 9 3 9 2 7 2 0 3 0 opening Step NATURAL 1 2 1 7 0 2 0 9 0 7 1 2 opening LP 2 9 3 9 0 9 2 7 2 0 3 0 CHECK SAFETY SHUTDOWN PERFORMANCE WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Perform the safety shutdown test any time work is done on a gas system 1 Place gas control knob in PILOT position Main burner should go of...

Page 12: ...thepilotisburning Theservopressure regulator monitors outlet pressure to provide an even main burner gas flow Loss of power closes the automatic valves butleavesthepilotlit readytoreturntonormalservicewhen power is restored Loss of pilot flame or flame too small to reliably light the main burner closes the safety shutoff valve and the second automatic valve The gas control must be manually reset G...

Page 13: ... the gas control outlet This decreases gas pressure under the second automatic valve diaphragm and repositions the valve disc further from the seat Thus flow of gas through the second automatic valve is increased and outlet pres sure rises to the desired level Slow Opening Pressure Regulation VR8200H and VR4200H Delayed and Slow opening Regulation VR8200J Slow opening gas controls function the sam...

Page 14: ... closes and is held closed by spring pressure on the diaphrahm When Pilot Flame Goes Out When pilot flame goes out or is too small to reliably light the main burner thermocouple output drops below the power unit hold in valve The power unit drops out closing the safety valve and stopping all gas flow through the con trol With the loss of outlet pressure the second automatic valve closes and is hel...

Page 15: ...ot burner flame adjustment Refer to the Adjust the Pilot Burner Flame section 3 Check the wiring between the thermocouple and the gas control valve operator 4 Assure thermocouple connection to the power unit is tightened 1 4 turn beyond finger tight 5 If pilot burner flame still goes out measure the open and closed thermocouple output voltage Compare it to the acceptablerangechartsinthethermocoupl...

Page 16: ...specific controls used and the procedures outlined by the manufacturer of your appliancemaydiffer andrequirespecialinstructions TO LIGHT THE PILOT BURNER STOP Read the safety information in the WARNING This appliance has a pilot burner which must be lit by hand If the pilot flame has gone out follow these instruc tions exactly 1 Set the thermostat to the lowest setting and shut off electric power ...

Reviews: