Honeywell VR4200A Manual Download Page 12

68-0046—4

12

VR8200, VR4200

MAINTENANCE • OPERATION

Maintenance

Regular preventive maintenance is important in applica-

tions that place a heavy load on system controls such as in
the commercial cooking and agricultural and industrial
industries because:

• In many such applications, particularly commercial

cooking, the equipment operates 100,000-200,000
cycles per year. Such heavy cycling can wear out the
gas control in one to two years.

• Exposure to water, dirt, chemicals and heat can dam-

age the gas control and shut down the control system.

The maintenance program should include regular check-

out of the gas control, see the Startup and Checkout section,
and the control system as described in the appliance manufac-
turer literature.

Maintenance frequency must be determined individually

for each application. Some considerations are:

• Cycling frequency. Appliances that may cycle 120,000

times annually should be checked monthly.

• Intermittent use. Appliances that are used seasonally

should be checked before shutdown and again before
the next use.

• Consequence of unexpected shutdown. Where the cost

of an unexpected shutdown would be high, the system
should be checked more often.

• Dusty, wet, or corrosive environment. Since these

environments can cause the gas control to deteriorate
more rapidly, the system should be checked more
often.

Gas valves exposed to high ammonia conditions, i.e.,

those used in greenhouses or animal barns, may fail in one or
two years. Contact your Honeywell sales representative to
request a gas valve with corrosion resistant construction.

The gas control should be replaced if:
• It does not perform properly on checkout or trouble-

shooting.

• The gas control knob is hard to turn or push down, or

it fails to pop back up when released.

• The gas control is likely to have operated for more

than 200,000 cycles.

Operation

The VR8200, VR4200 gas controls provide 3-position

(OFF-PILOT-ON) manual control of gas flow. The OFF
position prevents pilot and main burner gas flow. The
PILOT position allows pilot burner gas flow only. The ON
position allows pilot burner and main burner gas flow under
control of the thermostat and the two automatic valves.

When the thermostat calls for heat, the first automatic

valve and the second automatic valve operator open.  The
second automatic valve diaphragm, controlled by the servo
pressure regulator, opens and adjusts gas flow as long as the
system is powered and the pilot is burning. The servo pressure
regulator monitors outlet pressure to provide an even main
burner gas flow. Loss of power closes the automatic valves,
but leaves the pilot lit, ready to return to normal service when
power is restored. Loss of pilot flame or flame too small to
reliably light the main burner, closes the safety shutoff valve
and the second automatic valve. The gas control must be
manually reset. Gas control operation is described in more
detail below.

VALVE POSITION DURING THERMOSTAT OFF
CYCLE

The valve is positioned as shown in Fig. 14 when the:
• manual gas control knob is in the ON position.
• pilot burner is lit.
• thermostat is not calling for heat.
The power unit holds the safety shutoff valve disc off its

seat,  so gas can flow into the control.  Pilot gas flows
through a port in the bushing around the reset button shaft
to the pilot burner. The first automatic valve is closed. The
second automatic valve operator is de-energized, closing
the channel to the pressure regulator, and opening a channel

to the underside of the second automatic valve diaphragm.
The combination of spring pressure under the second auto-
matic valve diaphragm and the lack of outlet pressure hold
the diaphragm firmly closed.  Main burner gas flow is
blocked by both automatic valves.

WHEN THERMOSTAT CALLS FOR HEAT

The gas control allows pilot and main burner gas flow

during the thermostat ON cycle, as shown in Fig. 15. When
the thermostat calls for heat, the first automatic valve and the
second automatic valve operator are energized. The first
automatic valve opens, and the second automatic valve
operator valve disc is lifted off its seal.  This diverts gas flow
from the automatic valve diaphragm, and causes a reduction
of pressure on the underside of this diaphragm. The reduced
pressure on the bottom of the automatic valve diaphragm
repositions the diaphragm downward away from the valve
seat, allowing main burner gas flow.

Standard Opening Pressure Regulation (VR8200A,M
and VR4200A,M)

During the ON cycle, the servo pressure regulator pro-

vides close control of outlet pressure, even if inlet pressure
and flow rate vary widely. Any outlet pressure change is
immediately reflected back to the pressure regulator dia-
phragm, which repositions to change the flow rate through
the regulator valve and, thus, through the diaphragm-oper-
ated automatic valve.

If outlet pressure begins to rise, the pressure regulator

diaphragm moves slightly higher, allowing less gas flow to
the gas control outlet. This increases gas pressure under the
automatic valve and repositions the valve disc closer to the

Summary of Contents for VR4200A

Page 1: ... be pushed down only in PILOT position All adjustments wiring connections and pilot out let are accessible from the top of the gas control Compact size Straight through body pattern right angle adapters available for inlet and outlet 1 2 in inlet and 1 2 inch outlet adapters available for 3 8 or 3 4 inch Adjustable servo regulator effectively maintains almost constant gas output pressure under wid...

Page 2: ...n request POWER UNIT Hold in current 300 mA maximum Drop out current 250 to 90 mA THERMOCOUPLE Nominal output 30 mV 0 018 ohms Open Circuit Turndown Voltage 2 mV ELECTRICAL CONNECTIONS 2 1 4 inch male quick connects Two convenience terminals on top of control optional Terminal block color coded beige THERMOSTAT HEAT ANTICIPATOR SETTING VR4200 0 1A VR8200 0 5A TYPE OF GAS VR8200 and VR4200 set up f...

Page 3: ...as 5 5 as 1 37 as 8 12 2 to 3 ordereda ordereda ordereda ordereda Full Rate Full Rate Full Rate Full Rate 10 2 5 8 to 12 2 to 3 VR8200H Slow Natural 3 5 0 9 3 to 5 0 7 to 1 2 3 to 5 0 7 to 1 2 VR4200H opening LP 10 0 2 5 8 to 12 2 to 3 8 to 12 2 to 3 VR8200J Delayed and Natural 3 5 0 9 3 to 5 0 7 to 1 2 3 to 5 0 7 to 1 2 Slow opening LP 10 0 2 5 8 to 12 2 to 3 8 to 12 2 to 3 a Step pressure not ad...

Page 4: ...ment damage 2 To avoid dangerous accumulation of fuel gas turnoffgassupplyattheapplianceservicevalve before starting installation and perform Gas Leak Test after completion of installation 3 Do not bend pilot tubing at gas control or pilot burner after compression fitting has been tight ened or gas leakage at the connection may result 4 Always install sediment trap in gas supply line to prevent co...

Page 5: ...ING TERMINALS 2 INLET PRESSURE TAP PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW PILOT OUTLET PILOT ADJUSTMENT UNDER CAP SCREW GAS CONTROL KNOB M2916 RED RESET BUTTON THERMOCOUPLE CONNECTION SCREW TERMINALS 2 for LP regulator and 3 5 in wc 0 9 kPa for natural gas regulator 6 Check the regulator setting either with a manometer or by clocking the gas meter Refer to Startup and Check out section 7 In...

Page 6: ... gas control in the same location as the old gas control Install Piping to Gas Control All piping must comply with local codes and ordi nances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubingisused ensuretheendsaresquare deburredandclean All tubi...

Page 7: ...ntroluntilitbottoms Whileholdingtubingall the way in slide compression fitting into place and engage threads turn until finger tight Then tighten one more turn with wrench Do not overtighten Refer to Fig 9 5 Connect the other end of tubing to pilot burner according to pilot burner manufacturer instructions 7 68 0046 4 5 Remove seals over gas control inlet and outlet if necessary 6 Connect pipe to ...

Page 8: ...ctions furnished by the appli ance manufacturer if available or use the general instruc tions provided below Where these instructions differ from the appliance manufacturer follow the appliance manufacturer instructions All wiring including 1 4 in quick connect terminals must comply with applicable electrical codes and ordi nances Disconnect power supply before making wiring con nections to preven...

Page 9: ... DEATH 1 Do not force the gas control knob Use only your hand to push down the reset button or turn the gas control knob Never use any tools 2 If the gas control knob or reset button will not operate by hand or if the reset button stays depressed after it is released the gas control should be replaced by a qualified service technician GAS CONTROL KNOB SETTINGS The gas control knob has three settin...

Page 10: ...t rating stamped on the appliance nameplate or manufacturer recom mended burner orifice pressure for the size orifice s used Assure the main burner primary air supply is properly adjusted for complete combustion refertotheappliancemanufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING THE GAS METER Assure that the only gas flow through the meter is that of the appliance being tested Assure ...

Page 11: ... Standard NATURAL 1 2 1 7 0 9 0 7 1 2 Slow LP 2 9 3 9 2 7 2 0 3 0 opening Step NATURAL 1 2 1 7 0 2 0 9 0 7 1 2 opening LP 2 9 3 9 0 9 2 7 2 0 3 0 CHECK SAFETY SHUTDOWN PERFORMANCE WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Perform the safety shutdown test any time work is done on a gas system 1 Place gas control knob in PILOT position Main burner should go of...

Page 12: ...thepilotisburning Theservopressure regulator monitors outlet pressure to provide an even main burner gas flow Loss of power closes the automatic valves butleavesthepilotlit readytoreturntonormalservicewhen power is restored Loss of pilot flame or flame too small to reliably light the main burner closes the safety shutoff valve and the second automatic valve The gas control must be manually reset G...

Page 13: ... the gas control outlet This decreases gas pressure under the second automatic valve diaphragm and repositions the valve disc further from the seat Thus flow of gas through the second automatic valve is increased and outlet pres sure rises to the desired level Slow Opening Pressure Regulation VR8200H and VR4200H Delayed and Slow opening Regulation VR8200J Slow opening gas controls function the sam...

Page 14: ... closes and is held closed by spring pressure on the diaphrahm When Pilot Flame Goes Out When pilot flame goes out or is too small to reliably light the main burner thermocouple output drops below the power unit hold in valve The power unit drops out closing the safety valve and stopping all gas flow through the con trol With the loss of outlet pressure the second automatic valve closes and is hel...

Page 15: ...ot burner flame adjustment Refer to the Adjust the Pilot Burner Flame section 3 Check the wiring between the thermocouple and the gas control valve operator 4 Assure thermocouple connection to the power unit is tightened 1 4 turn beyond finger tight 5 If pilot burner flame still goes out measure the open and closed thermocouple output voltage Compare it to the acceptablerangechartsinthethermocoupl...

Page 16: ...specific controls used and the procedures outlined by the manufacturer of your appliancemaydiffer andrequirespecialinstructions TO LIGHT THE PILOT BURNER STOP Read the safety information in the WARNING This appliance has a pilot burner which must be lit by hand If the pilot flame has gone out follow these instruc tions exactly 1 Set the thermostat to the lowest setting and shut off electric power ...

Reviews: