Installation Instructions Viewguard DUAL / AM FAI

1.

Introduction

2.

Installation Guide line

3.

Installation

The Viewguard DUAL motion detector comprises two systems that operate fully
independently: Passive infrared detector plus Microwave detector. The functioning principle
of the detector is based on the intelligent linkage of a passive infrared sensor and
microwave. This type of linking renders the detectors particularly insensitive to air and
thermal turbulences. (Microwave module see Fig.

).

They are delivered with the following main features:

Volumetric mirror optic

, see Fig.

, (only 033440/450)

FAI (First Alarm Indication):

Selectable range and sensitivity
Memory function
Selectable range and sensitivity
Self-test (only 033440

)

Monitoring of operating voltage
Tamper and back tamper

Maximum sensitivity is achieved when mounted crosswise to the horizontal detection
zones of the PIR sensors. Therefore, select a mounting site that runs crosswise to the
expected direction of motion. (See Fig.

).

Minimum distance to ceiling: 2 cm

* Mounting above radiators
* Mounting near air discharge openings (e.g. air conditioning systems)
* Direct sunlight
* Mounting near to fluorescent lamps
* Mounting near to light bulbs

(see Fig. 1)

If necessary, break the seal with a small screwdriver or similar object and pull downward

. Press the notch (at the bottom in the middle, see Fig.

) slightly inward

and

press off the front of the housing

. Lift off the housing front

.

• 0° Vertical

see Fig. 5/1

Fig.

• Vertical at a 3° downward angle

see

5/2

Fig.

• Horizontal at a 45° angle to the left or right

see

5/3

Fig.

• Corner mounting

see

5/4

Fig.

The detector can be mounted by using the optional swivel bracket (033390 or 033588, see
"Accessories").

(See

4)

For surface mounted wiring
For flush mounted wiring
For use with adjusting hinge
For strain relief with cable strap

3-

(see Fig. 3-

, Fig. 6)

2-

Microwave sensor inactive in the "disarmed" state.

When multiple detector on a single zone, Indicate the first detector in alarm

/450

6-A

2-

4-

Fig.

4-

Fig.

4-

Fig.

4-

Fig.

(see Fig. 4)

Required for installation according to DIN CLC/TS 50131-2-4 grade 3.
The backtamper can be used if installed as illustrated in Fig. 5/1, 5/2, 5/3a, 5/3b and 5/4.

Tappet for backtamper. Remove the pin at the tappet, if the backtamper is
being used (see illustration)
Protective cover for back-tamper (on the rear). Remove, when mounting as
per Fig. 5/3a or 5/4

���

���

���

���

���

���

���

���

���

���

���

���

-
-

-

-
-
-
-
-
-

Avoid:

Open housing

Mounting options

Screw on position

Cabling, strain relief

A
B, C
C
D

Anti-masking up to 30 cm from the detector

-

Backtamper

a

b

4.2

Easy Logic operating mode without FAI function

The control signals "Walk test", "disarmed" and "FAI" are not connected. In this operating
mode no alarm indication, no FAI function and no memory is available.

The DIP-switches S4, S5 and S6 must be in position "ON".

The Microwave sensor is always active.

Detector 1

F

Detector 2

Detector 3

Detector 20

F

F

F

Function of inputs:

(Pull-up resistors in the detector)

Function

a) armed

b) disarmed

c) walk test, clear alarm indication

High

Low

Inputs

walk test "T"

arm/disarm "U"

High

High

Low

Low

4.1

Viewguard operating mode with FAI function

(FAI = irst larm ndication)

The FAI connections "F" of all detectors are connected to one another. A connection to the
control panel is not required. The LED flashes on the detector that triggers first, the LED
light on the subsequently triggered detectors (see 6. "LED indication").

F

A

I

FAI logic:

Close housing

Apply operating voltage

Walk test in Easy Logic mode

See Fig. 1 in reverse order. Ensure that the housing is closed correctly and locked into
position. Do not insert the seal to lock the housing until installation is completed

After applying the operating voltage, the detector automatically performs an initialisation.
Both LEDs flash (see 6.).

. After max.

60 seconds the detector is ready for operation. After this period, do not change anything in
the close vicinity (up to 50 cm) that may influence the reflected light.

The detector is automatically in

for approx.

after initialising is

completed. Conduct the walk test within this time period. LED indication see 6.

The detector is operationally ready after the 10 minutes have expired.

Do not enter the Anti-Mask range during initialisation

walk test mode

10 minutes

5.

Setting

DIP-switches:

see Fig.

3-

���

S3

Sensitivity

ON

normal

OFF

high

S1

S2

Range

OFF

OFF

8 m

ON

OFF

11 m

OFF

ON

13 m

ON

ON

15 m

S4

S6

Operating mode

(

)

Anti-Mask only 033440

/

ON

ON

Easy Logic mode only (see 4.2)

ON

OFF

Viewguard mode with FAI

OFF

OFF

Viewguard mode with FAI

OFF

ON

450

Anti-Mask always active

Anti-Mask always active

Anti-Mask inactive in "armed" state

N.A.

S5

Fault/Cover

ON

do not save

OFF

save

Memory:

Do not save:

Save:

Fault/cover signal is automatically cleared after
elimination of the fault/cover.

Not possible in Easy Logic mode!

Fault/cover signal remains saved in the detector
until it is cleared via control panel.

4.

Connection diagram

Installation Instructions

Viewguard Series DUAL

GB

Fault

Tamper

Alarm

T
U
F

-
+

Fault

Alarm

Tamper

Walk test

0 V
+12 V DC

Spare terminals for

end of line resistors

arm/disarm
FAI

Fault

Tamper

Alarm

If the control panel has no fault input,
the "Alarm" and "Fault" outputs can
be connected in series.

PIR and MW operate automatically
with the same range.

Summary of Contents for Viewguard DUAL AM FAI

Page 1: ...E F NL Installation Instructions Instrucciones de instalación Notice d installation Installatievoorschriften GB E F Page 2 Página 4 Page 6 NL Kant 8 Fig 1 Fig 3 Fig 4 Fig 6 2 5m 5m 10m 15m 0m 0 10 20 30 40 10 20 30 40 0m 9m 9m 5m 10m 15m 0m 0 Fig 5 1 A C B D b A B D C a a DUAL AM FAI DUAL FAI Fig 5 0 45 45 5 1 5 2 5 3 5 4 a b c ...

Page 2: ...amper a b 4 2 Easy Logic operating mode without FAI function The control signals Walk test disarmed and FAI are not connected In this operating mode no alarm indication no FAI function and no memory is available The DIP switches S4 S5 and S6 must be in position ON The Microwave sensor is always active Detector 1 F Detector 2 Detector 3 Detector 20 F F F Function of inputs Pull up resistors in the ...

Page 3: ...g 033391 Seal Swivel range Horizontal Vertical 4 up to 8 PU 20 piece 20 033440 033450 Viewguard DUAL AM FAI DIN CLC TS 50131 2 4 grade 3 033441 033451 Viewguard DUAL FAI DIN CLC TS 50131 2 4 grade 2 The detectors Viewguard DUAL AM FAI Item no 033440 033450 and Viewguard DUAL FAI Item no 033441 033451 when used as intended comply with the basic require ments of Article 3 of the R TTE TheEUconformit...

Page 4: ...temas que funcionan de forma totalmente independiente Detector pasivo de infrarrojos más detector de microondas El principio de funcionamiento del detector se basa en la conexión inteligente de un sensor de infrarrojos pasivo y microondas Este tipo de conexión hace que los detectores sean especialmente insensibles a las turbulencias de aire y térmicas Módulo de microondas véase la ilust 3 Dispone ...

Page 5: ...ción anti enmascaramiento W W W 8 Accesorios 9 Conformidad CE 033390 033588 Juegoderótulasparamontajeenparedyesquina 033391 Sello Rótula de montaje Alcance de giro Horizontal 20 Vertical 4 hasta 8 PU 20 unidades LadeclaracióndeconformidadUEpuededescargarseen 033440 033450 Viewguard DUAL AM FAI CLC TS 50131 2 4 Grado 3 033441 033451 Viewguard DUAL FAI CLC TS 50131 2 4 Grado 2 Los detectores Viewgua...

Page 6: ...mment la détection infrarouge passif et la détection hyperfréquence Le principe de fonctionnement du détecteur repose sur la liaison intelligente entre la détection infrarouge passif et la détection hyperfréquence Ce type de liaison garantit l insensibilité des détecteurs aux mouvements d air et aux variations de température module à hyper fréquence voir Fig 3 Ces derniers présentent les caractéri...

Page 7: ...ype de relais NF Ouvert en cas de défaut Contact d autoprotection Pouvoir de coupure 15 Vcc 0 1 A Résistance interne 10 Type de contact NF Ouvert en cas d autoprotection Catégorie de protection selon EN 60529 IP 30 Température de fonctionnement 10 C à 55 C Température de stockage 25 C à 70 C Dimensions l x h x p 64 x 158 x 48 mm Couleur Blanc semblable à RAL 9010 Fonction anti masque W W W 8 Acces...

Page 8: ... systemen die volledig onafhankelijk van elkaar functioneren Een passief infraroodmelder en een microgolfmelder De werking van de melder is gebaseerd op de intelligente koppeling van een passief infraroodsensor en microgolven Door deze combinatie zijn de melders bijzonder ongevoelig voorluchtturbulentieofthermischeturbulentie microgolfmodule zieafb 3 Deze beschikken over de volgende hoofdeigenscha...

Page 9: ...geuitgang Max contactbelasting 15 V DC 0 1 A Interne weerstand 10 Status open in geval van een sabotage Beschermklasse conform EN 60529 IP 30 Milieuklasse conform VdS II Bedrijfstemperatuur 10 C tot 55 C Opslagtemperatuur 25 C tot 70 C Afmetingen B x H x D 64 x 158 x 48 mm Kleur wit vergelijkbaar met RAL 9010 Anti masking functie W W W 8 Accessoires 9 EU conformiteit 033390 Verstelbare 033588 voor...

Page 10: ...10 ...

Page 11: ...11 ...

Page 12: ...P01715 10 007 00 24 10 2007 2007 Novar GmbH ...

Reviews: