Honeywell Velociti Series Installation And Maintenance Instructions Download Page 4

C0160-00

FIGURE 9. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A

1.  To select Class A, remove the two shunts from the “A/B select” positions.
2.   To use a common power supply between multiple MMI-6SF modules, connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent 

MMI-6SF module.

FIGURE 10. RELAY CONTROL MODULE USED TO DISCONNECT A POWER SUPPLY

C0248-00

  

I56-2742-009 

 

 7/1/2022

Summary of Contents for Velociti Series

Page 1: ...ICATIONS Normal Operating Voltage 15 32VDC Standby Current 2 3 mA 24 V Alarm Current 40 mA assumes all six LEDs solid on Temperature Range 32ºF to 120ºF 0ºC to 49ºC Humidity 10 to 85 Non condensing Dimensions 6 8 H x 5 8 W x 1 0 D Accessories CHS 6 Chassis MBB 6 Cabinet MBB 2 Cabinet CAB 4 Series Cabinets CAB 3 Series Cabinets Wire Gauge 12 18 AWG Maximum IDC Wiring Resistance 25 Ohms External Pow...

Page 2: ...for installing a module in the rear position of a chassis Method one is for installation of a rear module only when no module will be installed in front of it Refer to Figure 5 for instruc tions Method two is for installation of a rear module when another mod ule will be installed in the chassis position in front of it Refer to Figures 6A 6C for method two All necessary screws and standoffs are su...

Page 3: ...be used for other modules on the SLC For Class A and B operation DO NOT set the lowest address above 154 as the other modules will be assigned to nonexistent addresses NOTE The MMI 6SF must have power cycled for shunt changes to take effect NOTE Some panels support extended addressing In order to set the module above address 99 on compatible systems carefully remove the stop on the upper rotary sw...

Page 4: ...he two shunts from the A B select positions 2 To use a common power supply between multiple MMI 6SF modules connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent MMI 6SF module FIGURE 10 RELAY CONTROL MODULE USED TO DISCONNECT A POWER SUPPLY C0248 00 4 I56 2742 009 7 1 2022 ...

Page 5: ...e harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the ...