Honeywell Velociti Series Installation And Maintenance Instructions Download Page 3

FIGURE 6C. INSTALLATION OF MMI-6SF MODULE IN FRONT CHASSIS 

POSITION

 

2

3

1

 C0226-01

Step 1:   Insert the bottom edge of the MMI-6SF module down into a front slot 

of the chassis.

Step 2:    Carefully swing the upper edge of the board towards the back of the 

chassis until it touches the 1.25˝ (32 mm) standoffs installed on the 
rear module.

Step 3:   Align two 4-40 screws with the two standoffs and tighten.
Step 4:    Address and wire the modules according to the instructions in this 

manual.

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and 
regulations.

NOTE:  All references to power limited represent “Power Limited (Class 2)”.

1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.   All wiring to the MMI-6SF is done via terminal blocks. In order to prop-

erly make electrical connections strip approximately 0.25˝ of insulation 
from the end of wire, sliding the bare end of the wire under the clamping 
plate screw.

3.   Set the address on the modules per the job drawing. Use the rotary code 

switches to set the address of the first module (between 01 and 154).

 

 In Class B operation, the remaining modules are automatically assigned to 
the next five higher addresses. For example, if the base address switch is 
set to 28, the next five modules will be addressed to 29, 30, 31, 32 and 33.

 

 The module is shipped in Class B position, remove shunts for Class 
A. When operating in Class A, alternate modules are paired together 
(+0/+1, +2/+3, +4/+5), resulting in a total of three modules. For 

example, if the base address switch is set to 28, then 30 and 32 will be 
automatically assigned to the modules while 29, 31 and 33 are available 
to be used for other modules on the SLC. For Class A and B operation, 
DO NOT set the lowest address above 154, as the other modules will be 
assigned to nonexistent addresses.

 

 NOTE: The MMI-6SF must have power cycled for shunt changes to take effect.

 

 NOTE: Some panels support extended addressing. In order to set the 
module above address 99 on compatible systems, carefully remove the 
stop on the upper rotary switch (see Figure 7). If the panel does not sup-
port extended addressing, do not set the lowest address above 94.

FIGURE 7. 

 

TENS

0

7 8

6

5

4

3

2

1

9

10

11

12

13

14

15

 

C0227-00

4.    A shunt is provided to disable a maximum of two unused modules in 

Class B operation and Class A operation. Modules are disabled from the 
highest address and work downward.  If two modules are disabled, the 
lowest four addresses will be functional, while the highest two will be dis-
abled. For example, in Class B operation, if the shunt for Address Disable 
is placed on “two” and the base switch is set to 28, the modules will be 
assigned to 28, 29, 30 and 31 while disabling the highest two positions.

 

 NOTE: Place unused shunts on single pin to store on board for future use.

 

 NOTE: Power must not be applied to the unit when changing functional-
ity on the shunts.

WIRING NOTES

•  Power-limited circuits must employ type FPL, FPLR, or FPLP cable as 

required by Article 760 of the NEC.

•  All wiring must be in accordance with the NEC, NFPA 72 and all other 

applicable codes and standards. All external power supplies must be 
power limited with battery back-up. All external power supplies and 
detectors must be UL listed for fire protection signaling applications.

FIGURE 8. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B

To use a common power supply between multiple MMI-6SF modules, connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent MMI-6SF.

C0853-00

  

I56-2742-009 

 

 7/1/2022

Summary of Contents for Velociti Series

Page 1: ...ICATIONS Normal Operating Voltage 15 32VDC Standby Current 2 3 mA 24 V Alarm Current 40 mA assumes all six LEDs solid on Temperature Range 32ºF to 120ºF 0ºC to 49ºC Humidity 10 to 85 Non condensing Dimensions 6 8 H x 5 8 W x 1 0 D Accessories CHS 6 Chassis MBB 6 Cabinet MBB 2 Cabinet CAB 4 Series Cabinets CAB 3 Series Cabinets Wire Gauge 12 18 AWG Maximum IDC Wiring Resistance 25 Ohms External Pow...

Page 2: ...for installing a module in the rear position of a chassis Method one is for installation of a rear module only when no module will be installed in front of it Refer to Figure 5 for instruc tions Method two is for installation of a rear module when another mod ule will be installed in the chassis position in front of it Refer to Figures 6A 6C for method two All necessary screws and standoffs are su...

Page 3: ...be used for other modules on the SLC For Class A and B operation DO NOT set the lowest address above 154 as the other modules will be assigned to nonexistent addresses NOTE The MMI 6SF must have power cycled for shunt changes to take effect NOTE Some panels support extended addressing In order to set the module above address 99 on compatible systems carefully remove the stop on the upper rotary sw...

Page 4: ...he two shunts from the A B select positions 2 To use a common power supply between multiple MMI 6SF modules connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent MMI 6SF module FIGURE 10 RELAY CONTROL MODULE USED TO DISCONNECT A POWER SUPPLY C0248 00 4 I56 2742 009 7 1 2022 ...

Page 5: ...e harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the ...

Reviews: