V5004TF ACTUATOR – INSTALLATION INSTRUCTIONS
MU1B-0655GE51 R1019A
3
Table 1. Differential pressure at which valve exercises its regulating effect
OS-No.
Flow [I/h]
Pressure
Min.
Max.
Close-off
V5004TF1050
2000 - 20000
40
400
600
V5004TF1065
3000 - 30000
30
400
600
V5004TF1080
3000 - 30000
30
400
600
V5004TF1100
5500 - 55000
30
400
600
V5004TF1125
9000 - 90000
35
400
600
V5004TF1150
15000 - 150000
50
400
600
V5004TF1200LF
20000 - 200000
40
400
400
V5004TF1200HF
30000 - 300000
40
400
400
V5004TF1250LF
30000 - 300000
40
400
400
V5004TF1250HF
50000 - 500000
65
400
400
5. Wiring
COMMON
24 VAC/DC
CONTROL SIGNAL 1, OPEN / Y*
*SELECTABLE RANGES
CONTROL SIGNAL 2, CLOSE*
FEEDBACK SIGNAL
1
2
3
4
5
BK
RD
WH
GN
BU
FACTORY DEFAULT
0...10 VDC
---
0...10 VDC
Fig. 3. Wiring
Table 2. Wire guidelines
Input
Number
1
2
3
4
5
Remarks
Color
Black (BK) Red (RD)
White (WH)
Green (GN) Blue (BU)
Internal control
(A
Common
24 AC/DC
Feedback:
0(2)…10 V
0(4)…20 mA
Power: cable 1-2
Voltage signal
Common
24 AC/DC
0…10 VDC
,
2…10 VDC
Feedback:
0(2)…10 V
0(4)…20 mA
Power: cable 1-2
Voltage signal: cable 1-3
Current signal
Common
24 AC/DC
0…20 mA,
4…20 mA
Feedback:
0(2)…10 V
0(4)…20 mA
Power: cable 1-2
Current signal: cable 1-3
ON/OFF signal
Common
24 AC/DC
24 VDC (open)
Feedback:
0(2)…10 V
0(4)…20 mA
Power: cable 1-2
0 V (close)
ON/OFF signal: cable 1-3
Floating
Common
24 AC/DC
Opening
24 VAC/DC
Closing
24 VAC/DC
Feedback:
0(2)…10 V
0(4)…20 mA
Power: cable 1-2
Floating: cable 3-4
PWM control
(B
Common
24 AC/DC PWM signal
Feedback:
0(2)…10 V
0(4)…20 mA
Power: cable 1-2
PWM control: cable 1-3
(A
Flow rate can be set by buttons on the actuator and read on the 4-digit display.
(B
PWM type 1: 0.1…5 sec / step 20 ms; PWM type 2: 0.1…25 sec / step 100 ms