UVL-COIL ULTRAVIOLET LAMP KITS FOR AHU COILS
31-00402—02
4
Fig. 2. Optimal Irradiation Distance.
Fig. 3. Lamp Spacing.
Fig. 4. Vertical Support Configuration.
UV Lamp Configuration Guidelines
• Maximum germicidal effectiveness is within an 18 inch
radius from UV lamp center axis.
• The optimal distance between UV lamp(s) and the
irradiated surface is 12 inch.
• The distance between stacked UV lamps should not
exceed 36 inches.
• The distance between end to end UV lamps should not
exceed 12 inches.
• The distance of UV lamp ends to the edge of irradiated
surface should not exceed 10 inches.
• The spacing guidelines above may not apply for all
applications. Use recommendations in Table 2 to select
appropriate kit based on coil size.
WARNING
Be careful of damage to equipment.
Ultraviolet light can cause color fading or degraded
structure of plastic material found in HVAC
equipment, avoid plastic material or equipment
with unknown performance against ultraviolet light
in the area of irradiation.
WARNING
UV Light Hazard.
Harmful to bare skin and eyes.
Can cause temporary or permanent loss of vision.
Do not look at the UV lamp when lighting is on. Use
indicator light on the ballast to check status. In
order to prevent exposure to UV light, before repair
of any parts of HVAC system, shut off power supply
to UV system. Do not install in a position where UV
lamp is visible during normal operation of HVAC
equipment.
12” Lamp to Coil
36”
Max
Lamp to
Lamp
Coil
12” Max. space between lamps
10” Max. space to end of coils
Overlap lamps where necessary
Multiple lamps with Optional Vertical Support to prevent sagging
36”
Max