background image

UVL-COIL ULTRAVIOLET LAMP KITS FOR AHU COILS

7

31-00402—02

TROUBLESHOOTING

Table 4. Troubleshooting.

Problem

Solution

UV Lamp(s) Not Lighting

1.

Check that power is applied.

2.

Check that the unit is turned ON.

3.

Ensure the remote lamp cables are properly connected.

4.

Check the fuse. Replace only with same size and type.

5.

Reset power switch on power supply (off then on).

6.

Install New UV Lamp(s).

7.

Consult Factory.

UV Lamp(s) Flickering

1.

UV Lamp(s) have reached end of effective service life. Install new 
lamp(s) of same type.

2.

If unit is new, check remote cables to ensure they are properly con-
nected.

3.

Reset power switch on power supply (off then on).

4.

If new lamps still flicker, consult factory.

UV Lamps Have burned Out Prematurely

1.

Consult Factory.

Power Supply Will Not Light UV Lamps even 
after new lamps are installed

1.

Consult Factory.

2.

External power suppressor may be needed if power surges occur.

Summary of Contents for UVL-COIL-60D

Page 1: ...nside of air handlers or the exposed conditions of outdoor packaged air conditioning systems The number and placement of lamps is determined by the coil dimensions FEATURES UV C light irradiates coil air handler interior killing mold bacteria and viruses Scalable design allows wide variety of multi lamp configurations High quality water resistant lamps Mounts using off the shelf inch EMT conduit t...

Page 2: ...mm length UV C Power UVL 32 LAMP 28 W UVL 60 LAMP 54 W Output at 1 Meter UVL 32 LAMP 250 μW cm2 UVL 60 LAMP 395 μW cm2 Spectrum 100 254 nm Germicidal UV C Bulb Type Shielded Quartz Hot Filament Bulb Life 18 000 hours Accessories UVL 32 LAMP 32 inch replacement lamp UVL 60 LAMP 60 inch replacement lamp Table 1 Models Power supply not available for purchase outside of kit Part Number Description Rep...

Page 3: ...unting use optimal irradiation distance Fig 2 and lamp spacing Fig 3 diagrams to confirm than when installed the UV lamps will be positioned properly The UV lamps are mounted onto a framework of EMT tubing When two or more UV lamps are supported on a single length of EMT it is recommended to add an optional vertical support Fig 4 Table 2 Sizing Based on Coil Dimensions Table 3 Sizing Based on Unit...

Page 4: ...based on coil size WARNING Be careful of damage to equipment Ultraviolet light can cause color fading or degraded structure of plastic material found in HVAC equipment avoid plastic material or equipment with unknown performance against ultraviolet light in the area of irradiation WARNING UV Light Hazard Harmful to bare skin and eyes Can cause temporary or permanent loss of vision Do not look at t...

Page 5: ...h to the conduit tubing to support framework and prevents sagging on installations with three or more lamps per tubing length Measure the distance from floor to ceiling then measure and cut tubing 1 75 inches less than that length Use inch pipe coupling to extend the vertical support to the floor and ceiling for a snug fit Fig 7 Fig 7 Optional Vertical Support Install UV Lamps Snap UV Lamps into t...

Page 6: ...ower supply to the main power Fig 10 Electrical Connections Connect Lamps and Cables Arrange cables as needed for installation If necessary use cable strain relief fittings or other means to pass cables through the cabinets or air system walls When UV lamps power supplies and cables are in place join the lamp and power supply cables by aligning the electrical pins and flanges on the rubber connect...

Page 7: ...upply off then on 6 Install New UV Lamp s 7 Consult Factory UV Lamp s Flickering 1 UV Lamp s have reached end of effective service life Install new lamp s of same type 2 If unit is new check remote cables to ensure they are properly con nected 3 Reset power switch on power supply off then on 4 If new lamps still flicker consult factory UV Lamps Have burned Out Prematurely 1 Consult Factory Power S...