Function Blocks
Function Block Reference Guide
3/99
80
2.26 HLLM Function Block
Description
The HLLM label stands for
High Low
limiter. This block is part of the
Auxiliary
category. It looks like this
graphically on the Control Builder:
Function
Provide high-low limit for an analog (
X
) value.
Turns ON H or L digital output if input exceeds or falls below set limits.
• If X < or = Low Limit value, then:
OUT = LoLlM; L = ON; H = OFF.
• If X > or = High Limit value, then:
OUT = HiLlM; L = OFF; H= ON.
• If X > Low Limit value and < high Limit value, then:
OUT = X; L = OFF; H = OFF.
Input
X
= Analog Value
Output
OUT
= Analog value within limits
L
= Low Limit digital indication
H
= High Limit digital indication
Continued next page