Honeywell TrueZONE ARD Series Installation Instructions Manual Download Page 3

TRUEZONE ARD, EARD, AND ZD SERIES DAMPERS

3

33-00040—01

Installing the Round (ARD and 

EARD) Dampers

1.

Insert the crimped end of the ARD or EARD into the 

uncrimped end of the rigid round duct and secure with 

sheet metal screws (not provided). When using flexible 

duct, slip the duct over the end of the ARD or EARD and 

secure it with duct straps (not provided).

2.

When installing the damper in a horizontal application, 

make sure the motor actuator is located on the side or 

top of the damper. Do not locate the motor on the bot-

tom of the damper. The damper can be mounted in a 

vertical duct.

3.

Adjust Range stop position to desired closed positions. 

ARD and ZD Dampers are completely closed in position 

0. EARD Dampers are completely open in position 0.

Fig. 2. TrueZONE Actuator range stop positions.

Wiring Multiple Dampers

When the same zone controls two or more dampers, wire the 

dampers in parallel to terminals M1 and M6 on the zone 

control panel.

INSTALLATION OF ZD DAMPER

When Installing this Product…

1.

Read these instructions carefully. Failure to follow these 

instructions can damage the product or cause a hazard-

ous condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service techni-

cian.

4.

All wiring must comply with local electrical codes, ordi-

nances, and regulations.

5.

After completing installation, use these instructions to 

check out the product operation.

Planning the Installation

Selecting a Location

Select a location for the zone dampers that is at least three 

feet from the HVAC unit plenum in the air duct takeoff to the 

respective zone and is easily accessible for checkout and 

maintenance.

The ZD comes complete and ready for installation. The motor 

and linkage are factory-assembled to the damper. The 

damper is assembled for installation and wiring to the control 

panel.

Selecting Damper Size

To ensure correct operation, be sure to select the correct zone 

damper size for the air duct:

IMPORTANT

Be aware that damper sizes are built 5/32 in. smaller 

than the listed dimensional sizes.

• If the damper is forced into an undersized air duct, the 

excess pressure can jam the damper blades and cause 

improper operation.

• When a small percentage of continuous flow is desired in a 

zone, even when the damper blades are closed, adjust 

motor closed position to be slightly open to maintain 

desired air flow.

Selecting Location with Humidifier 

Installed

IMPORTANT

Excessive lime or mineral deposits can accumulate 

on damper blades and cause improper operation 

when spray or atomizing type humidifiers are 

installed in the furnace plenum or air supply duct with 

the zone dampers.

• Spray or atomizer type humidifiers that are installed in the 

furnace plenum or air supply duct are not recommended.

• Evaporative type humidifiers are recommended.

Installing the Damper

IMPORTANT

— Install dampers into a squared air duct.

— Do not weld dampers to the air ducts.

— Do not force dampers into undersized air ducts.

Excess pressure can damage damper blades.

— Be sure high limit setting is less than 200° F (93°C).

— Higher settings can damage the electric actuator.

1.

Be sure the ZD is correctly sized to the air duct (see 

Selecting Damper Size section).

2.

Select a ZD location that is three feet from the furnace 

plenum.

3.

Cut a 4-in. (102 mm) opening in the accessible side of 

the air duct at the location selected; ensure the opening 

of the air duct is cut fully from seam to seam.

4.

Secure the ZD mounting plate to the air duct with the 

self-tapping sheet metal screws provided.

M35187

RANGE STOP

LOCATIONS

Summary of Contents for TrueZONE ARD Series

Page 1: ...Male crimped and female uncrimped ends to connect to any rigid or flexible round duct Rated to operate up to 1 in wc Blade closes off tightly against gasket for minimal leakage Fail safe normally open operation Simple easy to wire two wire installation with a third wire option M4 for LED open only light EARD Features Adjustable open position range stops Shipped as power open spring return closed d...

Page 2: ...eans Direct connection to damper shaft Motor Mounting Position Multi poise Motor Dimensions See Fig 1 Construction ARD Dampers Frame Galvanized steel spiral duct crimped on down stream side ARD Sizes 5 in 6 in 7 in 8 in 9 in 10 in 12 in 14 in 16 in 18 in and 20 in diameters Gauge ARD5 ARD12 24 Gauge frame and 22 Gauge Blade ARD14 ARD20 22 Gauge frame and 20 Gauge Blade EARD Dampers Frame Galvanize...

Page 3: ...r checkout and maintenance The ZD comes complete and ready for installation The motor and linkage are factory assembled to the damper The damper is assembled for installation and wiring to the control panel Selecting Damper Size To ensure correct operation be sure to select the correct zone damper size for the air duct IMPORTANT Be aware that damper sizes are built 5 32 in smaller than the listed ...

Page 4: ... set screw pointing toward the open position on the label 5 Attach new motor to the coupling be sure the standoff on motor is positioned in the grommet on the faceplate and the set screw is aligned with the motor shaft hole 6 Tighten the set screw Wiring a Single ARD Power Closed to a Control Panel Fig 3 ARD configured as power closed Checkout CAUTION Possible Equipment Damage Do not manually open...

Page 5: ... G AT120 W8150A EARD 6 HVAC W C RC Y G G RC CC CH W G TH8110U R C DAMPER AUX REMOTE M23547 M23591 HVAC W C R Y G VISIONPRO TH9000 THERMOSTAT H U M D H M V N T OR 1 2 3 C R RC RH 24 VAC COMMUNICATION TERMINALS COMMUNICATION LED W1 W2 W3 Y Y2 G O B AUX AUX2 Y Y2 G CONV HP L NOT USED 1 2 1 2 SYSTEM MONITOR NOT USED OUTDOOR TEMP SENSOR INDOOR TEMP SENSOR DISCHARGE AIR TEMP SENSOR 1 2 D A T S O U T I N...

Page 6: ...TABLE 1 0 3 ENVIRACOM FURN NO YES 4 PURGE TIME 2 MIN 3 5 MIN 5 PURGE FAN HVAC PANEL 6 PURGE DAMPER NO CHG OPEN 7 COMP STAGES 1 2 8 HEAT FAN HVAC PANEL 9 HP CHANGEOVER O B 10 UNUSED O N 1 2 3 4 5 6 7 8 9 10 1 2 CONV HT STG 1 1 1 1 0 2 0 1 3 0 0 HP 24 VOLT 40 VA TRANSFORMER R C L1 L2 R W1 W2 Y1 Y2 G C DOTTED LINES FOR 2 STAGE APPLICATIONS SINGLE TRANSFORMER HEATING COOLING SYSTEMS REQUIRE A JUMPER T...

Page 7: ...hat requires 24V to the two motor leads to power the damper closed When power is removed from the motor the damper springs back to its normally open position When used with Honeywell Networked Zoning use closed and com terminals Fig 7 Power closed spring return open ZD wiring Wiring Multiple Dampers When the same zone controls two or more dampers wire the dampers in parallel to terminals M1 and M6...

Page 8: ...RS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2015 Honeywell International Inc 33 00040 01 M S 02 15 Printed in United States ...

Reviews: