INSTALLATION INSTRUCTIONS

33-00040-01

TrueZONE ARD, EARD, and ZD 

Series Dampers

APPLICATION

ARD Series Damper

The ARD is a round damper with a 24 Vac, spring-Open return 

damper motor used to control circulating air in heating, 

cooling, and ventilating systems.

EARD Series Damper

The EARD is a round damper with a 24 Vac powered-open/

spring-closed motor. It is used for fresh air intake for 

Ventilation or for combustion makeup air.

ZD Series Damper

The ZD is a power close and spring open damper. It has a 24-

volt motor used to control circulating air in HVAC systems and 

used when a normally-open damper is required. The ZD is 

typically used with the TrueZONE and other electronic zoning 

systems.

FEATURES

• Taping Flange and non-interfering set screw 
• High Temperature outer plastic for hot environments 
• Redesigned all Metal Drive Train Gears
• Front facing display with LED Indication light for Open 

and Close. 

• Adjustable damper position range stops
• Quiet operation.

ARD Features

• Adjustable close position range stops 

• Shipped as power closed/spring return open damper.

• Available in 5 to 10” inch, 12, 14, 16, 18, and 20 inch 

diameter sizes.

• Male (crimped) and female (uncrimped) ends to connect to 

any rigid or flexible round duct. 

• Rated to operate up to 1 in. wc

• Blade closes off tightly against gasket for minimal leakage. 

• Fail-safe, normally open operation

• Simple, easy-to-wire, two-wire installation with a third wire 

option M4 for LED open only light 

EARD Features

• Adjustable open position range stops

• Shipped as power open/spring return closed damper. 

• Blade closes off tightly against gasket for minimal leakage. 

• Galvanized steel

• Rated to operate up to 1 in. wc

• Simple, easy-to-wire, two-wire installation

• Male (crimped) and female (uncrimped) ends to connect to 

any rigid or flexible round duct. 

ZD Features

• Adjustable closed position range stops

• Rated to operate up to 1 in. wc

• Solid construction using extruded aluminum frame and 

blades

• Parallel blade design for low leakage performance

• Simple, easy-to-wire, two-wire installation with a third wire 

option M4 for LED open light 

• Fail-safe, normally open operation

• Ordering Instructions: Order ZD (dimension 1) x 

(dimension 2). (Motor is always mounted on dimension 2 

side.) For example, ZD10x8TZ is a 10 in. x 8 in. damper 

with the motor on the 8 in. side; but a ZD8x10TZ is a 8 in. x 

10 in. damper that has the motor on the 10 in. side.

• Damper can be installed in any orientation (mounting side 

can be on either the bottom or the side of the duct).

Summary of Contents for TrueZONE ARD Series

Page 1: ...Male crimped and female uncrimped ends to connect to any rigid or flexible round duct Rated to operate up to 1 in wc Blade closes off tightly against gasket for minimal leakage Fail safe normally open operation Simple easy to wire two wire installation with a third wire option M4 for LED open only light EARD Features Adjustable open position range stops Shipped as power open spring return closed d...

Page 2: ...eans Direct connection to damper shaft Motor Mounting Position Multi poise Motor Dimensions See Fig 1 Construction ARD Dampers Frame Galvanized steel spiral duct crimped on down stream side ARD Sizes 5 in 6 in 7 in 8 in 9 in 10 in 12 in 14 in 16 in 18 in and 20 in diameters Gauge ARD5 ARD12 24 Gauge frame and 22 Gauge Blade ARD14 ARD20 22 Gauge frame and 20 Gauge Blade EARD Dampers Frame Galvanize...

Page 3: ...r checkout and maintenance The ZD comes complete and ready for installation The motor and linkage are factory assembled to the damper The damper is assembled for installation and wiring to the control panel Selecting Damper Size To ensure correct operation be sure to select the correct zone damper size for the air duct IMPORTANT Be aware that damper sizes are built 5 32 in smaller than the listed ...

Page 4: ... set screw pointing toward the open position on the label 5 Attach new motor to the coupling be sure the standoff on motor is positioned in the grommet on the faceplate and the set screw is aligned with the motor shaft hole 6 Tighten the set screw Wiring a Single ARD Power Closed to a Control Panel Fig 3 ARD configured as power closed Checkout CAUTION Possible Equipment Damage Do not manually open...

Page 5: ... G AT120 W8150A EARD 6 HVAC W C RC Y G G RC CC CH W G TH8110U R C DAMPER AUX REMOTE M23547 M23591 HVAC W C R Y G VISIONPRO TH9000 THERMOSTAT H U M D H M V N T OR 1 2 3 C R RC RH 24 VAC COMMUNICATION TERMINALS COMMUNICATION LED W1 W2 W3 Y Y2 G O B AUX AUX2 Y Y2 G CONV HP L NOT USED 1 2 1 2 SYSTEM MONITOR NOT USED OUTDOOR TEMP SENSOR INDOOR TEMP SENSOR DISCHARGE AIR TEMP SENSOR 1 2 D A T S O U T I N...

Page 6: ...TABLE 1 0 3 ENVIRACOM FURN NO YES 4 PURGE TIME 2 MIN 3 5 MIN 5 PURGE FAN HVAC PANEL 6 PURGE DAMPER NO CHG OPEN 7 COMP STAGES 1 2 8 HEAT FAN HVAC PANEL 9 HP CHANGEOVER O B 10 UNUSED O N 1 2 3 4 5 6 7 8 9 10 1 2 CONV HT STG 1 1 1 1 0 2 0 1 3 0 0 HP 24 VOLT 40 VA TRANSFORMER R C L1 L2 R W1 W2 Y1 Y2 G C DOTTED LINES FOR 2 STAGE APPLICATIONS SINGLE TRANSFORMER HEATING COOLING SYSTEMS REQUIRE A JUMPER T...

Page 7: ...hat requires 24V to the two motor leads to power the damper closed When power is removed from the motor the damper springs back to its normally open position When used with Honeywell Networked Zoning use closed and com terminals Fig 7 Power closed spring return open ZD wiring Wiring Multiple Dampers When the same zone controls two or more dampers wire the dampers in parallel to terminals M1 and M6...

Page 8: ...RS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2015 Honeywell International Inc 33 00040 01 M S 02 15 Printed in United States ...

Reviews: