OPERATION AND SETTINGS

Operation and Settings

HIGH LIMIT

The high limit opens and turns off the burner when the

water temperature reaches the setpoint. The high limit
automatically resets after the water temperature drops past
the setpoint and through the 10

°

F (6

°

C) differential.

WARNING

CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY OR DEATH.
Product is for use only in a system with a pressure
relief valve.

LOW LIMIT AND CIRCULATOR CONTROL

On a temperature rise, with the adjustable differential at

the minimum setting of 10

°

F (6

°

C), the low limit circuit

(RB) breaks and the circulator circuit (R-W) makes at the
control setpoint. On a temperature drop of 10

°

F (6

°

C)

below the setpoint, the R-B circuit makes and the R-W
circuit breaks.

Fig. 5—Typical hookup for the L8151A in a
multizone system.

L1 
(HOT)

L2

1

2

3

3

4

4

1

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.

CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
USE GROUNDING SCREW PROVIDED.

LINE VOLTAGE OIL BURNER CONTROL OR GAS VALVE.

B1 IS 1/4 IN. TAB TERMINAL.

M8885

T

T

ZC

ZR

B1

B2

C1

C2

1

2

G

THERMOSTAT
ZONE 1

THERM.

BURNER

CIRCULATOR
ZONE 1

LINE

HYDRONIC HEATING
CONTROL TERMINALS

2

1

4

3

5

6

R845A RELAY

TO ADDITIONAL
R845A RELAYS
FOR OTHER ZONES

THERMO-
STAT
ZONE 2

CIRCULATOR
ZONE 2

CIRC.

IF CONTROLLING TWO LOADS USE:
—TERMINALS 3 AND 4 FOR LINE 
VOLTAGE LOAD.
—TERMINALS 5 AND 6 FOR LINE 
OR LOW VOLTAGE LOAD.

Fig. 6—L8151A internal schematic.

2

1

T

T

1K

B2

B1

ZR

ZC

R

B

W

C1

C2

1K1

HIGH LIMIT

1K2

LOW
LIMIT

CIRCULATOR
CONTROL

M8884

Fig. 7—Relationship of setpoints and differen-
tial.

LOW LIMIT 
AND 
CIRCULATOR
SETTING

HIGH LIMIT
SETTING

SWITCH BREAKS ON 
TEMPERATURE RISE. 
BURNER TURNS OFF. 
CIRCULATOR OPERATES 
ON A CALL FOR HEAT.

SWITCH MAKES ON 
TEMPERATURE FALL.
BURNER OPERATES ON A 
CALL FOR HEAT.

SWITCH MAKES R-W 
AND BREAKS R-B ON 
TEMPERATURE RISE.

SWITCH MAKES R-B AND 
BREAKS R-W ON 
TEMPERATURE FALL. 
BURNER IS ON TO 
MAINTAIN MINIMUM 
WATER TEMPERATURE. 
CIRCULATOR IS OFF.

110°F  (43°C)

240°F  (116°C)

M1523

SWITCH MAKES R-W 
AND BREAKS R-B ON 
TEMPERATURE RISE.

WHEN WATER REACHES PROPER TEMPERATURE, THE BURNER 
SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING 
FOR HEAT).

1

1

10°F  (6°C)
DIFFERENTIAL

25°F  (14°C)
DIFFERENTIAL

10°F  (6°C)
DIFFERENTIAL

At any differential setting greater than 10

°

F (6

°

C), the

R-B make and R-W break temperatures remain the same
(control setting minus 10

°

F (6

°

C). The R-B break and R-W

make temperatures are the setpoint temperatures plus the
difference between the differential setting and 10

°

F (6

°

C).

Summary of Contents for TRIPLEAQUASTAT L8151A

Page 1: ...ulator control for maintaining boiler temperatures Can provide multizone control by using a separate thermostat and R845 Relay for each zone An internal transformer powers the thermostat cir cuit Shielded capillary allows convenient mounting Consistsofadiaphragmpowerheadandmicroswitch assembly that responds to temperature changes in the boiler water CONTENTS Specifications 2 Ordering Information 2...

Page 2: ...MBPR2 Installation WHEN INSTALLING THIS PRODUCT 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product op...

Page 3: ...e approved for copper wire only Fig 1 Approximate L8151 dimensions in in mm 1 1 4 32 1 1 4 32 13 16 21 2 3 6 56 3 5 16 84 4 23 32 120 4 5 16 110 KNOCKOUT FOR 1 2 IN CONDUIT 5 CAPILLARY 30 IN 762 13 64 X 21 64 4 4 1 2 114 6 1 8 156 1 1 2 38 1 7 16 37 1 8 3 2 3 16 56 M8892 MOUNTING THE CASE Mount the case in a convenient location near the boiler Remember that the shielded capillary must reach from t...

Page 4: ... JAWS TO FIT OVER RIDGE ON SPUD OF WELL JAWS 4 With part no 121371AA Retainer Clamp attached to well spud be sure jaws of clamp hook over ridge at end of spud as shown at points A adjust tubing to fit through retainer clamp groove as shown at point B 5 Tighten draw nut so that retainer clamp is firmly attached to well spud and tubing is held securely in place Be careful not to damage the capillary...

Page 5: ...HEATING CONTROL TERMINALS 2 1 4 3 5 6 R845A RELAY TO ADDITIONAL R845A RELAYS FOR OTHER ZONES THERMO STAT ZONE 2 CIRCULATOR ZONE 2 CIRC IF CONTROLLING TWO LOADS USE TERMINALS 3 AND 4 FOR LINE VOLTAGE LOAD TERMINALS 5 AND 6 FOR LINE OR LOW VOLTAGE LOAD Fig 6 L8151A internal schematic 2 1 T T 1K B2 B1 ZR ZC R B W C1 C2 1K1 HIGH LIMIT 1K2 LOW LIMIT CIRCULATOR CONTROL M8884 Fig 7 Relationship of setpoi...

Page 6: ...N AND SETTINGS CHECKOUT THERMOSTAT ANTICIPATOR Set the thermostat heat anticipator at 0 2A Checkout Put the system into operation and observe each function through at least one complete cycle Be sure the control operates as intended Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North ...

Reviews: