Honeywell Tradeline T8611M Installation Instructions Manual Download Page 9

T8611M DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS

9

69-1415—1

 

Fig. 12. Display of all LCD segments.

Fig. 13. Display of test number.

Refer to Table 5 for the directions and results of the 
specific tests.

NOTE: Press Time 

 to advance to the next test and 

Time 

 to go back to the previous test. Press 

Run Program to exit the System Test,

Table 5. Installer System Test Options.

NOTE: Press any key and the displayed numbers change. Press Time 

 to go to the previous test and Time 

 to go to 

the next test. The Run Program key does not exit this test. Press Time 

 or Time 

 and then the 

Run Program key to exit.

M14559

Aux Ht

Set Day/Time

Set Program

Mon
Wake Leave Return

Sleep

Outdoor

Room

Filter

Wait

System

Fan

Em Heat

On

Auto

Off

Cool
Auto

AM

PM

Hold for

Heat

Cool

Repl Batt

Recovery

DST

Tue Wed Thu Fri Sat Sun

Days

Temporary

Setting

Em Ht

M14612

Keys to 

Press

Test 

Number

Description

Heating Equipment System Test
Time

 

 

10

Enter heating equipment system test.

s

11

Stage one heat comes on. The system fan is also energized.

s

12

Stage two heat comes on. Stage one heat and system fan remain on.

s

13

Stage three heat comes on. Stage one and two remain on.

t

12

Stage three heat turns off.

t

11

Stage two heat turns off.

t

10

Stage one heat and system fan turn off.

Emergency Equipment Heating Equipment System Test
Time

 

 

20

Change from heating to emergency heating equipment system test.

s

21

Emergency heat comes on.

s

22

Stage two emergency heat comes on.

s

21

Stage two emergency heat turns off.

t

20

Emergency heat turns off.

Cooling Equipment System Test
Time

 

 

30

Change from heating or emergency heating to cooling equipment system test. 

s

31

Cool and system fan come on.

s

32

Stage two cooling comes on.

t

31

Stage two cooling turns off.

t

30

Cool and system fan turn off.

Fan Equipment System Test
Time

 

 

40

Change from cooling to fan equipment system test.

s

41

Fan comes on.

t

40

Fan turns off.

Key Operation System Test
Time

 

 

60 

Change from fan to key operation system test.

Summary of Contents for Tradeline T8611M

Page 1: ...er disposal of the old control INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing...

Page 2: ...hen not level 2 Use a pencil to mark the mounting holes See Fig 2 3 Remove the wallplate from the wall and drill two 76 mm 3 16 inch holes in the wall if drywall as marked For firmer material such as plaster drill two 5 56 mm 7 32 inch holes Gently tap anchors provided into the drilled holes until flush with the wall 4 Position the wallplate over the holes pulling wires through the wiring opening ...

Page 3: ...R C7089B1000 AND CONFIGURE INSTALLER SETUP NUMBER 24 TO 1 BE SURE INSTALLER SETUP NUMBER 3 IS SET TO 2 FOR TWO COMPRESSOR SYSTEMS WIRE EQUIPMENT MONITOR OR DEFROST RESET CONTROL PER MANUFACTURER INSTRUCTIONS CONFIGURE IN INSTALLER SETUP 1 AUX HEAT RELAY M13289 COMPRESSOR CONTACTOR 1 FAN RELAY R OT OT O B G Y1 C E W3 OUTDOOR TEMPERATURE SENSOR COOL HEAT CHANGEOVER VALVE EM HEAT RELAY THERMOSTAT 1 2...

Page 4: ... cycles the Emergency Heat relay and the highest heat stage Cooling system is off Compressor is de energized Heat The thermostat controls the heating Off Both the heating and cooling are off Cool The thermostat controls the cooling Auto The thermostat automatically changes between heating and cooling operation depending on the indoor temperature Fan settings control the system fan On Fan operates ...

Page 5: ...on i key with the increase s and decrease t keys until the first number is displayed All display segments appear for approximately three seconds before the number is displayed See Fig 10 and 11 To advance to the next Installer Setup press the Time key To change a setting use the increase s or decrease t key To scroll the Installer Setup numbers backward press the Time key To exit the Installer Set...

Page 6: ...isplay 14 0 Temperature is displayed in F 1 Temperature is displayed in C Not Used 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not Used 17 thru 18 Extended fan operation in heating 19 0 No extended fan operation after the call for heat ends 1 Fan operation is extended 90 seconds after the call for heat ends Extended fan operation in cooling 20 No extended fan operation after t...

Page 7: ... adjustment 37 0 No difference in displayed temperature and actual room temperature 3 thru 3 1 Display adjusts to 1 F higher than actual room temperature 2 Display adjusts to 2 F higher than actual room temperature 3 Display adjusts to 3 F higher than actual room temperature 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Di...

Page 8: ...System Test Avoid cycling compressor quickly To start the system test Press and hold the increase s and decrease t keys at the same time until 10 appears All segments of the display are displayed before the 10 appears See Fig 12 and 13 Table 4 Tests Available In Installer System Test M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Retur...

Page 9: ...ing Equipment System Test Time 10 Enter heating equipment system test s 11 Stage one heat comes on The system fan is also energized s 12 Stage two heat comes on Stage one heat and system fan remain on s 13 Stage three heat comes on Stage one and two remain on t 12 Stage three heat turns off t 11 Stage two heat turns off t 10 Stage one heat and system fan turn off Emergency Equipment Heating Equipm...

Page 10: ...re identification code Example 02 software ID code 2 4 Press the increase s key again to display the software revision number Example 001 Revision number 1 5 Press the increase s key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the System Test The System Test times out after four minutes without any key presses CHECKOUT Outdoor Tempe...

Page 11: ...power to the thermostat Check for 24 Vac between R and W terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connec...

Page 12: ... or cool air is coming from the registers Heating or cooling equipment is not operating Verify operation of heating or cooling equipment in self test Outdoor tempera ture not displayeda Option not activated Enter Installer Setup number 24 and set to 1 Thermostat must have OT terminals and a C7089B1000 installed Outdoor temperature display is incorrecta Outdoor sensor is connected incorrectly Refer...

Reviews: