Honeywell Tradeline T8611M Installation Instructions Manual Download Page 6

T8611M DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS

69-1415—1

6

Table 3. Thermostat Installer Setup Options.

Select

Installer Setup 

Number (Press 

Time 

 key to 

change)

Factory Setting

Other Choices

(Press 

s

 or 

t

 key to change)

Actual 

Setting

Display

Description

Display

Description

Not Used.

1 thru 4

Number of 
compressor 
stages.

3

2

Two compressor 
stages or two 
speed compressor.

1

Single stage compressor 
systems.

Heating cycle.

Not Used.

3—3 cph 

6

6

Auxiliary heat.

3, 6 or 9 6—6 cph used for last stage 

of heat pump systems.

7

9

Emergency heat.

3, 6 or 9

9—9 cph used for electric 

heat.

Not Used.

8 thru 11

System setting 
adjustment

12

1

Manual 
changeover

0 or 2

0—Auto changeover.
2—Fixed auto changeover.

Adaptive 
Intelligent 
Recovery™ 
control.

13

0

Adaptive Intelligent 
Recovery™ 
control is activated 
(system starts 
early so setpoint is 
reached by start of 
program period).

1

Conventional recovery 
(system starts recovery at 
programmed time).

Degree 
temperature 
display.

14

0

Temperature is 
displayed in °F

1

Temperature is displayed 
in °C.

Not Used.

15

Clock format.

16

0

12-hour clock 
format.

1

24-hour clock format.

Not Used.

17 thru 18

Extended fan 
operation in 
heating.

19

0

No extended fan 
operation after the 
call for heat ends.

1

Fan operation is extended 
90 seconds after the call for 
heat ends.

Extended fan 
operation in 
cooling.

20

No extended fan 
operation after the 
call for cool ends.

1

Fan operation is extended 
90 seconds after the call for 
cool ends.

Not Used.

21 thru 23

Outdoor 
temperature 
display (models 
with OT 
terminals).

24

0

No outdoor 
temperature is 
displayed.

1

Outdoor temperature is 
displayed. Needs a 
C7089B1000 Outdoor 
Temperature Sensor to 
operate.

Not Used.

25 thru 28

O/B terminal 
energized in 
heating or 
cooling.

29

0

O/B terminal 
energized for 
reversing valve in 
cooling.

1

O/B terminal energized for 
reversing valve in heating.

Deadband

30

3

Heating and 
cooling setpoints 
can be set no 
closer than 3°F 
(1.5°C).

4 thru 10 Heating and cooling 

setpoints can be set no 
closer than the chosen 
value:

4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)

Not Used.

31 and 32

Summary of Contents for Tradeline T8611M

Page 1: ...er disposal of the old control INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing...

Page 2: ...hen not level 2 Use a pencil to mark the mounting holes See Fig 2 3 Remove the wallplate from the wall and drill two 76 mm 3 16 inch holes in the wall if drywall as marked For firmer material such as plaster drill two 5 56 mm 7 32 inch holes Gently tap anchors provided into the drilled holes until flush with the wall 4 Position the wallplate over the holes pulling wires through the wiring opening ...

Page 3: ...R C7089B1000 AND CONFIGURE INSTALLER SETUP NUMBER 24 TO 1 BE SURE INSTALLER SETUP NUMBER 3 IS SET TO 2 FOR TWO COMPRESSOR SYSTEMS WIRE EQUIPMENT MONITOR OR DEFROST RESET CONTROL PER MANUFACTURER INSTRUCTIONS CONFIGURE IN INSTALLER SETUP 1 AUX HEAT RELAY M13289 COMPRESSOR CONTACTOR 1 FAN RELAY R OT OT O B G Y1 C E W3 OUTDOOR TEMPERATURE SENSOR COOL HEAT CHANGEOVER VALVE EM HEAT RELAY THERMOSTAT 1 2...

Page 4: ... cycles the Emergency Heat relay and the highest heat stage Cooling system is off Compressor is de energized Heat The thermostat controls the heating Off Both the heating and cooling are off Cool The thermostat controls the cooling Auto The thermostat automatically changes between heating and cooling operation depending on the indoor temperature Fan settings control the system fan On Fan operates ...

Page 5: ...on i key with the increase s and decrease t keys until the first number is displayed All display segments appear for approximately three seconds before the number is displayed See Fig 10 and 11 To advance to the next Installer Setup press the Time key To change a setting use the increase s or decrease t key To scroll the Installer Setup numbers backward press the Time key To exit the Installer Set...

Page 6: ...isplay 14 0 Temperature is displayed in F 1 Temperature is displayed in C Not Used 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not Used 17 thru 18 Extended fan operation in heating 19 0 No extended fan operation after the call for heat ends 1 Fan operation is extended 90 seconds after the call for heat ends Extended fan operation in cooling 20 No extended fan operation after t...

Page 7: ... adjustment 37 0 No difference in displayed temperature and actual room temperature 3 thru 3 1 Display adjusts to 1 F higher than actual room temperature 2 Display adjusts to 2 F higher than actual room temperature 3 Display adjusts to 3 F higher than actual room temperature 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Di...

Page 8: ...System Test Avoid cycling compressor quickly To start the system test Press and hold the increase s and decrease t keys at the same time until 10 appears All segments of the display are displayed before the 10 appears See Fig 12 and 13 Table 4 Tests Available In Installer System Test M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Retur...

Page 9: ...ing Equipment System Test Time 10 Enter heating equipment system test s 11 Stage one heat comes on The system fan is also energized s 12 Stage two heat comes on Stage one heat and system fan remain on s 13 Stage three heat comes on Stage one and two remain on t 12 Stage three heat turns off t 11 Stage two heat turns off t 10 Stage one heat and system fan turn off Emergency Equipment Heating Equipm...

Page 10: ...re identification code Example 02 software ID code 2 4 Press the increase s key again to display the software revision number Example 001 Revision number 1 5 Press the increase s key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the System Test The System Test times out after four minutes without any key presses CHECKOUT Outdoor Tempe...

Page 11: ...power to the thermostat Check for 24 Vac between R and W terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connec...

Page 12: ... or cool air is coming from the registers Heating or cooling equipment is not operating Verify operation of heating or cooling equipment in self test Outdoor tempera ture not displayeda Option not activated Enter Installer Setup number 24 and set to 1 Thermostat must have OT terminals and a C7089B1000 installed Outdoor temperature display is incorrecta Outdoor sensor is connected incorrectly Refer...

Reviews: