T8611M DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
69-1415—1
6
Table 3. Thermostat Installer Setup Options.
Select
Installer Setup
Number (Press
Time
∆
key to
change)
Factory Setting
Other Choices
(Press
s
or
t
key to change)
Actual
Setting
Display
Description
Display
Description
Not Used.
1 thru 4
—
—
—
—
—
Number of
compressor
stages.
3
2
Two compressor
stages or two
speed compressor.
1
Single stage compressor
systems.
Heating cycle.
Not Used.
—
—
—
3—3 cph
6
6
Auxiliary heat.
3, 6 or 9 6—6 cph used for last stage
of heat pump systems.
—
7
9
Emergency heat.
3, 6 or 9
9—9 cph used for electric
heat.
Not Used.
8 thru 11
—
—
—
—
—
System setting
adjustment
12
1
Manual
changeover
0 or 2
0—Auto changeover.
2—Fixed auto changeover.
Adaptive
Intelligent
Recovery™
control.
13
0
Adaptive Intelligent
Recovery™
control is activated
(system starts
early so setpoint is
reached by start of
program period).
1
Conventional recovery
(system starts recovery at
programmed time).
—
Degree
temperature
display.
14
0
Temperature is
displayed in °F
1
Temperature is displayed
in °C.
Not Used.
15
—
—
—
—
—
Clock format.
16
0
12-hour clock
format.
1
24-hour clock format.
Not Used.
17 thru 18
—
—
—
—
—
Extended fan
operation in
heating.
19
0
No extended fan
operation after the
call for heat ends.
1
Fan operation is extended
90 seconds after the call for
heat ends.
Extended fan
operation in
cooling.
20
No extended fan
operation after the
call for cool ends.
1
Fan operation is extended
90 seconds after the call for
cool ends.
Not Used.
21 thru 23
—
—
—
—
—
Outdoor
temperature
display (models
with OT
terminals).
24
0
No outdoor
temperature is
displayed.
1
Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor
Temperature Sensor to
operate.
Not Used.
25 thru 28
—
—
—
—
—
O/B terminal
energized in
heating or
cooling.
29
0
O/B terminal
energized for
reversing valve in
cooling.
1
O/B terminal energized for
reversing valve in heating.
Deadband
30
3
Heating and
cooling setpoints
can be set no
closer than 3°F
(1.5°C).
4 thru 10 Heating and cooling
setpoints can be set no
closer than the chosen
value:
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Not Used.
31 and 32
—
—
—
—
—