T8611M DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS

11

69-1415—1

TROUBLESHOOTING GUIDE

Table 6. Troubleshooting Guide.

Symptom

Possible Cause

Action

Display doesnot 
come on.

Thermostat is not being 
powered.

• Check for 24 Vac between R and C terminals.

— If missing 24 Vac:

— check if the circuit breaker is tripped—reset the circuit 

breaker.

— check if the system fuse is blown—replace the fuse.
— check if the power switch on the HVAC equipment is in 

the Off position—set to the On position.

— check wiring between thermostat and HVAC 

equipment—replace any broken wires and tighten any 
loose connections.

— If 24 Vac is present, proceed with troubleshooting

Temperature 
display is incorrect.

Room temperature display has 
been reconfigured.

Enter Installer Setup number 37 and reconfigure the display.

Thermostat is configured for °F 
or °C display.

Enter Installer Setup number 14 and reconfigure the display.

Bad thermostat location.

Relocate the thermostat.

Temperature 
settings do not 
change. (Example: 
Cannot set the 
heating higher or 
the cooling lower.)

The upper or lower temperature 
limits were reached. 

Check the temperature setpoints:

• Heating limits are 40 to 90°F (4.5 to 32°C)
• Cooling limits are 48 to 99°F (7 to 37°C)

The setpoint temperature range 
stops were configured.

Check Installer Setup numbers 34 and 35 and reconfigure the 
setpoint stops.

Heating does not 
come on.

No power to the thermostat.

• Check for 24 Vac between R and W terminals.

— If missing 24 Vac:

— check if the circuit breaker is tripped—reset the circuit 

breaker.

— check if the system fuse is blown—replace the fuse.
— check if the power switch on the HVAC equipment is in 

the Off position—set to the On position.

— check wiring between thermostat and HVAC 

equipment—replace any broken wires and tighten any 
loose connections.

— If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is 
activated.

Wait up to five minutes for the system to respond.

System selection is not set to 
Heat.

Set system selection to Heat.

Heating setpoint is below room 
temperature.

Check heating setpoint. Set heating setpoint to desired 
temperature.

Cooling does not 
come on.

No power to the thermostat.

• Check for 24 Vac between R and C terminals.

— If missing 24 Vac:

— check if the circuit breaker is tripped—reset the circuit 

breaker.

— check if the system fuse is blown—replace the fuse. 
— check if the power switch on the HVAC equipment is in 

the Off position—set to the On position.

— check wiring between thermostat and HVAC 

equipment—replace any broken wires and tighten any 
loose connections.

— If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is 
activated.

• Wait up to five minutes for the system to respond.
• Enter Installer Setup number 33. Reconfigure minimum off 

time (if required).

System selection is not set to 
Cool.

Set system selection to Cool.

Cool setpoint is above room 
temperature.

Check cooling setpoint. Set cooling setpoint to desired 
temperature.

Summary of Contents for Tradeline T8611M

Page 1: ...er disposal of the old control INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing...

Page 2: ...hen not level 2 Use a pencil to mark the mounting holes See Fig 2 3 Remove the wallplate from the wall and drill two 76 mm 3 16 inch holes in the wall if drywall as marked For firmer material such as plaster drill two 5 56 mm 7 32 inch holes Gently tap anchors provided into the drilled holes until flush with the wall 4 Position the wallplate over the holes pulling wires through the wiring opening ...

Page 3: ...R C7089B1000 AND CONFIGURE INSTALLER SETUP NUMBER 24 TO 1 BE SURE INSTALLER SETUP NUMBER 3 IS SET TO 2 FOR TWO COMPRESSOR SYSTEMS WIRE EQUIPMENT MONITOR OR DEFROST RESET CONTROL PER MANUFACTURER INSTRUCTIONS CONFIGURE IN INSTALLER SETUP 1 AUX HEAT RELAY M13289 COMPRESSOR CONTACTOR 1 FAN RELAY R OT OT O B G Y1 C E W3 OUTDOOR TEMPERATURE SENSOR COOL HEAT CHANGEOVER VALVE EM HEAT RELAY THERMOSTAT 1 2...

Page 4: ... cycles the Emergency Heat relay and the highest heat stage Cooling system is off Compressor is de energized Heat The thermostat controls the heating Off Both the heating and cooling are off Cool The thermostat controls the cooling Auto The thermostat automatically changes between heating and cooling operation depending on the indoor temperature Fan settings control the system fan On Fan operates ...

Page 5: ...on i key with the increase s and decrease t keys until the first number is displayed All display segments appear for approximately three seconds before the number is displayed See Fig 10 and 11 To advance to the next Installer Setup press the Time key To change a setting use the increase s or decrease t key To scroll the Installer Setup numbers backward press the Time key To exit the Installer Set...

Page 6: ...isplay 14 0 Temperature is displayed in F 1 Temperature is displayed in C Not Used 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not Used 17 thru 18 Extended fan operation in heating 19 0 No extended fan operation after the call for heat ends 1 Fan operation is extended 90 seconds after the call for heat ends Extended fan operation in cooling 20 No extended fan operation after t...

Page 7: ... adjustment 37 0 No difference in displayed temperature and actual room temperature 3 thru 3 1 Display adjusts to 1 F higher than actual room temperature 2 Display adjusts to 2 F higher than actual room temperature 3 Display adjusts to 3 F higher than actual room temperature 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Di...

Page 8: ...System Test Avoid cycling compressor quickly To start the system test Press and hold the increase s and decrease t keys at the same time until 10 appears All segments of the display are displayed before the 10 appears See Fig 12 and 13 Table 4 Tests Available In Installer System Test M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Retur...

Page 9: ...ing Equipment System Test Time 10 Enter heating equipment system test s 11 Stage one heat comes on The system fan is also energized s 12 Stage two heat comes on Stage one heat and system fan remain on s 13 Stage three heat comes on Stage one and two remain on t 12 Stage three heat turns off t 11 Stage two heat turns off t 10 Stage one heat and system fan turn off Emergency Equipment Heating Equipm...

Page 10: ...re identification code Example 02 software ID code 2 4 Press the increase s key again to display the software revision number Example 001 Revision number 1 5 Press the increase s key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the System Test The System Test times out after four minutes without any key presses CHECKOUT Outdoor Tempe...

Page 11: ...power to the thermostat Check for 24 Vac between R and W terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connec...

Page 12: ... or cool air is coming from the registers Heating or cooling equipment is not operating Verify operation of heating or cooling equipment in self test Outdoor tempera ture not displayeda Option not activated Enter Installer Setup number 24 and set to 1 Thermostat must have OT terminals and a C7089B1000 installed Outdoor temperature display is incorrecta Outdoor sensor is connected incorrectly Refer...

Reviews: