background image

® U.S. Registered Trademark
Copyright © 2002 Honeywell •   

 • All Rights Reserved

69-1415—1

INSTALLATION INSTRUCTIONS

T8611M Deluxe Programmable

Heat Pump Thermostats

APPLICATION

The T8611M Deluxe Programmable Heat Pump Thermostat provides electronic control of 24 Vac single-zone two 
compressor or two speed heat pump systems with auxiliary heat. The T8611M can be configured to run a single 
compressor heat pump system. Refer to Table 1 for a general description of the thermostat. All T8611 thermostats 
require a common wire to supply power.

Table 1. Description of T8611 Thermostats.

MERCURY NOTICE

If this control is replacing a control that contains 
mercury in a sealed tube, do not place your old 
control in the trash. Dispose of properly.

Contact your local waste management authority 
for instructions regarding recycling and the 
proper disposal of the old control. 

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
the instructions can damage the product or cause 
a hazardous condition.

2.

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After completing installation, use these instructions 
to check out the product operation.

Location

Install the thermostat about 5 ft (1.5m) above the floor in 
an area with good air circulation at average temperature. 
See Fig. 1.

Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall 

behind the thermostat.

T8611

Changeover

System Selection

Fan

Selection

Comments

M

Automatic

Em Heat-Heat-Off-Cool-Auto

On-Auto

Down-selectable for single-compressor 
systems.

Summary of Contents for Tradeline T8611M

Page 1: ...er disposal of the old control INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing...

Page 2: ...hen not level 2 Use a pencil to mark the mounting holes See Fig 2 3 Remove the wallplate from the wall and drill two 76 mm 3 16 inch holes in the wall if drywall as marked For firmer material such as plaster drill two 5 56 mm 7 32 inch holes Gently tap anchors provided into the drilled holes until flush with the wall 4 Position the wallplate over the holes pulling wires through the wiring opening ...

Page 3: ...R C7089B1000 AND CONFIGURE INSTALLER SETUP NUMBER 24 TO 1 BE SURE INSTALLER SETUP NUMBER 3 IS SET TO 2 FOR TWO COMPRESSOR SYSTEMS WIRE EQUIPMENT MONITOR OR DEFROST RESET CONTROL PER MANUFACTURER INSTRUCTIONS CONFIGURE IN INSTALLER SETUP 1 AUX HEAT RELAY M13289 COMPRESSOR CONTACTOR 1 FAN RELAY R OT OT O B G Y1 C E W3 OUTDOOR TEMPERATURE SENSOR COOL HEAT CHANGEOVER VALVE EM HEAT RELAY THERMOSTAT 1 2...

Page 4: ... cycles the Emergency Heat relay and the highest heat stage Cooling system is off Compressor is de energized Heat The thermostat controls the heating Off Both the heating and cooling are off Cool The thermostat controls the cooling Auto The thermostat automatically changes between heating and cooling operation depending on the indoor temperature Fan settings control the system fan On Fan operates ...

Page 5: ...on i key with the increase s and decrease t keys until the first number is displayed All display segments appear for approximately three seconds before the number is displayed See Fig 10 and 11 To advance to the next Installer Setup press the Time key To change a setting use the increase s or decrease t key To scroll the Installer Setup numbers backward press the Time key To exit the Installer Set...

Page 6: ...isplay 14 0 Temperature is displayed in F 1 Temperature is displayed in C Not Used 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not Used 17 thru 18 Extended fan operation in heating 19 0 No extended fan operation after the call for heat ends 1 Fan operation is extended 90 seconds after the call for heat ends Extended fan operation in cooling 20 No extended fan operation after t...

Page 7: ... adjustment 37 0 No difference in displayed temperature and actual room temperature 3 thru 3 1 Display adjusts to 1 F higher than actual room temperature 2 Display adjusts to 2 F higher than actual room temperature 3 Display adjusts to 3 F higher than actual room temperature 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Di...

Page 8: ...System Test Avoid cycling compressor quickly To start the system test Press and hold the increase s and decrease t keys at the same time until 10 appears All segments of the display are displayed before the 10 appears See Fig 12 and 13 Table 4 Tests Available In Installer System Test M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Retur...

Page 9: ...ing Equipment System Test Time 10 Enter heating equipment system test s 11 Stage one heat comes on The system fan is also energized s 12 Stage two heat comes on Stage one heat and system fan remain on s 13 Stage three heat comes on Stage one and two remain on t 12 Stage three heat turns off t 11 Stage two heat turns off t 10 Stage one heat and system fan turn off Emergency Equipment Heating Equipm...

Page 10: ...re identification code Example 02 software ID code 2 4 Press the increase s key again to display the software revision number Example 001 Revision number 1 5 Press the increase s key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the System Test The System Test times out after four minutes without any key presses CHECKOUT Outdoor Tempe...

Page 11: ...power to the thermostat Check for 24 Vac between R and W terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connec...

Page 12: ... or cool air is coming from the registers Heating or cooling equipment is not operating Verify operation of heating or cooling equipment in self test Outdoor tempera ture not displayeda Option not activated Enter Installer Setup number 24 and set to 1 Thermostat must have OT terminals and a C7089B1000 installed Outdoor temperature display is incorrecta Outdoor sensor is connected incorrectly Refer...

Reviews: