C554A CADMIUM SULFIDE FLAME DETECTOR

OIL LINE

SCREW

OIL LINE ADAPTER 
BRACKET

TO
NOZZLE

MOUNTING
BRACKET

LEADWIRE

SOCKET

PLUG-IN
CELL

M7856

Fig. 5. Use oil line adapter bracket to mount

C554A on oil line.

Wiring

Disconnect power supply before beginning wiring to
prevent electrical shock or equipment damage.

All wiring must comply with local electrical codes and
ordinances. See Fig. 6 for a typical C554A hookup to the
oil burner primary control.

T

T

F

F

THERMOSTAT
(24 VOLT)

C554A
CAD CELL

OIL BURNER RELAY

M7858

Fig. 6. Typical hookup for C554A to oil

burner primary control.

CHECKOUT

To check cad cell operation, use the following procedure:

Disconnect cad cell leadwires; then start burner.
Shortly after burner starts, place a temporary jumper
between terminals F-F. Connect an ohmmeter
across cad cell leadwires; resistance should be less
than 1600 ohms.

Stop burner and remove temporary jumper.

With burner off, check dark cell resistance across
cad cell leadwires. Resistance should be greater
than 20,000 ohms.

NOTE:

If cell resistances are different than
specified, recheck wiring and location of
cell. If necessary, replace plug-in portion of
cell, Honeywell part no. 130367 Replace-
ment Cad Cell.

Reconnect cad cell leadwires. Check the
Protectorelay

 (burner sequencing relay) control

according to the instructions packed with the control.

SERVICE AND REPLACEMENT

Under normal operating conditions, the C554A does not
require cleaning. If a badly adjusted burner causes heavy
accumulation of dirt and soot on the cell surface, carefully
wipe the cell surface to restore full view of the oil flame.

If the C554A is damaged, replace the plug-in portion of the
cell. Order Honeywell part no. 130367 Replacement Cad
Cell.

Summary of Contents for TRADELINE C554A

Page 1: ...M7854 PLUG IN CELL MOUNTING BRACKET SOCKET LEADWIRE Fig 1 C554A Cadmium Sulfide Flame Detector cad cell INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must...

Page 2: ...sert the mounting bracket into the slot on the socket Fig 3 as far as it will go NOTE Bend the mounting bracket to fit if necessary 쐋 While holding the mounting bracket in the slot insert the screwdriver in the other end of the slot Fig 4 Bend the screwdriver first to the left then to the right to crimp the end of the mounting bracket and hold it in position 쐏 Remove the screwdriver and replace th...

Page 3: ...n terminals F F Connect an ohmmeter across cad cell leadwires resistance should be less than 1600 ohms 쐇 Stop burner and remove temporary jumper 쐋 With burner off check dark cell resistance across cad cell leadwires Resistance should be greater than 20 000 ohms NOTE If cell resistances are different than specified recheck wiring and location of cell If necessary replace plug in portion of cell Hon...

Page 4: ...UM SULFIDE FLAME DETECTOR Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 60 0164 1 J S Rev 2 96 Automation and Control Solutions Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 ...

Reviews: