background image

60-0164—1

2

C554A CADMIUM SULFIDE FLAME DETECTOR

While holding the mounting bracket in the slot,
insert the screwdriver in the other end of the slot
(Fig. 4). Bend the screwdriver first to the left, then
to the right, to crimp the end of the mounting
bracket and hold it in position.

Remove the screwdriver and replace the cell.

Mount the new cell and bracket assembly in the
location of the old assembly.

BRACKET

SLOT

SOCKET

LEADWIRE

M7853

Fig. 3. Insert mounting bracket into socket slot.

Oil Line Mounting

If desired, mount the C554A on the oil line using the oil line
adapter bracket and the mounting bracket supplied.

Remove the cell from the socket.

Insert the mounting bracket into the slot on the
socket (Fig. 3) as far as it will go.

NOTE:

Bend the mounting bracket to fit, if
necessary.

While holding the mounting bracket in the slot, insert
the screwdriver in the other end of the slot (Fig. 4).
Bend the screwdriver first to the left, then to the
right, to crimp the end of the mounting bracket and
hold it in position.

Remove the screwdriver and replace the cell.

Slide the mounting bracket into the sleeve on the oil
line adapter bracket. Push firmly to lock the cell and
the bracket assembly in position.

Mount the oil line adapter bracket on the oil line
using the screw and nut provided (Fig. 5).

BRACKET

BRACKET

SOCKET

SOCKET

LEADWIRE

SCREWDRIVER

SCREWDRIVER

SLOT

INSERT SCREWDRIVER AND MOVE IN DIRECTION SHOWN BY
ARROWS TO SECURE BRACKET IN SOCKET

M7855

Fig. 4. Insert screwdriver to secure bracket in socket.

Summary of Contents for TRADELINE C554A

Page 1: ...M7854 PLUG IN CELL MOUNTING BRACKET SOCKET LEADWIRE Fig 1 C554A Cadmium Sulfide Flame Detector cad cell INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must...

Page 2: ...sert the mounting bracket into the slot on the socket Fig 3 as far as it will go NOTE Bend the mounting bracket to fit if necessary 쐋 While holding the mounting bracket in the slot insert the screwdriver in the other end of the slot Fig 4 Bend the screwdriver first to the left then to the right to crimp the end of the mounting bracket and hold it in position 쐏 Remove the screwdriver and replace th...

Page 3: ...n terminals F F Connect an ohmmeter across cad cell leadwires resistance should be less than 1600 ohms 쐇 Stop burner and remove temporary jumper 쐋 With burner off check dark cell resistance across cad cell leadwires Resistance should be greater than 20 000 ohms NOTE If cell resistances are different than specified recheck wiring and location of cell If necessary replace plug in portion of cell Hon...

Page 4: ...UM SULFIDE FLAME DETECTOR Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 60 0164 1 J S Rev 2 96 Automation and Control Solutions Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 ...

Reviews: