Page 10
NET
NET
NET A/B (no polarity)
L
ON
W
ORKS
Data Cables
•
The L
ON
W
ORKS
1
data cable must be twisted-pair.
•
In a free-topology configuration, the sum total of the sections must not
exceed 500m.
•
In a bus configuration, the sum total of the sections must not exceed
2700m.
•
In a free-topology configuration, activate the 50ohm terminator by placing
the appropriate jumper on the FTT10A plug-in of the CTU-PLG06 board
inside the TemaServer.
•
In a bus configuration, place two terminators (with resistance values of
100ohm 1% ½W) at the two ends of the bus.
1
L
ON
W
ORKS
®
is a trademark of Echelon Corporation