background image

BACNET® FIXED FUNCTION THERMOSTAT

31-00093—01

2

Location

Do not install the thermostat where it can be affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall 

behind the thermostat.

IMPORTANT

To avoid electrical interference, which can cause 
erratic performances, keep wiring runs as short as 
possible and do not run thermostat wires adjacent 
to the line voltage electrical distribution systems. 
Use shielded cable. The cable shield must be 
grounded only at the controlled equipment case.

WHEN USED TO SENSE ROOM TEMPERATURE

Install the thermostat about 5 ft. (1.5m) above the floor in 
an area with good air circulation at average temperature. 
(See Fig. 2.)

WHEN NOT USED TO SENSE ROOM TEMPERATURE

When using the remote-mounted temperature (and 
humidity) sensor(s) to sense ambient conditions, install 
the thermostat in an area that is accessible for setting and 
adjusting the temperature and settings.

Fig. 2. Typical location of thermostat 

or remote-mounted sensor.

Mounting Wallplate

The thermostat can be mounted horizontally on the wall or 
on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.

1.

Position and level the wallplate (for appearance only).

2.

Use a pencil to mark the mounting holes (see Fig. 3).

3.

Drill two pilot holes in the wall, on the marks. For dry-
wall, drill 3/16-in. holes. For firmer material such as 
plaster, drill 7/32-in. holes. Gently tap anchors (pro-
vided) into the pilot holes until flush with the wall.

4.

Pull the wires through the wiring opening, and posi-
tion the wallplate over the mounting holes.

5.

Insert the screws into the holes and tighten.

Fig. 3. Wallplate dimensions.

Wiring the Wallplate

IMPORTANT

All wiring must comply with local electrical codes 
and ordinances.

NOTE:

Maximum (and recommended) wire size is 18-
gauge. Do not use wire smaller than 22-gauge.

Follow equipment manufacturer wiring instructions when 
available. A letter code is located near each terminal for 
identification.

CAUTION

Power must not be connected while wiring.

Wiring a unit that is powered may result in 
electrical shock and/or equipment damage.

1.

Connect wires to the terminal blocks. See Fig. 4 for 
terminal assignments and Table 1 for terminal 
descriptions.

2.

Securely tighten each screw.

3.

Push excess wire back into the hole.

4.

Plug the hole with non-flammable insulation to pre-
vent drafts from affecting the Fixed Function Ther-
mostat.

5.

Check for loose or frayed wire that may cause a short.

5 FEET

(1.5 METERS)

YES

NO

NO

NO

M4823A

Summary of Contents for TB3026B

Page 1: ...ls are TB3026B and TB3026B W which includes a wireless sensor option INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check ratings given in instructions and on the product to ensure the product is suitable for the application 3 Installer must be a trained experienced service technician 4 ...

Page 2: ...n a 4 in x 2 in 101 6 mm x 50 8 mm wiring box 1 Position and level the wallplate for appearance only 2 Use a pencil to mark the mounting holes see Fig 3 3 Drill two pilot holes in the wall on the marks For dry wall drill 3 16 in holes For firmer material such as plaster drill 7 32 in holes Gently tap anchors pro vided into the pilot holes until flush with the wall 4 Pull the wires through the wiri...

Page 3: ... Analog Output 16 GND Ground 17 BO2 Relay Output 18 BO3 Relay Output 19 BO4 Relay Output 20 BO5 Relay Output Table 2 MS TP LAN facts Transmission speed 9 6 19 2 38 4 76 8Kbps configured at global controller Layout Bus Cabling BACnet specifies the following Shielded twisted pair cabling with characteristic impedance between 100 and 130W Distributed capacitance between conductors must be less than 3...

Page 4: ...es and becomes more square When the resistance value increases the amplitude of the wave form increases and becomes less square Typically precision resistors in the range 80 130 Ohms 1 yield acceptable results Ideally the value of the terminating resistors should match the rated characteristic impedance of the installed cable For example if the installed MS TP cable has a listed characteristic imp...

Page 5: ...one to exit installer setup For example if the MAC address is 15 and the device instance to 1876 use these settings ISU code 800 15 ISU code 801 0 ISU code 802 00 ISU code 803 18 ISU code 804 76 Installer Setup ISU Codes Installer setup mode provides access to functions specific to installation of a BACnet FF Some BACnet FF configuration parameters can be altered from the ISU screens The ISU param...

Page 6: ... Hum pad change reminder AV 125 0 reminder not used 1 90 days 2 180 days 3 365 days 520 UV lamp change reminder AV 126 0 reminder not used 1 365 days 540 Program periods AV 129 2 Wake Sleep 4 Wake Leave Return Sleep 640 Clock format BV 83 12 12 hour BV 83 0 24 24 hour BV 83 1 670 Keypad lock AV 128 0 no lock 1 access temperature settings only 2 fully locked 700 Sensed room temperature offset AV 13...

Page 7: ...a radio signal 4 Activate the sensor to be paired NOTE Pairing times out after 10 seconds of no pairing activity 5 Verify that the BACnet FF and sensor successfully paired Paired sensor status is displayed replacing Timed out RESET is displayed and sensor status is Fig 10 Door sensor number 1 paired and in closed status TO ERASE SENSOR TO BACNET FF PAIRINGS 1 While viewing any sensor status screen...

Page 8: ...ersal inputs with 12 bit accuracy providing con trolled voltage current and resistive modes Internal Sensors 1 internal temperature sensor 0 120 deg F 17 8 48 9 deg C 1 internal humidity 5 95 RH non condens ing Relay Outputs 6 relay outputs normally open contacts with a maximum switch rating of 24VAC 0 5A 12VA BO 0 BO 2 and BO 5 are powered from the controller transformer BO 1 BO 3 and BO 4 are po...

Reviews: