TB3 SERIES COMMUNICATING THERMOSTATS INSTALLATION INSTRUCTIONS
31-00576-01
20
11 Analog
Value #11
10 °C to 25 °C
(50 °F to 77 °F)
Changeover
Temperature
for
Cooling
If “Universal Input” is
set to “3”, this
parameter adjusts
changeover
temperature for cooling
mode.
16 °C
(61 °F)
R/W
-
12 Analog
Value #12
26 °C to 45 °C
(79 °F to 113 °F)
Changeover
Temperature
for Heating
If “Universal Input” is
set to “3”, this
parameter adjusts
changeover
temperature for heating
mode.
28 °C
(82 °F)
R/W
-
13 Analog
Value #13 0 to 255 minutes
Mode
Change
Delay
This parameter adjusts
the delay time between
heat and cool modes.
3 minutes R/W
-
14 Analog
Value #14
-10 °C to 10 °C
(-18 °F to 18 °F)
Universal
Input
Temperature
Calibration
This parameter adjusts
sensor value calibrate
with 0.1 °C (1°F) steps.
0 °C
(0 °F)
R/W
-
15 Analog
Value #15
0 °C to 15 °C
(0 °F to 27 °F)
Dead Zone
If “Mode” is set to
“Auto”, this parameter
adjusts the dead zone.
2 °C
(4 °F)
R/W
-
16 Analog
Value #16
0 °C to 15 °C
(0 °F to 27 °F)
Hysteresis
This parameter adjusts
the hysteresis.
1 °C
(2 °F)
R/W
-
17 Analog
Value #17 0 to 5 second
Fan Stage
Change
Delay
This parameter adjusts
the delay of the
changing range of the
fan.
2 Second
R/W
-
18 Analog
Value #18 0 to 60 second
Fan Off
Delay
This parameter adjusts
delay of the closing
time the fan.
0 Second
R/W
-
19 Analog
Value #19 0 to 3
Fan Status
0 = Off
1 = Low
2 = Med
3 = High
0
R
COV
20 Analog
Value #20 1 to 100
Valve
Proportional
Band
This parameter
determines the fan's
output value
proportionally
depending on the
difference between
Room Temperature and
Set Point.
Range: 0.1°C to 10°C
20
R/W
COV
21 Analog
Value #21 0 to 100
VA1 State
0 V to 10 V
0
O
COV
22 Analog
Value #22 0 to 100
VA2 State
0 V to 10 V
0
O
COV
NO OBJECT
VALUE
OBJECT
NAME
FUNCTION
DEFAULT READ (R)/
WRITE (W)
COV
PROPERTY