TB3 SERIES COMMUNICATING THERMOSTATS INSTALLATION INSTRUCTIONS
19
31-00576-01
5
Analog
Value #5
5°C to 40 °C
(41°F to 104°F)
Set Point
Low Limit
This parameter adjusts
the low limit for desired
room temperature.
5 °C
(41°F)
R/W
-
6
Analog
Value #6
0 to 63
Key Lock
0 = Unlocked
1 = Lock On/Off
2 = Lock Mode
4 = Lock Setpoint
8 = Lock Fan Speed
16 = Lock Time Settings
32 = Lock Time
Schedule
Settings 63 = Locked All
NOTE:
To lock two or
more buttons at
the same time,
add the button
values. Enter 12
to lock the
setpoint (4) and
fan speed (8).
0
R/W
-
7
Analog
Value #7
0 to 2
Power
Failure
This parameter adjusts
the condition that the
device will continue
when
the power failure. 0 =
Device
starts off
1 = Device starts on
2 = Keep State Before
Power
Failure
2
R/W
-
8
Analog
Value #8
2 to 4
Fan Coil
Type
2 = 2 Pipe System
4 = 4 Pipe System
4
R/W
-
9
Analog
Value #9
-10 °C to 10 °C
(-18 °F to 18 °F)
Internal
Temperature
Sensor
Calibration
This parameter adjusts
sensor value calibrate
with 0.1 °C (1°F) steps.
0 °C
(0 °F)
R/W
-
10 Analog
Value #10 0 to 5
Universal
Input
0 = Not Used
1=External temperature
sensor for room (NTC
10K)
2 = External sensor for
room (NTC 10K)
3 = Changeover sensor
(NTC 10K)
4 = Windows
contact/Energy saving-
On/Off (NC Contact)
5 = Windows
contact/Energy saving-
Off/On (NO Contact)
0
R/W
COV
NO OBJECT
VALUE
OBJECT
NAME
FUNCTION
DEFAULT READ (R)/
WRITE (W)
COV
PROPERTY