background image

Summary of Contents for T8611G Chmnothern IV

Page 1: ...an area with good air circulation at average temperature See Fig 1 DO not install the thermostat where it can be affected by drafts or dead sppts behind doors and incornere hot or cold air from ducts radiant heat from sun or appliances m concealed pipes and chimneys unheatad unccoled areas such as an outaide wall behind the thermostat WallplateInstallation The thermostat can be mounted horizontall...

Page 2: ...g 2 Mounting tim wallplate IMPORTANT Use 18 gauge color coded thermostat cabl6 for proper wiring 2 Securely tighten each terminal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat Fig 3 _plcat hookup of TSE11G in a heat pump system 69 0936_1 2 ...

Page 3: ... setting is Heat and the fan default setting is Auto Use the System and Fan keys to change the settings See Fig 7 The fan settings can be set for each program period individually The system selection is for all the program periods System settings control the thermostat operation as follows Em Heat Emergency heat relay Is on conttnuousty Thermostat cycles highest stage of heat Cooling system is off...

Page 4: ...lnt Setting Wake 6 00 AM 70 F 78 F Auto 21 C 25 5 C eave 8 00 AM 62 F B5 F Auto 1E 5 C 29 5 C Return 6 00 PM 7O F 78 F Auto 21 C 28 5 C Sleep 10 00 PM 62 F B2 F Auto t6 5 C 28 C Rg 7 T8611G System and Fan key locations TWO LED INO_CATORS Rg 8 LEDs location INSTALLER SETUP NOTE For most applications the thermostat factory settings will not need to be changed Review the factory settings in Table 2 a...

Page 5: ...ostat doesnofhavea systam k_ _ Setup Nunfosr12 wi I notbe dtsp ayed Rewew Table 3 factoty smtir_js andrnatk any d_ired changes in _e Aof_al _ttlr_ _umn Whenlnstal_rSetupiscomp_e t_ew _e settingstocon_rm_at theymatch_e _atam Select got used taating cycle Not used Systemsetting adjustment Adaptive Intelligent ReCoveryTM control Degree temperature display N_used Clock format Not used Extended fan ope...

Page 6: ...oser than 3 F chosen value 1 5 C 4 4OF 2oc 5 5OF 2 goc _ F 3 C 7 7OF 3 5_C 8 8OF 4oC 9_9 F 4 5oc 10 10OF 5oC Not used 31 and 32 Minimum off 33 5 5 minute minimum 0 thru Minimum number of minutes O time for the off time for the 4 thru 5 the compressor will be oft compressor compressor between calJsfor the compressor Temperature 34 90 Highest setpoint 40 to I Temperature range 1OF range stops in hea...

Page 7: ...tem Test to check the thermostat operation Refer to Table 4 for a list of the available system tasts To start the system test CAUTION The minimum off time for compressors Is bypassed during the Installer System Test Equipment damage can occur if the compressor is cycled too quickly Press and hold the increase and decrease keys at the same time until 10 appears All segments of the display will be d...

Page 8: ...em test 31 Cool and system fan come on 30 Cool and system fan turn off Fan Equipment System Teat Time A 40 Change from cooling to fan equipment system tast 41 Fan comes on 40 Fan turns off Key Operation System Teat TJme_ I 60 2 _Change from fan to key opera on syst Eu3 _st I I NOTE Press any key and the disptaysd numbers will change Press Time to go to the previous test and the Time _ to go to the...

Page 9: ...configured for F Enter installer Setup number 14 and reconfigure the display 3r C display Bad thermostat location Relocate the thermostat Temperature rhe upper or lower temperature Check the temperature setpointa settings will not imits were reached Heating limits are 40 to 90 F 4 5 to 32 C change Example Cooling limits are 48 to 99 F 7 to 37 C Cannot set the heating higher or The setpoint tempera...

Page 10: ...24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off pesition_sst to the On position check wiring between thermostat and HVAC eduipment replace any broken wires and tighten any loose connectk_ns If 24 Vac is present proceed with troubleshooting Wait up to five minute...

Page 11: ...11 69 0936_1 ...

Page 12: ... Control Honeywell Inc Honeywell Limited Honeywell Limit_e Honeywell Plaza 155 Gordon Baker Road P O Box 524 North York Ontario Minneapolis MN 55408_9524 M2H 3N7 69 0936 1 J H Ray 6 97 PrlntBdinTaiwan LO C Uon l Helping You Control Your World _ ...

Reviews: