T8601D CHRONOTHERM

® 

IV DELUXE ZONE THERMOSTATS

69-1413—2

6

Not Used.

15

Clock format.

16

0

12-hour clock 
format.

1

24-hour clock format.

Not Used.

17 and 18

Extended fan 
operation in 
heating

a

19

0

No extended fan 
operation after the 
call for heat ends.

1

Fan operation is extended 
90 seconds after the call for 
heat ends.

Extended fan 
operation in 
cooling

a

20

No extended fan 
operation after the 
call for cool ends.

1

Fan operation is extended 
90 seconds after the call for 
cool ends.

Not Used.

21 thru 23

Outdoor 
temperature 
display

a

 

24

0

No outdoor 
temperature is 
displayed.

1

Outdoor temperature is 
displayed. Needs a 
C7089B1000 Outdoor 
Temperature Sensor to 
operate.

Not Used.

25 thru 29

Deadband

30

3

Heating and 
cooling setpoints 
can be set no 
closer than 3°F 
(1.5°C).

3 thru 10 Heating and cooling 

setpoints can be set no 
closer than the chosen 
value:

2—2°F (1°C)
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)

Not Used.

31and 32

Minimum off 
time for the 
compressor.

33

5

5 minute minimum 
off time for the 
compressor.

0 thru 4

Minimum number of minutes 
(0 thru 5) the compressor is 
off between calls for the 
compressor.

Temperature 
range stops in 
heating.

34

90

Highest heating 
setpoint setting.

40 to 89

Temperature range (1°F 
increments) heating setpoint 
can be set to.

Temperature 
range stops in 
cooling.

35

45

Lowest cooling 
setpoint setting.

46 to 99

Temperature range (1°F 
increments) cooling setpoint 
can be set to.

System on 
indicator 
(flame=heat, 
snowflake= 
cool) is 
displayed.

a

36

0

LCD On symbol is 
displayed when 
system is 
energized.

1

Display is disabled.

Available on select models.

Table 4. Thermostat Installer Setup Options. (Continued)

Select

Installer Setup 

Number (Press 

Time 

 key to 

change)

Factory Setting

Other Choices

(Press 

s

 or 

t

 key to change)

Actual 

Setting

Display

Description

Display

Description

69-1413-2.fm  Page 6  Wednesday, July 13, 2005  10:07 AM

Summary of Contents for T8601D

Page 1: ...n area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat Wallplate Installation The thermostat can be mounted horizontally...

Page 2: ...the hole 4 Plug the hole with nonflammable insulation to pre vent drafts from affecting the thermostat The two OC terminals can be wired to the TZ 3 panel for remote operation of the Zone A Lone feature during the Leave and Sleep periods See Table 2 and the TZ 3 Installation Instructions form 68 0223 for more information Table 2 Occupied Terminal Operation Fig 3 Typical wiring diagram for T8601D o...

Page 3: ...the wall first pull out at the bottom of the thermostat remove top last Fig 6 Mounting thermostat on wallplate O G B C Y R W OC OC OT W2 L G Y R W M6 M4 M1 OT THERMOSTAT TotalZone PANEL THERMOSTAT CONNECTIONS C7089B OUTDOOR TEMPERATURE SENSOR OPTIONAL M12183A TO OC ON TZ 3 USE ON ZONE 1 THERMOSTAT ONLY TO OC ON TZ 3 1 1 O B AND STAGE JUMPER MUST BE CONFIGURED FOR TZ 3 M4826 FOR WRAPAROUND INSERTIO...

Page 4: ...n until the time is blank The fan setting feature is available on select thermostat models See Owner s Guide form number 69 1400 for complete instructions on changing the program Table 3 Default Program Settings INSTALLER SETUP NOTE For most applications the thermostat factory settings will not need to be changed Review the factory settings in Table 2 and if no changes are necessary go to the Inst...

Page 5: ... Actual Setting column When Installer Setup is com plete review the settings to confirm that they match the system M14559 Aux Ht Set Day Time Set Program Mon Wake Leave Return Sleep Outdoor Room Filter Wait System Fan Em Heat On Auto Off Cool Auto AM PM Hold for Heat Cool Repl Batt Recovery DST Tue Wed Thu Fri Sat Sun Days Temporary Setting Em Ht M14618 INSTALLER SETUP NUMBER DISPLAY COLUMN 2 OF T...

Page 6: ...en value 2 2 F 1 C 4 4 F 2 C 5 5 F 2 5 C 6 6 F 3 C 7 7 F 3 5 C 8 8 F 4 C 9 9 F 4 5 C 10 10 F 5 C Not Used 31and 32 Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 Minimum number of minutes 0 thru 5 the compressor is off between calls for the compressor Temperature range stops in heating 34 90 Highest heating setpoint setting 40 to 89 Temperature range...

Page 7: ...ture 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Display adjusts to 3 F lower than actual room temperature Furnace Air Filter Timer 43 2 30 days System run time 0 1 3 4 0 off 1 10 days 3 60 days 4 120 days Time is counted when heat cool or fan running Humidifier Pad Monitor 44 0 Off 1 2 3 1 90 days 2 180 days 3 365 days ...

Page 8: ...pressor quickly To start the system test Press and hold the increase s and decrease t keys at the same time until 10 appears All segments of the display will be displayed before the 10 appears See Fig 11 and 12 Table 5 Tests Available In Installer System Test M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Return Sleep Day Heat Cool Set...

Page 9: ... Wake Leave Return Sleep Outdoor Room Filter Wait System Fan Em Heat On Auto Off Cool Auto AM PM Hold for Heat Cool Repl Batt Recovery DST Tue Wed Thu Fri Sat Sun Days Temporary Setting Em Ht M14612 Keys to Press Test Number Description Heating Equipment Self Test Time 10 Enter heating equipment self test s 11 Heat comes on When Installer Setup number 2 is 1 the system fan is also energized t 10 H...

Page 10: ...le 02 software ID code 2 4 Press the increase s key again to display the soft ware revision number Example 001 Revision number 1 5 Press the increase s key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the system test The system test times out after four minutes without any key presses CHECKOUT Outdoor Temperature Sensor Select Models...

Page 11: ...k for 24 Vac between R and C terminals If missing 24 Vac verify that thermostat is correctly wired to the zone con trol panel R on the thermostat to R on the TZ 3 and C to M1 R on the thermostat to R on the EMM 3U and C to C verify the wiring between thermostat and zone control panel replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermo...

Page 12: ...RONOTHERM IV DELUXE ZONE THERMOSTATS Automation and Control Solutions Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 69 1413 2 fm Page 12 Wednesday July 13 2005 10 07 AM ...

Reviews: