background image

T8601D CHRONOTHERM

® 

IV DELUXE ZONE THERMOSTATS

11

69-1413—2

TROUBLESHOOTING GUIDE

Table 7. Troubleshooting Guide.

Symptom

Possible Cause

Action

Display does not 
come on.

Thermostat is not being 
powered.

• Check for 24 Vac between R and C terminals.

— If missing 24 Vac:

— verify that thermostat is correctly wired to the zone con-

trol panel. 

— R on the thermostat to R on the TZ-3 and C to M1.
— R on the thermostat to R on the EMM-3U and C to C.
— verify the wiring between thermostat and zone control 
panel.
— replace any broken wires and tighten any loose 
connections.

— If 24 Vac is present, proceed with troubleshooting

Thermostat is not fully 
connected to wallplate.

Verify that thermostat is correctly positioned and securely 

latched to wallplate.

Temperature 
display is incorrect.

Room temperature display has 
been reconfigured.

Enter Installer Setup number 37 and reconfigure the display.

Thermostat is configured to °F 
or °C display.

Enter Installer Setup number 14 and reconfigure the display.

Bad thermostat location. 

Relocate the thermostat.

Temperature 
settings do not 
change. (Example: 
Cannot set the 
heating higher or 
the cooling lower.)

The upper or lower temperature 
limits were reached. 

Check the temperature setpoints:

• Heating limits are 40 to 90°F (7 to 31°C).
• Cooling limits are 45 to 99°F (9 to 37°C).

The setpoint temperature range 
stops were configured.

Check Installer Setup numbers 34 and 35 and reconfigure the 
setpoint stops.

Heating or cooling 
does not come on.

No power to the thermostat

• Check for 24 Vac between R and C terminals.

— If missing 24 Vac:

— verify that thermostat is correctly wired to the zone con-

trol panel. 

— R on the thermostat to R on the TZ-3 and C to M1.
— R on the thermostat to R on the EMM-3U and C to C.
— verify the wiring between thermostat and zone control 
panel.
— replace any broken wires and tighten any loose 
connections.

— If 24 Vac is present, proceed with troubleshooting

Thermostat minimum off time is 
activated.

Wait up to five minutes for the thermostat to respond.
Enter Installer Setup number 33.
Reconfigure the minimum off time, if required.

System selector is set to off.

Verify that the system selector is set for Heat, Cool or Auto.

Thermostat is not calling for 
heat or cool.

Verify that the heat or cool icon (flame or snowflake) is present. 
If not, raise or lower the setpoint to make a call for cool or heat.

System on indicator 
(flame=heat, 
snowflake=cool) is 
displayed, but no 
warm or cool air is 
coming from the 
registers.

Thermostat is not wired 
correctly to the zone panel.

Verify wiring. Check if other zones can bring on the heat or cool.

Zone panel is not correctly 
configured or wired properly.

If no zones can bring on the heat, verify equipment configuration 
and wiring.

Outdoor 
tempera-ture is not 
displayed.

Option not activated.

Enter Installer Setup number 24 and set to 1. Thermostat must 
have OT terminals and a C7089B1000 installed.

Outdoor 
temperature display 
is incorrect.

Outdoor sensor is connected 
incorrectly.

Refer to C7089B1000 Installation Instructions and check wiring 
between the thermostat and sensor.

Wrong sensor.

Replace sensor with C7089B1000 Sensor.

a

Available on select models.

69-1413-2.fm  Page 11  Wednesday, July 13, 2005  10:07 AM

Summary of Contents for T8601D

Page 1: ...n area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat Wallplate Installation The thermostat can be mounted horizontally...

Page 2: ...the hole 4 Plug the hole with nonflammable insulation to pre vent drafts from affecting the thermostat The two OC terminals can be wired to the TZ 3 panel for remote operation of the Zone A Lone feature during the Leave and Sleep periods See Table 2 and the TZ 3 Installation Instructions form 68 0223 for more information Table 2 Occupied Terminal Operation Fig 3 Typical wiring diagram for T8601D o...

Page 3: ...the wall first pull out at the bottom of the thermostat remove top last Fig 6 Mounting thermostat on wallplate O G B C Y R W OC OC OT W2 L G Y R W M6 M4 M1 OT THERMOSTAT TotalZone PANEL THERMOSTAT CONNECTIONS C7089B OUTDOOR TEMPERATURE SENSOR OPTIONAL M12183A TO OC ON TZ 3 USE ON ZONE 1 THERMOSTAT ONLY TO OC ON TZ 3 1 1 O B AND STAGE JUMPER MUST BE CONFIGURED FOR TZ 3 M4826 FOR WRAPAROUND INSERTIO...

Page 4: ...n until the time is blank The fan setting feature is available on select thermostat models See Owner s Guide form number 69 1400 for complete instructions on changing the program Table 3 Default Program Settings INSTALLER SETUP NOTE For most applications the thermostat factory settings will not need to be changed Review the factory settings in Table 2 and if no changes are necessary go to the Inst...

Page 5: ... Actual Setting column When Installer Setup is com plete review the settings to confirm that they match the system M14559 Aux Ht Set Day Time Set Program Mon Wake Leave Return Sleep Outdoor Room Filter Wait System Fan Em Heat On Auto Off Cool Auto AM PM Hold for Heat Cool Repl Batt Recovery DST Tue Wed Thu Fri Sat Sun Days Temporary Setting Em Ht M14618 INSTALLER SETUP NUMBER DISPLAY COLUMN 2 OF T...

Page 6: ...en value 2 2 F 1 C 4 4 F 2 C 5 5 F 2 5 C 6 6 F 3 C 7 7 F 3 5 C 8 8 F 4 C 9 9 F 4 5 C 10 10 F 5 C Not Used 31and 32 Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 Minimum number of minutes 0 thru 5 the compressor is off between calls for the compressor Temperature range stops in heating 34 90 Highest heating setpoint setting 40 to 89 Temperature range...

Page 7: ...ture 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Display adjusts to 3 F lower than actual room temperature Furnace Air Filter Timer 43 2 30 days System run time 0 1 3 4 0 off 1 10 days 3 60 days 4 120 days Time is counted when heat cool or fan running Humidifier Pad Monitor 44 0 Off 1 2 3 1 90 days 2 180 days 3 365 days ...

Page 8: ...pressor quickly To start the system test Press and hold the increase s and decrease t keys at the same time until 10 appears All segments of the display will be displayed before the 10 appears See Fig 11 and 12 Table 5 Tests Available In Installer System Test M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Return Sleep Day Heat Cool Set...

Page 9: ... Wake Leave Return Sleep Outdoor Room Filter Wait System Fan Em Heat On Auto Off Cool Auto AM PM Hold for Heat Cool Repl Batt Recovery DST Tue Wed Thu Fri Sat Sun Days Temporary Setting Em Ht M14612 Keys to Press Test Number Description Heating Equipment Self Test Time 10 Enter heating equipment self test s 11 Heat comes on When Installer Setup number 2 is 1 the system fan is also energized t 10 H...

Page 10: ...le 02 software ID code 2 4 Press the increase s key again to display the soft ware revision number Example 001 Revision number 1 5 Press the increase s key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the system test The system test times out after four minutes without any key presses CHECKOUT Outdoor Temperature Sensor Select Models...

Page 11: ...k for 24 Vac between R and C terminals If missing 24 Vac verify that thermostat is correctly wired to the zone con trol panel R on the thermostat to R on the TZ 3 and C to M1 R on the thermostat to R on the EMM 3U and C to C verify the wiring between thermostat and zone control panel replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermo...

Page 12: ...RONOTHERM IV DELUXE ZONE THERMOSTATS Automation and Control Solutions Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 69 1413 2 fm Page 12 Wednesday July 13 2005 10 07 AM ...

Reviews: