69-1049—1

8

T8501D DELUXE ZONE THERMOSTAT

5. Press the increase 

 key again to display the

EEPROM identification code.

6. Press and hold the increase 

 and decrease 

keys together, until the room temperature is
displayed, to exit the system-test. The system-test
times out after ten minutes without any key presses.

CHECKOUT

Outdoor Temperature Sensor
(Where Applicable)

Allow the outdoor temperature sensor to soak in the
outdoor air for a minimum of five minutes before taking a
reading. With an accurate thermometer (

±

1

°

F [

±

0.5

°

C]),

measure the temperature at the sensor location, allowing
time for the thermometer to stabilize before reading. Match
the thermometer reading to the outdoor temperature
display at the thermostat.

(Continued)

M4867

TROUBLESHOOTING GUIDE

a

Available on select models.

Symptom

Possible Cause

Action

Display will not
come on.

Thermostat is not being
powered.

Check that C terminal is connected to the system transformer.

Check for 24 Vac between C and R terminals.

If missing 24 Vac:

check if the circuit breaker is tripped—reset the
circuit breaker.

check if the system fuse is blown—replace the fuse.  

check if the power switch on the HVAC equipment is
in the Off position—set to the On position.

check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Thermostat microprocessor is
locked up.

Remove the thermostat from the wallplate for 2 minutes. After  
2 minutes, replace the thermostat on the wallplate.

Temperature
display is incorrect.

Room temperature display
has been reconfigured.

Enter Installer Setup number 37 and reconfigure the display.

Thermostat is configured for
°F or °C display.

a

Enter Installer Setup number 14 and reconfigure the display.

Bad thermostat location.

Relocate the thermostat.

Temperature
settings will not
change. (Example:
Cannot set the  

The upper or lower
temperature limits were
reached.  

Check the temperature setpoints:

Heating limits are 40 to 90°F (4.5 to 32°C)

Cooling limits are 48 to 99°F (7 to 35°C).

heating higher or
the cooling lower.)

The setpoint temperature
range stops were configured.

Check Installer Setup numbers 34 and 35 and reconfigure the
setpoint stops.

Summary of Contents for T8501D

Page 1: ... 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat Wallplate Installation The thermostat can...

Page 2: ...power before wiring to prevent electrical shock or equipment damage 1 Loosen the terminal screws on the wallplate and connect the system wires See Fig 5 IMPORTANT Use 18 gauge color coded thermostat cable for proper wiring 2 Securely tighten each terminal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat 5 FEET ...

Page 3: ...igure Installer Setup check System Test display outdoor temperature select models set the system operation set the fan operation See Fig 7 for the location of the keys Fig 7 Key locations and descriptions O G B C W R Y OT OT O1 T8 G1 T7 B1 T6 E1 T5 T4 M1 THERMOSTAT CHANGEOVER CONTROL OUTDOOR TEMPERATURE SENSOR OPTIONAL ZONE 1 M12187 O B G Y R W C OT OT W2 L G Y R W M6 M4 M1 THERMOSTAT TotalZone PA...

Page 4: ...n of key presses are required to use the Installer Setup feature To enter the Installer Setup press and hold the Information i key with the increase and decrease keys until the first number is displayed All display segments appear for approximately three seconds before the number is displayed See Fig 9 and 10 To advance to the next Installer Setup press the Information i key To change a setting us...

Page 5: ...operation after the call for cool ends 01 Fan operation is extended 90 seconds after the call for cool ends Not used 21 thru 23 Outdoor temperature displayb 24 00 No outdoor temperature is displayed 01 Outdoor temperature is displayed Needs a C7089B1000 Outdoor Sensor to operate Not used 25 thru 32 Minimum off time for the compressor 33 05 5 minute minimum off time for the compressor 00 01 02 03 o...

Page 6: ...ess and hold the increase and decrease keys together for three seconds to exit the system test The system test will time out after ten minutes without any key presses Table 4 Installer System Test Options Continued Em HeatOffCool Auto Only Heat Cool OnAuto System Fan Room Outdoor Em Ht Temporary Setting Wait Humid Aux Ht Remote Repl Batt M4844 M6792 TEST MODE NUMBER Test Number Self Test Descripti...

Page 7: ...s the thermo stat information 4 Press the increase key again to display the software revision number Example 001 Revision number 1 M4864 M10444 M4866 M6791 Key to Press Test Number Description Key Operation System Test IMPORTANT Test numbers will only be displayed when the system is configured for the selected function EXAMPLE Numbers 60 61 and 62 are the only numbers that will be displayed when a...

Page 8: ...he circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat microprocessor is locked up ...

Page 9: ...eck wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat minimum off time is activated Wait up to five minutes for the system to respond Enter Installer Setup number 33 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool System on ind...