background image

69-0959

4

T8501A,B,C,D MICROELECTRONIC THERMOSTATS

Fig. 7. Mounting thermostat on wallplate.

NOTE: To remove the thermostat from the wall, first pull out

at the bottom of the thermostat; remove top last.

Using Thermostat Keys

The thermostat keys are used to:

set temperature,

display present setting,

configure Installer Setup,

check Self-Test,

display outdoor temperature (select models).

Select models have keys to:

set the system operation,

set the fan operation.

See Fig. 8 for key information.

Fig. 8. Thermostat key locations and descriptions.

SETTINGS

System and Fan Settings

System settings control the thermostat operation as
follows:

Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between

heating and cooling operation, depending on the
indoor temperature.

Fan settings control the system fan as follows:

On: Fan operates continuously.
Auto: Equipment controls fan.

The system default setting is Heat and the fan default
setting is Auto. Use the keyboard or system and fan
switches, depending on model, to change to the desired
settings. See Figs. 9 and 10.

Fig. 9. T8501C system and fan switches location.

Fig. 10. T8501D system and fan keys location.

NOTE:

Always press the system and fan keys with your
fingertip or similar blunt tool. Sharp instruments
like a pen or pencil point can damage the
keyboard.

Temperature Settings

The default setpoint for heat is 70

°

F (21

°

C) and for cool is

78

°

F (25.5

°

C). Press the increase 

 or decrease 

 key to

change the present setting. To change between heat and
cool, press the Information

   i   

key until the setting to be

changed appears.

INSTALLER SETUP

NOTE:

For most applications, the thermostat factory-
settings do not need to be changed. Review the
factory settings in Table 2 and if no changes are
necessary, go to the Installer Self-Test section.

M6798A

B.

  

PRESS LOWER EDGE OF CASE TO LATCH.

A.

  

ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.

M10147

i

Press to select
heating or cooling
equipment.

  

Em. Ht.-Emergency heating
Heat— Heating equipment
Off — No equipment
Cool—Cooling equipment
Auto—Thermostat

automatically selects
heating and cooling
equipment.

Press to select
heating or cooling
equipment.

  

On

Fan runs continuously

Auto—Fan runs when

heating or cooling
equipment operates

System

System

System

Fan

Fan

Fan

1

1

CHECK LIGHT ON SELECT MODELS

M6801

DISPLAY PRESENT 
SETTINGS AND SCROLL 
THROUGH INSTALLER 
SETUP MODES 
(INFORMATION KEY)

i

DECREASE
TEMPERATURE 
SETTING

INCREASE
TEMPERATURE 
SETTING

M10146

i

HEAT      OFF      COOL

ON    AUTO

HEAT      OFF      COOL

ON    AUTO

SYSTEM

Selection for heating or cooling
equipment operation.

Heat - Heating equipment
Off - No equipment
Cool - Cooling equipment

FAN

On - Fan runs continuously
Auto  - Fan runs when

heating or cooling
equipment operates

Summary of Contents for t8501A

Page 1: ...g installation use these instructions to check out the product operation T8501 System Changeover System Selection Fan Selection Comments A Heat only None None None B Heat only None Heat Off On Auto Select models have only a system switch or fan switch and some models have both C Heat Cool Manual Heat Off Cool On Auto System and fan selections are done by switches D Heat Cool Automatic Heat Off Coo...

Page 2: ...he holes 쐂 Tighten mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 through 5 for typical hookups A letter code is located near each terminal for identifica tion CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 쐃 Loosen the terminal screws on the wallplate and connect the system wires See Fig 6 IMPORTANT U...

Page 3: ...O G Y W OUTDOOR TEMPERATURE SENSOR COOL CHANGEOVER VALVE OR DAMPER HEAT CHANGEOVER VALVE OR DAMPER THERMOSTAT 1 2 2 M4826 FOR WRAPAROUND INSERTION STRIP 7 16 IN 11 MM FOR STRAIGHT INSERTION STRIP 5 16 IN 8 MM L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED AVAILABLE ON SELECT MODELS JUMPER Rh TO Rc IN A SINGLE TRANSFORMER SYSTEM 1 HEATING RELAY OR VALVE COIL M48...

Page 4: ...with your fingertip or similar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard Temperature Settings The default setpoint for heat is 70 F 21 C and for cool is 78 F 25 5 C Press the increase or decrease key to change the present setting To change between heat and cool press the Information i key until the setting to be changed appears INSTALLER SETUP NOTE For most ap...

Page 5: ...on of key presses are required to use the Installer Setup feature To enter the Installer Setup mode press and hold the Information i key with the increase and decrease keys until the first mode number is displayed All display segments appear for approximately three seconds before the mode number is displayed See Figs 11 and 12 To advance to the next Installer Setup mode press the Information i key...

Page 6: ...perate Not used 25 thru 32 Minimum off time for the compressor 33 05 5 minute minimum off time for the compressor 00 01 02 03 or 04 Minimum number of minutes 0 thru 5 the compressor will be off between calls for the compressor Heating setpoint range stopa 34 90 Heating setpoint can be set no higher than 90 F 40 thru 90 Number can be set anywhere between 40 and 90 in 1 F increments Cooling setpoint...

Page 7: ...two zeros appear Continued Em HeatOffCool Auto Only Heat Cool OnAuto System Fan Room Outdoor Em Ht Temporary Setting Wait Humid Aux Ht Remote Repl Batt M4844 M6792 TEST MODE NUMBER Test Number Self Test Description 10 19 Heating equipment can be turned on and off 30 39 Cooling equipment can be turned on and off 40 49 Fan equipment T8501D only can be turned on and off 60 69 System key or system swi...

Page 8: ...ss Test Mode Number Description Key or Switch Operation Self Test a IMPORTANT Test Mode Numbers will only be displayed when the system is configured for the selected function EXAMPLE Numbers 60 61 and 62 are the only numbers that will be displayed when a system is configured for heat only SYSTEM KEY OR SWITCH SELF TEST When system switch is used move switch to see Test Mode Numbers i 60 Change fro...

Page 9: ...d tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat microprocessor is locked up Remove the thermostat from the wallplate for 2 minutes After 2 minutes replace the thermostat on the wallplate Temperature display is incorrect Room temperature display has been reconfigured Enter Installer Setup mode number 37 and reconfigure the display Thermostat is configure...

Page 10: ...ostat minimum off time is activated Wait up to five minutes for the system to respond Enter Installer Setup mode number 33 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool System On indicator is lit but no heat is being delivered Fan operation set for 00 conventional heat when it should be set for 01 electric heat Enter Installer Setup mode ...

Page 11: ...69 0959 11 T8501A B C D MICROELECTRONIC THERMOSTATS ...

Page 12: ...uilding Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 69 0959 J H 10 96 Printed in Taiwan R O C Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 www honeywell com yourhome ...

Reviews: