Honeywell T834C Quick Start Manual Download Page 8

68-0075-2   G.H.  Rev. 1-03 

www.honeywell.com/yourhome

Automation and Control Solutions

Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN  55422

Scarborough, Ontario
M1V 4Z9

Printed in U.S.A. on recycled 
paper containing at least 10% 
post-consumer paper fibers.

T834C, T8034C HEATING/COOLING THERMOSTATS

CHECKOUT

CAUTION

Checkout Method Hazard. 

Can damage thermostat heat anticipator.

Avoid checking thermostat operation by shorting 

across system control terminals.

IMPORTANT

— To ensure accurate temperature control, do not 

touch or breathe on bimetal of thermometer.

Heating

1.

Set system switch to Heat and Fan switch to Auto.

2.

Move temperature setting lever about 10°F (6°C) above 

room temperature.

• Gas or oil -fired systems: Heating starts immediately. 

Fan starts after short delay.

• Heat pump and some central electric heating 

systems: Heating and fan start.

3.

Move temperature setting lever about 10°F (6°C) below 

room temperature.

• Gas or oil-fired systems: Heating shuts off 

immediately. Fan shuts off after a short delay.

• Heat pump and some electric heat systems: Heating 

and fan shut off.

Cooling

CAUTION

Equipment Damage Hazard.

Can short-cycle air conditioner compressor.

Install minimum-off timer to provide five-minute time 

delay to prevent operating compressor for five minutes 

after thermostat turns off compressor or for five 

minutes after system receives power.

Avoid operating thermostat in cooling applications 

when outdoor temperature is below 50°F (6°C).

See air conditioner manufacturer recommendations.

1.

To prevent compressor short cycling, install a minimum 

off-timer to provide a five-minute time delay. (The time 

delay will not activate the compressor for five minutes 

after the thermostat turns off the compressor or for five 

minutes after the system receives power.)

2.

With System switch set to Cool and Fan switch set to 

Auto, move the temperature setting lever about 10°F 

(6°C) below room temperature. Cooling and fan should 

start immediately. 

3.

Move temperature setting lever about 10°F (6°C) above 

room temperature. Cooling and fan should shut off.

Fan

1.

With System switch set to Off and Fan switch set to On, 

the fan runs continuously. 

2.

Move Fan switch to Auto. In gas-fired or oil-fired sys-

tems, fan operation is controlled by thermostat in cool-

ing and by plenum fan control in heating. In heat pump 

and some central electric heat systems, fan operation is 

controlled by the thermostat in both heating and cooling.

Recalibration

These thermostats are calibrated at the factory and should not 

require recalibration. If thermostat seems out adjustment, first 

check for accurate levelling. To check calibration:

1.

Move temperature setting lever to low end of tempera-

ture scale. (

System switch must be placed to Off. 

Wait at least five minutes.)

2.

Remove thermostat cover. Move temperature setting 

lever until switch just makes contact. (The mercury in 

the switch will drop to the contact end of the tube.)

3.

Replace the thermostat cover and wait five minutes for 

the cover and the thermostat to lose the heat it has 

gained from your hands. (If the thermometer pointer and 

the temperature lever indicator read approximately the 

same, no recalibration is needed.)

4.

If recalibration appears necessary, use this procedure:

a. Place temperature setting lever at same setting as 

thermometer. 

b. Remove the thermostat cover.

c. Insert 104994A Calibration Wrench (ordered sepa-

rately) onto hex nut under coil. See Fig. 10. Holding 

setting lever so it does not move, turn wrench clock-

wise until mercury rolls to right end of tube. 

d. Remove wrench and replace thermostat cover.

e. Move temperature setting lever to low setting. Wait 

at least five minutes for temperature to stabilize.

f. Slowly move the temperature setting lever until it 

reads the same as the thermometer.

g. Remove cover. Holding temperature setting lever so 

it does not move, reinsert the wrench and carefully 

turn the wrench counterclockwise until the mercury 

just rolls to the left end of the tube,

 but no farther.

h. Recheck calibration by setting thermostat System 

switch for the desired operation.

i.

Replace the cover.

Fig. 10. Recalibrating thermostat.

CALIBRATION
WRENCH

COIL SHOWN WITHOUT
HEAT ANTICIPATOR

M2044A

Summary of Contents for T834C

Page 1: ...ed bimetal operates silent dust free spdt mercury switch T834C models have vented cover to provide better air flow for temperature sensing Adjustable heat anticipator and fixed cool anticipator on all models T834C models mount directly on wall or on a vertical outlet box T8034C models mount directly on wall or on a horizontal outlet box SUPER TRADELINE T8034C includes horizontal wallplate for cove...

Page 2: ...rd cooling systems mounts horizontally adjustable heat anticipator 0 18 to 1 0A Additional SUPERTRADELINE Features Fan can be controlled from thermostat or plenum switch Wallplate for covering marks from old thermostat T8034C only TRADELINE Models T843C Heating Cooling Thermostat for use in single stage heat pump electric furnace and standard heating cooling systems mounts vertically adjustable he...

Page 3: ... the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Hazard Can cause personal electrical shock or equipment da...

Page 4: ...he thermostat and mounting plate if used to the wall or outlet box with a screw through the top mounting hole Adjust thermostat so it is approxi mately level and start the second screw through the bottom mounting hole Do not tighten 8 Level the thermostat exactly using a level device Tighten the mounting screws IMPORTANT This thermostat is calibrated at the factory mounted at true level Any inaccu...

Page 5: ...le to the wall or outlet box with a screw through the left mounting hole Adjust thermostat so it is approximately level and start the second screw through the right mounting hole Do not tighten 8 Level the thermostat exactly using a level device Tighten the mounting screws IMPORTANT This thermostat is calibrated at the factory mounted at true level Any inaccuracy in leveling during the mounting ca...

Page 6: ...SYSTEM SWITCH HEAT OFF COOL FAN SWITCH AUTO ON H1 TEMP FALL C1 ANTICIPATOR FAN RELAY HEAT OFF COOL C1 H1 ANTICIPATOR G R Y L1 HOT L2 W HEAT RELAY 1 1 H1 TEMP FALL C1 L1 HOT L2 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED INSTALL JUMPER BETWEEN W AND Y TERMINALS WHEN HEAT RELAY IS NOT USED HEAT RELAY FAN RELAY FAN SWITCH ON AUTO COOL OFF HEAT COOL OFF HEAT SYSTE...

Page 7: ...urrent draw of the primary control Use this thermostat only on systems with current draws that fall within the range of the heat anticipa tor do not use this device on Powerpile millivolt systems 1 A current rating is usually stamped in the nameplate of the primary control Set the adjustable heat anticipator indicator to match the value given on the nameplate 2 If the current rating is not availab...

Page 8: ...iately 3 Move temperature setting lever about 10 F 6 C above room temperature Cooling and fan should shut off Fan 1 With System switch set to Off and Fan switch set to On the fan runs continuously 2 Move Fan switch to Auto In gas fired or oil fired sys tems fan operation is controlled by thermostat in cool ing and by plenum fan control in heating In heat pump and some central electric heat systems...

Reviews: