T834C, T8034C HEATING/COOLING THERMOSTATS

68-0075-2

4

T834C

The T834C can be mounted directly on a wall or vertical outlet 

box: 

— Use the 193121A Mounting Plate Assembly (ordered 

separately) to mount thermostat on horizontal outlet box or 

to cover marks from an old thermostat. 

— If mounting plate assembly is used, review instructions 

provided with assembly before wiring and mounting 

thermostat.

1.

In replacement applications, check existing thermostat 

wires for cracked or frayed insulation. Replace any 

wires in poor condition. 

NOTE: If wire is plastered into the wall, make a hole next to 

the wires and loosen them so they can be pushed 

back into the wall later.

2.

In new installations, run wiring, if necessary, to the   

thermostat location.

3.

Connect the wires to the terminals on back of thermo-

stat. See Fig. 5-9 for internal schematics and typical 

hookup diagrams.For systems requiring thermostat con-

trol of fan operation in heat (some electric heat applica-

tions), jumper terminals 1 and 2. See Fig. 3.

4.

Remove thermostat cover by pulling outward from 

indentation on right or left side of cover until it snaps 

free of thermostat base. Carefully remove and discard 

foam plastic shipping insert protecting switch and 

bimetal assembly during shipping.

5.

Set the adjustable heat anticipator indicator to match 

the current draw of the primary heating control (see 

Heat Anticipator Setting).

6.

Push excess wire back through the hole and plug any 

opening with insulation to prevent drafts that can affect 

thermostat performance.

7.

Loosely fasten the thermostat and mounting plate, if 

used, to the wall or outlet box with a screw through the 

top mounting hole. Adjust thermostat so it is approxi-

mately level and start the second screw through the   

bottom mounting hole. Do not tighten.

8.

Level the thermostat exactly using a level device. 

Tighten the mounting screws.

IMPORTANT

This thermostat is calibrated at the factory, mounted 

at true level. Any inaccuracy in leveling during the 

mounting causes control point deviation.

9.

Replace thermostat cover.

Fig. 3. Jumpering terminals 1 and 2 to control fan 

operation from thermostat during heating

 (electric heat application).

T8034C

The T834C can be mounted directly on a wall or horizontal 

outlet box: 

— Use the 200581 Horizontal Wallplate to cover mounting 

marks from an old thermostat or use 193121A Mounting 

Plate Assembly to mount thermostat on vertical outlet box 

or to cover marks from an old thermostat where a larger 

plate is needed. (The SUPERTRADELINE T8034C 

includes the 200581 Horizontal Wallplate. For other 

T8034C models, horizontal wallplate or mounting plate 

assembly must be ordered separately.)

— Using 200581 Horizontal Wallplate: Align thermostat 

and wallplate (see Fig. 4) and press firmly together 

until wallplate snaps in place; then wire and mount the 

thermostat.

— Using 193121A Mounting Plate Assembly: Review 

instructions provided with assembly before wiring and 

mounting thermostat.

Fig. 4. Mounting SUPERTRADELINE T8034C on wallplate.

JUMPER

M8675

R

1

W

Y

G

2

1

1

2

2

IN ELECTRIC HEAT AND HEAT PUMP APPLICATIONS, JUMPER
TERMINALS 1 AND 2 FOR AUTOMATIC FAN CONTROL IN HEATING
 AND COOLING.

IN GAS-AND OIL-FIRED APPLICATIONS, JUMPER TERMINALS 1
AND Y FOR AUTOMATIC FAN CONTROL IN COOLING.

M20951

Heat Off Cool

90

80

70

60

On

Fan Au

to

Summary of Contents for T834C

Page 1: ...ed bimetal operates silent dust free spdt mercury switch T834C models have vented cover to provide better air flow for temperature sensing Adjustable heat anticipator and fixed cool anticipator on all models T834C models mount directly on wall or on a vertical outlet box T8034C models mount directly on wall or on a horizontal outlet box SUPER TRADELINE T8034C includes horizontal wallplate for cove...

Page 2: ...rd cooling systems mounts horizontally adjustable heat anticipator 0 18 to 1 0A Additional SUPERTRADELINE Features Fan can be controlled from thermostat or plenum switch Wallplate for covering marks from old thermostat T8034C only TRADELINE Models T843C Heating Cooling Thermostat for use in single stage heat pump electric furnace and standard heating cooling systems mounts vertically adjustable he...

Page 3: ... the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Hazard Can cause personal electrical shock or equipment da...

Page 4: ...he thermostat and mounting plate if used to the wall or outlet box with a screw through the top mounting hole Adjust thermostat so it is approxi mately level and start the second screw through the bottom mounting hole Do not tighten 8 Level the thermostat exactly using a level device Tighten the mounting screws IMPORTANT This thermostat is calibrated at the factory mounted at true level Any inaccu...

Page 5: ...le to the wall or outlet box with a screw through the left mounting hole Adjust thermostat so it is approximately level and start the second screw through the right mounting hole Do not tighten 8 Level the thermostat exactly using a level device Tighten the mounting screws IMPORTANT This thermostat is calibrated at the factory mounted at true level Any inaccuracy in leveling during the mounting ca...

Page 6: ...SYSTEM SWITCH HEAT OFF COOL FAN SWITCH AUTO ON H1 TEMP FALL C1 ANTICIPATOR FAN RELAY HEAT OFF COOL C1 H1 ANTICIPATOR G R Y L1 HOT L2 W HEAT RELAY 1 1 H1 TEMP FALL C1 L1 HOT L2 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED INSTALL JUMPER BETWEEN W AND Y TERMINALS WHEN HEAT RELAY IS NOT USED HEAT RELAY FAN RELAY FAN SWITCH ON AUTO COOL OFF HEAT COOL OFF HEAT SYSTE...

Page 7: ...urrent draw of the primary control Use this thermostat only on systems with current draws that fall within the range of the heat anticipa tor do not use this device on Powerpile millivolt systems 1 A current rating is usually stamped in the nameplate of the primary control Set the adjustable heat anticipator indicator to match the value given on the nameplate 2 If the current rating is not availab...

Page 8: ...iately 3 Move temperature setting lever about 10 F 6 C above room temperature Cooling and fan should shut off Fan 1 With System switch set to Off and Fan switch set to On the fan runs continuously 2 Move Fan switch to Auto In gas fired or oil fired sys tems fan operation is controlled by thermostat in cool ing and by plenum fan control in heating In heat pump and some central electric heat systems...

Reviews: