background image

68-0148—1

2

T8131A,B,C; T8132A,B,C

SPECIFICATIONS • ORDERING INFORMATION

Ordering Information

When purchasing replacement and modernization products form your TRADELINE

®

 wholesaler or your distributor, refer to the

TRADELINE Catalog or price sheets for complete ordering information, or specify—

1. Order Number.
2. Accessories, if desired.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1. Your local Honeywell Home and Building Control Sales Office (check white pages of phone directory).
2. Home and Building Control Customer Satisfaction

Honeywell Inc., 1985 Douglas Drive North
Minneapolis, Minnesota 554212-4386 (612) 951-1000.

In Canada—Honeywell Controls Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9 . International
Sales and Service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan,
Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

Specifications

IMPORTANT: The specifications given in this publica-

tion do not include normal manufacturing toler-
ances; therefore, an individual unit may not exactly
match the listed specifications. Also, this product is
tested and calibrated under closely controlled condi-
tions, and some minor differences in performance
can be expected if those conditions are changed.

MODELS:

T8131A/T8132A Programmable Thermostats: Provide

eight program keys; with keyboard door.

T8131B/T8132B Programmable Thermostats: Provide

eight program keys; without keyboard door.

T8131C/T8132C Programmable Thermostats: Deluxe

models, provide twelve program keys including us-
age key; with keyboard door.

ELECTRICAL RATING: T8131: 24 Vac.

T8132: Battery operated (2 AA alkaline batteries).

SYSTEM AND FAN RATINGS:

1.2A run; 7.5A inrush.
Total cooling and fan load not to exceed 1.2A.

DIMENSIONS: See Fig. 1.

Fig. 1—Dimensions in in. [mm] of T8131 and T8132 models.

M9349

1 [25]

1     

 [32]

1
4

4

[102]

3
4

[19]

7
8

6    [175]

MOUNTING MEANS: Position mounting plate directly

on wall using two mounting screws and wall anchors
provided (See Fig. 2).

LIGHT EMITTING DIODE (LED): One LED on T8131

models only; lights to indicate proper operation when
both sides of the 24 Vac system transformer are prop-
erly connected. See Fig. 2 for position of LED.

SET POINT RANGE: 45° F to 88° F [7° C to 31° C].

OPERATING AMBIENT TEMPERATURE RANGE:

40° F to 110° F [4° C to 43° C].

SHIPPING TEMPERATURE RANGE: -20° F to 120° F

[-29° C to -49° C].

OPERATING RELATIVE HUMIDITY: 5 percent RH to

90 percent RH; noncondensing.

TIME INDICATION: 12 hour with AM, PM indication.

Summary of Contents for T812A1002 - Mechanical Thermostat

Page 1: ...re control Four daily energy saving programs Available in taupe and Premier White Compatible with most 24 Vac standing pilot gas electronic ignition oil or central electric systems T8131 Models Only Powered directly from 24 Vac system transformer Greenlightemittingdiode LED lightswhenprop erly connected Two AA alkaline batteries for backup power recommended T8132 Models Only Requires two AA alkali...

Page 2: ...he listed specifications Also this product is tested and calibrated under closely controlled condi tions and some minor differences in performance can be expected if those conditions are changed MODELS T8131A T8132A Programmable Thermostats Provide eight program keys with keyboard door T8131B T8132B Programmable Thermostats Provide eight program keys without keyboard door T8131C T8132C Programmabl...

Page 3: ...seboard Electric 120 240 Line Volt No Heat pumps Multistage Equipment No Not compatible with any 120 240 volt circuit Not designed for steam or gravity systems a Compatiblewith2 wireHoneywellzonevalves Isolating relay required for 3 wire thermostats for zone valves Not compatible with 2 wire White Rodgers no 1361 Valves WARNING ELECTROCUTION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH ...

Page 4: ...ired number of wires to the thermostat location check the appropriate wiring diagram Refer to Figs 8 through 11 for typical wiring diagrams In 5 wire installations only be sure to remove the fac tory installed jumper connecting terminals R and Rc Fig 4 Proper wiring technique Fig 5 3 wire heat only application Fig 7 5 wire heat cool application Fig 6 4 wire cool only application C R W Y G B A 3 WI...

Page 5: ...NNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 JUMPER HEATING RELAY OR VALVE COIL M1710B COOLING CONTACTOR COIL FAN RELAY Fig 9 3 wire cool only application jumper intact Fig 11 5 wire heat cool application jumper removed R Rc W Y G B D A C 3 WIRE COOL ONLY JUMPER INTACT L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 JUMPER M848A COOLING CONTACTOR COIL FAN...

Page 6: ...e indicator starts flashing If the batteries are not replaced sometime during the flashing bAt Lo indicator the indi cator will eventually stop flashing When the batteries are almost completely dead bAt Lo will stay on without flashing to indicate the thermostat and heating cooling system have stopped working The thermostat will not function after the batteries are completelydead andthe bAtLo indi...

Page 7: ...dge of the case to latch INSTALL TWO AA ALKALINE BATTERIES AS SHOWN M1713 Fig 15 Mounting the thermostat on the subbase M9366 B PRESS LOWER EDGE OF CASE TO LATCH FOR T8131A C AND T8132A C SWING OPEN COVER CHECK OPERATION A ENGAGE TABS AT TOP OF THERMOSTAT AND MOUNTING PLATE NOTE IMPORTANT Although the thermostat has a low battery indicator replace the batteries once a year to pre vent the thermost...

Page 8: ...o permanently change a program repeat steps in Heat ing Program or Cooling Program section as applicable To Return to the normal program or the start program press Run Program T8131B AND T8132B MODELS Set Current Time Day To set time press and release Clock Day once then press Time or until current time displays To set day press and release Clock Day again and then press Time or until current day ...

Page 9: ...ck Guide for Operating or Making Changes NOTE System switch must be set to Heat or Cool to perform the following To temporarily change the temperature for the current period only press Warmer or Cooler The temperature will cancel itself at the next scheduled change To cancel sooner press Run Program To hold a temperature indefinitely press Hold Temp then Warmer or Cooler To cancel press Run Progra...

Page 10: ...ture The heating equipment should shut off Cooling A C B For T8131 models only before continuing check that the green LED is lit indicating the thermostat is powered properly To avoid possible compressor damage do not operate the cooling system when outside temperature is below 50 F 10 C See compressor manufacturer instructions for further information NOTE When cooling setting is changed thermosta...

Page 11: ...l not go T8131 T8132 lower than 45 F 7 C or higher The temperature setting limit has been reached The setting range is 45 F than 88 F 31 C during to 88 F 7 C to 31 C programming Heating will not come on T8131 Check that green LED is lit T8132 If display is blank or says bAt Lo install fresh batteries T8131 T8132 Check that switch on thermostat is set to HEAT Check the system fuse or circuit breake...

Page 12: ...ent setting does Check that the wiring hole in the wall behind the wallplate has been plug not match the display temperature ged with insulation to prevent drafts that might adversely affect thermostat operation Be aware that it is normal for the current setting and display temperature to differ occasionally T8131A B C T8132A B C TROUBLESHOOTING CROSS REFERENCE Cross Reference T8131 T8132 CROSS RE...

Reviews: