T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
25
62-0249—13
Fig. 61. Setup - Outputs - Mod Out - Reset.
3.3.3.1.6. RESET
This selection enables the controller’s Reset function, and
allows each output to be individually programmed for
Reset or No Reset.
IMPORTANT
To use the Reset function of the controller, the
first output (MOD1 or Relay 1 depending on the
model) must be set for Reset here.
The RESET choice is offered for all outputs in setup
mode, and you can set any or all of them for Reset=YES
or Reset=NO. The default is Reset=NO.
For the remaining outputs, if Reset=YES, then these
outputs use the reset curve programmed for the first
output.
1.
From the Mod menu, use the
and
buttons to
highlight RESET.
2.
Use the
and
buttons to highlight the desired
value.
Default: NO
3.
Press the
button to accept the selection and
return to the Mod menu.
Fig. 62. Setup - Outputs - Mod 1/2- Hide.
3.3.3.1.7. Hide
The Hide option is used to prevent the MOD 1 and MOD 2
outputs from displaying on the Home screen.
1.
From the Mod menu, use the
and
buttons to
highlight HIDE.
2.
Use the
and
buttons to highlight YES or NO.
Default: YES
3.
Press the
button to accept the selection and
return to the MOD menu.
NOTE: The MOD1 and MOD2 outputs are still active
even when hidden from the Home screen.
Fig. 63. Setup - Outputs - Number of Relays.
3.3.4. NBR OF RELAYS
1.
From the Outputs menu, use the
and
buttons
to highlight # RELAYS.
2.
Press the
button to display the number of relays.
3.
Use the
and
buttons to display the number
from 1 to 4 depending on the model. (See note
below).
4.
Press the
button to accept the value and display
the Outputs menu.
NOTES:
1.
The T775R models have the following outputs
available:
(a)T775R2001 up to 4 relay outputs
(b)T775R2019 up to 4 relay outputs
(c)T775R2027 up to 2 relay outputs
(d)T775R2035 up to 2 relay outputs
(e)T775R2043 no relay outputs
2.
The number of relays entered here display on
the home screen.
SETUP
OUTPUTS
RELAY 1
MOD 1
SETUP
OUTPUTS
MOD 1
RESET
USE
RESET
FOR
MOD1
YES-BOILER
YES-OTHER
NO
M24340
SETUP
OUTPUTS
MOD
1
HIDE
SETUP
OUTPUTS
MOD 1
HIDE
HIDE MOD 1 ON
HOME SCREEN
YES
NO
M28656
SETUP
OUTPUTS
#
RELAYS
ENTER
NUMBER OF
RELAYS
SETUP
OUTPUTS
# RELAYS
4
M24342