background image

T775J ELECTRONIC REMOTE TEMPERATURE CONTROLLER

63-2248—4

3

Mounting:
Mounts on any suitable horizontal or vertical surface. (See
Fig. 5 for mounting hole locations.)

Dimensions:
See Fig. 1.

Display Resolution:
Sensed temperature and other operating parameters are
displayed via a liquid crystal display (LCD) with a resolution of
1

°

F or 1

°

C.

Accessories:

C7100C1003 Duct Mount Averaging Sensor*.
T7047C1090 Wall Mount Sensor Case.
107324A Bulb Holder, duct insertion.
121371A Copper Immersion Well.
121371E Stainless Steel Immersion Well.
107408 Heat Conduction Compound, 4 ounce.
C7043A1098 Case and Immersion Well.
203401B Waterproof Sensor.
203531A Panel Mounting Kit.
A775A1003 Sensor Simulator.
*Use of C7100C1003 decreases accuracy of T775 to 

±

2

°

F

(

±

1

°

C).

Fig. 1. Approximate T775J dimensions in in. (mm).

INSTALLATION

When Installing this Product...

Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.

Check the ratings given in these instructions and on the
product to make sure the product is suitable for your
application.

Installer must be a trained, experienced service
technician.

After installation is complete, check out the product
operation as provided in these instructions.

SELECT

SET

ENTER

M344C

3-13/16 (97)

4-3/4 (121)

8-1/2
(216)

5-7/32
(134)

1-1/4
(32)

1-1/4
(32)

2-3/8 (60)

7/8 (22) DIAMETER

CAUTION

Disconnect power before installation to prevent
electrical shock or equipment damage.

Location and Mounting

Mount the controller in any convenient interior location using
the two mounting holes provided. Mounting screws are not
included. Use controller dimensions in Fig. 1  as a guide.

Sensor Location

The 193987GA Sensor can be used up to 1000 ft (304m)
from the T775 using standard AWG 18/2 unshielded wire. If
longer than 25 feet in an electrically noisy environment, use
shielded cable. Locate the sensor on pipes, in immersion
wells, in wall-mounted cases or on a bulb holder.

Multiple sensors can be parallel-series wired to sense
average temperature in large spaces. In order to maintain
control accuracy, be sure the number of sensors parallel-
series wired is of the n2 power (i.e., 1, 4, 9, 16, etc). See
Fig. 2.

Fig. 2. Parallel-series wiring of sensors.

Sensor Mounting

Mount the sensor on a wall or panel for sensing space
temperature (Fig. 3); strap it to a pipe, or insert it into a well
(Fig. 4) for hot/cold water sensing; or tape it  to a standard
cap or bulb holder for duct air sensing. To prevent moisture or
condensation entering the sensor through the leadwire holes,
mount the sensor with leadwires exiting the bottom of the
sensor.

NOTE:

Use heat conductive compound in immersion wells.
See Accessories.

TO T775 CONNECTIONS 1 AND 2 (SENSOR A)
OR 7 AND 8 (SENSOR B).

SENSORS

M7431

Summary of Contents for T775J

Page 1: ...ng and operation Accuracy is within 1 F C at nominal input voltage nominal sensor ambient temperature 77 F 25 C operating ambient Accuracy can vary as parameters deviate from nominal Stages independently programmed for heating or cooling 24 120 240 Vac voltage inputs Spdt relay outputs IMPORTANT The T775 is an operating control not a limit or safety control When used in applications requiring safe...

Page 2: ...40 F 34 C to 60 C Sensor 45 F to 225 F 43 C to 107 C Throttling Range for Modulating Output Adjustable 2 to 30 F or C Differential Range for Staged Output Adjustable 1 to 30 F Reset Ratio Adjustable between 1 to 30 and 30 to 1 Operating Humidity 5 to 95 percent relative humidity noncondensing Sensor Positive coefficient platinum type 4 8 ohms F 1000 feet maximum distance between sensor and solid s...

Page 3: ...3 16 97 4 3 4 121 8 1 2 216 5 7 32 134 1 1 4 32 1 1 4 32 2 3 8 60 7 8 22 DIAMETER CAUTION Disconnect power before installation to prevent electrical shock or equipment damage Location and Mounting Mount the controller in any convenient interior location using the two mounting holes provided Mounting screws are not included Use controller dimensions in Fig 1 as a guide Sensor Location The 193987GA ...

Page 4: ...rd conduit knockouts A C located around the enclosure perimeter NOTE Hole A should only be used for remote sensor wiring low voltage wiring and access to modulating output When wiring the input power only one source of power can be applied to the T775J e g 24 or 120 or 240 Vac Knockouts B and C can be used to gain access to 120 or 240 Vac input terminals and the load relay output terminals The T77...

Page 5: ...r to the T775 when an electrically noisy environment exists See Fig 6 SELECT SET ENTER NO COM NC OUTPUT 1 OUTPUT 2 NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 3 1 2 3 4 5 6 7 8 SA TOD 24V SB C F T775 GROUND SHIELD TO T775 CASE OR TO GROUNDING SCREW SHIELDED CABLE SHIELDED CABLE GROUNDING SCREW NOTE DO NOT GROUND SHIELDED CABLE AT SENSOR END NOTE TO MINIMIZE NOISE PICKUP MAKE CONNECTION FROM SHIELDED ...

Page 6: ...NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 3 1 2 3 4 5 6 7 8 SA TOD 24V SB C F M8111 SENSOR A 24 VAC SENSOR B LOAD 1 LOAD 2 SELECT SET ENTER NO COM NC OUTPUT 1 OUTPUT 2 NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 3 1 2 3 4 5 6 7 8 SA TOD 24V SB C F M8112 SENSOR A 120 VAC SENSOR B LOAD 1 LOAD 2 BLK WHT SELECT SET ENTER NO COM NC OUTPUT 1 OUTPUT 2 NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 3 1 2 3 4 5 6 7 ...

Page 7: ...M SLIDEWIRE DEVICES PROPER OUTPUT LEVELS CAN BE CHECKED BY MEASURING THE OPEN CIRCUIT VOLTAGE BETWEEN TERMINALS 1 W AND 2 R MINIMUM DRIVE CLOSED 0 17 VDC MAXIMUM DRIVE OPEN 1 7 VDC ELECTRONIC SERIES 90 MODUTROL MOTOR T775J NOTE B R W Fig 11 Reset control with 24 Vac input Series 90 and 24 Vac loads SELECT SET ENTER OUTPUT 2 NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 3 1 2 3 4 5 6 7 8 SA TOD 24V SB C...

Page 8: ...WITCHES FOR SENSOR TO LOAD SELECTION M954 OR M955 MODUTROL MOTOR M4717 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 USE 1300 OHM RESISTOR FOR 2 MOTORS 910 OHMS RESISTOR FOR 3 MOTORS 4047EAU RESISTOR KIT SHIPPED WITH M954 M955 MOTORS INCLUDES 1300 OHM AND 910 OHM RESISTORS 2 B R W SELECT SET ENTER NO COM NC OUTPUT 1 OUTPUT 2 NO COMNC 120V COM 240V 1 2 3 4 SA SB 1 2 ...

Page 9: ...user to program for both heating and cooling loads to be energized at the same time If this situation results cooling loads will be energized and heating loads will be prevented from also energizing The number 1 2 of these nonenergized loads will flash along with the word HEAT to indicate a call for both heating and cooling loads controlled by one sensor has occurred and to alert the user to repro...

Page 10: ...memory 쐄 Press Select to display the current stage throttling range or switching differential 쐂 Press Set up arrow to increase or Set down arrow to decrease the display to the desired throttling range or switching differential 쐆 Press Enter to enter the displayed value into memory 쐊 Repeat steps 2 through 7 to program each additional stage IMPORTANT After initial programming altering the setpoint ...

Page 11: ...sed for calibrating the device in column B following the example in column A Calibration Setpoint for Cooling Mode Fig 13 Setpoint for calibrating the lower voltage level closed position A B Sensed Temperature 78 Add 3 F or C to above 3 Calibration Setpoint 81 Calibration Setpoint for Heating Mode A B Sensed Temperature 78 Subtract 3 F or C from above 3 Calibration Setpoint 75 Calibrate the Lower ...

Page 12: ...NSOR INPUT TOD AND 24 VAC TERMINALS 1 2 34 SA SB 1 2 3 1 2 3 4 5 6 7 8 SA TOD 24V SB VOLTMETER CONNECT THE MODULATING VOLTAGE OUTPUT TO A VOLTMETER USING A SCREWDRIVER ADJUST THE LOWER LIMIT OF THE VOLTAGE TO THE DESIRED LEVEL ACCORDING TO THE STEPS OUTLINED IN CLAIBRATION PROCEDURE FOR 0 TO18 VDC OUTPUT NO COM NC OUTPUT 1 OUTPUT 2 NOCOM NC 120V COM 240V 0 18 STEP 3 1 2 3 1 2 3 4 3 14 17 8 OPEN GE...

Page 13: ...modulating or relay outputs for reset control Each stage of the T775J has its own independent setpoint that can be configured to operate in the cooling or heating mode The mode of operation for each stage is user determined by the programming keys For reset control with two outputs one of which is modulating the modulating output will be designated as stage 1 on the LCD display Although the modula...

Page 14: ... 1 8 of the throttling range There are three modulation options available for the T775J see Fig 20 for modulating output connecting terminals Fig 18 Reset switch configuration Fig 19 Summary of action direction switches PWB SWITCH SWITCH PWB OPEN CLOSED SIDEVIEW OPEN CLOSED RESET DIRECTION SWITCH RESET ACTION SWITCH RESET DIRECTION SWITCH WILL RESET THE COUNTROL POINT UP WHEN OPEN OR DOWN WHEN CLO...

Page 15: ...OOR TEMPERATURE DROPS BELOW SETPOINT B RIGHT RESETS AS IT RISES ABOVE IT C SWITCHES 3 AND 4 ARE NOT USED RESETS CONTROL SETPOINT A DOWN WHEN SENSOR B OUTSIDE TEMPERATURE IS BELOW SETPOINT RESETS CONTROL SETPOINT A DOWN WHEN SENSOR B OUTSIDE TEMPERATURE IS ABOVE SETPOINT RESETS CONTROL SETPOINT A UP WHEN SENSOR B OUTSIDE TEMPERATURE IS BELOW SETPOINT RESETS CONTROL SETPOINT A UP WHEN SENSOR B OUTSI...

Page 16: ...e F mode Remove the jumper plug for the C mode Remove and reapply power if the jumper is removed with the device powered DIP Switch Selections DIP switches see Fig 18 are provided for assignment of the reset configurations A second set of DIP switches provides voltage range selection for 0 to 18 Vdc modulating devices The span corresponding to each switch is given on the printed wiring board below...

Page 17: ... SF Sensor Failure The display flashing SF indicates an out of range sensor Make sure the sensors are properly connected For the T775J stage 2 load will be de energized when this error message is flashing for Sensor B When this message is flashing for Sensor A only stage 1 will not be de energized EF EEPROM Failure The values read back from the EEPROM are not the same as written into the EEPROM Th...

Page 18: ...a reset condition exists d If no reset condition exists On Off Control Values have not been changed e Go to step 11 f If a reset condition exists calculate the amount of reset using Formula 2 g Divide Reset Ratio B value by Reset Ratio A value h Multiply the result in step g by Temp Diff step a i If Reset Direction Switch is set to increase disregard any negative signs and add the amount of reset ...

Page 19: ... 80 Off 76 On 80 78 Off 74 On 120 Off 116 On 80 118 Off 80 Setpoint B ____________ Reset Direction __________ Setpoint B 30 Reset Direction Increase Sensor B _____________ Reset Action ____________ Sensor B 10 Reset Action Below Reset Ratio A _________ Reset Ratio B ___________ Reset Ratio A 1 Reset Ratio B 2 FORMULA 1 FORMULA 1 EXAMPLE Sensor B Sensor B 10 F Setpoint B Setpoint B 30 F Temp Diff _...

Page 20: ...rld Home and Building Control Honeywell Limited Honeywell Limitée 740 Ellesmere Road Scarborough Ontario M1P 2V9 63 2248 4 Rev 9 95 Printed in U S A www honeywell com building components QUALITY IS KEY Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 ...

Reviews: