T6570, T8570 SERIES DIGITAL FAN-COIL THERMOSTATS 

Table 5. Thermostat Parameter Options 

Parameter 

ID 

Description 

°C Scale 

°F Scale 

Default 

Values 

Default 

Values 

T

emperature 

S

cale 

tS 

Allows selection of either °C or °F scale  Yes 

– 

No 

– 

D

ead 

B

and 

db 

Setting deadband (Zero Energy Band)  2 

2, 3, 4 

3, 4, 5 

Heat or Cool 

Op

erating Mode 

OP 

Setting operating mode on single relay, 

non-changeover models, to either Heat 

or Cool 

0: cool 

1: heat 

0: cool 

1: heat 

U

noccupied 

C

ooling 

Setpoint 

uC 

Program unoccupied cooling setpoint 

for energy savings. 

25 

25 to 30 

77 

77 to 90 

U

noccupied 

H

eating 

Setpoint 

uH 

Program unoccupied heating setpoint 

for energy savings 

18 

10 to 18 

65 

50 to 65 

Minimum 

C

ooling 

O

ff Time 

CO 

Setting cooling off-time for short cycle 

prevention. 

0, 3, 4, 5 

0, 3, 4, 5 

Minimum 

H

eating 

O

ff Time 

HO 

Setting heating off-time for short cycle 

prevention. 

0, 3, 4, 5 

0, 3, 4, 5 

Minimum 

C

ooling 

Setpoint (

L

ow Limit) 

CL 

Sets the minimum allowable cooling 

setpoint. 

10 

10 to 30 

50 

50 to 90 

Maximum 

H

eating 

Setpoint (High 

L

imit) 

HL 

Sets the maximum allowable heating 

setpoint. 

30 

10 to 30 

90 

50 to 90 

E

nergy 

S

avings 

Configuration 

ES 

Activate energy savings mode by a 

choice of either contact closure or 

contact opening. 

1: normally open 

0: normally closed 

1: normally open 

0: normally closed 

Display of 

R

oom 

T

emperature 

rt 

Allows installer to restrict temperature 

display to set point only.  With this 

parameter, the unit will only display the 

set point temperature.  Useful where 

setpoint limits (HL and CL) will affect 

control performance and Room 

Temperature display will disagree with 

user setpoint. 

1: room temp. 

0: setpoint only 

1: room temp. 

0: setpoint only 

WIRING

 

Table 6. Leadwire Color Code (if fitted) 

Terminal 

Color 

Use 

Black (BK) 

L1 (Hot) 

White (WH) 

L2 (N) 

Orange (OR) 

Heat 

Yellow (YL) 

Cool 

Gray (GY) 

Damper 

Violet (VI) 

Fan Common 

Red (RD) 

Fan Low 

Blue (BU) 

Fan Medium 

Brown (BN) 

Fan High 

10 

– 

Energy Mgt. 

System

11 

– 

Fig. 6. Wiring 2-pipe cool-only thermostat with fan On/Auto

switch. 

95C-10897–6 

Summary of Contents for T6570 Series

Page 1: ...t temperature with user activated temperature display Digital display shows mode icons when cooling or heating relays operate or when energy savings mode is active Push button setpoint adjustment Switches allow manual control of system operation and fan speed Energy savings mode external energy savings input from time switch occupancy sensors or hotel cardkey overrides comfort setpoint with setbac...

Page 2: ...ectrical box or on 4 x 4 Operating Range 5 C to 45 C 41 F to 113 F box with optional 272878 adapter plate Shipping and Storage Range 20 C to 55 C 4 F to 131 F Wiring 11 terminals screw in terminals capable of accepting Humidity Range 5 to 95 RH non condensing at 26 C up to 2 x 18 AWG 1 x 14 AWG or 1 5 mm2 wires Some 79 F terminals pre fitted with color coded flyleads Thermostat Output 1spdt or 2 s...

Page 3: ...Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service techni cian 4 After installation is complete check out product opera tion as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power s...

Page 4: ...ostat straight away from the wallplate 1 2 3 M15396 Fig 3 Removing the thermostat Thoroughly check wiring to the wallplate before finally mounting the thermostat on the wall OPERATION Control PROPORTIONAL INTEGRAL P I CONTROL Like a mechanical thermostat the T6570 T8570 Series have On Off control output However this output is regulated by a P I algorithm enabling the thermostat to control closer t...

Page 5: ...On the thermostat undergoes a startup and self checking sequence First all LCD display segments are illuminated to check the display Next a number appears to indicate the software version The final check is a check of the sensor On completion of the startup sequence after approximately 2 seconds the thermostat will resume normal control in either Comfort or Economy mode On initial power on the tem...

Page 6: ...de The thermostat allows many of its operating parameters to be adjusted via an Installer Setup Mode Each operating parameter has a two letter identifier code which is shown on the display during the Installer Setup Mode programming sequence A description of these is shown in Table 5 PROGRAMMING PARAMETERS The installer setup mode is accessed by reducing the setpoint to 10 C 50 F waiting 3 seconds...

Page 7: ...nt Low Limit CL Sets the minimum allowable cooling setpoint 10 10 to 30 50 50 to 90 Maximum Heating Setpoint High Limit HL Sets the maximum allowable heating setpoint 30 10 to 30 90 50 to 90 Energy Savings Configuration ES Activate energy savings mode by a choice of either contact closure or contact opening 1 1 normally open 0 normally closed 1 1 normally open 0 normally closed Display of Room Tem...

Page 8: ...hangeover switch continuous fan switch Fig 11 Wiring 4 pipe auto heat cool changeover Fig 8 Wiring 2 pipe seasonal heat cool changeover with external aquastat fan On Auto switch Fig 12 Wiring 4 pipe auto heat cool changeover with fan On Auto switch Fig 9 Wiring 2 pipe heat cool with manual heat cool changeover switch continuous fan or cycled fan 95C 10897 6 8 ...

Page 9: ...provides 24 Vac power three interlocked fan relays and wiring center terminations for valve relay and contactor loads The W6380 schematic can be found in Fig 14 Fig 16 Wiring 2 pipe 24V heat thermostat with fan On Auto switch Fig 17 Wiring 2 pipe heat cool with manual heat cool changeover switch continuous or cycled fan Fig 14 W6380 wiring diagram Fig 15 Wiring 2 pipe 24V cool only thermostat with...

Page 10: ... use this for control To extend the sensor cable up to a maximum of 70 feet 20m use only shielded cable For example Beldfoil 18 AWG cable is a suitable cable The sensor connections are polarity sensitive so be sure to connect the shielded wire to the sensor blue wire as shown in Fig 21 below Fig 21 Wiring optional remote sensor for the T8575D model CAUTION Equipment Damage Hazard Operation at low ...

Page 11: ...T6570 T8570 SERIES DIGITAL FAN COIL THERMOSTATS 95C 10897 6 11 ...

Page 12: ...Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 95C 10897 6 M A Rev 09 05 ...

Reviews: