background image

Fig. 5 - Removing slotted knockouts.

Fig. 7 - Closing the strain relief bushing.

Fig. 6 - Insert strain relief bushing.

   

3. Refer to the following section for type of wiring

connections (standard wire push-in terminals or female
receptacle).

WIRING CONNECTIONS

   When connecting cable or conduit to this controller,
use care to avoid strain on the control case.
Connections can be made to standard wire push-in
terminals or female receptacles for 1/4 in. (6.4 mm)
male flag connectors on both the fan and limit
switches (Fig. 8).

FOR STANDARD WIRE PUSH-IN TERMINALS
   Connect wires to the terminals as follows:
   1. Use Nos. 14,16, or 18 solid wire or Nos. 14 or 16
stranded wire, depending on electrical requirement.
   2. Strip insulation from wires the distance shown by
the strip gauge on the controller.
   3. Solid wire may be inserted directly into the
terminal holes. If stranded wire is used, insert a small
screwdriver into the slot next to the terminal. Push
screwdriver in and hold while inserting wire into
terminal (Fig. 8). Remove screwdriver. If stranded wire
is solder-dipped, it can be pushed directly into
terminal holes.

FOR FEMALE RECEPTACLES -
   It is recommended that the female receptacles be
used for wiring accessory equipment; i.e.,
electronic air cleaner, humidifier, etc.
   Connect wires to the receptacles as follows:
   1. Use Nos. 14 to 18 size wire, depending on
electrical requirement.
   2. Attach 1/4 in. (6.4 mm) male flag connector to
each wire. Two male connectors with leadwires are
supplied.
   3. Push male flag connector directly into the
female receptacle. Make sure that the flag is forced
to the bottom of cavity and wire is in the channel
(Fig. 8).

IMPORTANT

Make certain all wires are clear of rotating scaleplate.

Fig. 8 - Location of wiring connections.

69-0117-3

3

2

69-0117-3

Fig. 3 - Rigid bracket mounting requires a hole 13/
16 in. (20.6 mm) diameter for element insertion.

Fig. 4 - Using SUPER TRADELINE adapter.

WIRING

   Disconnect power supply before beginning
installation to prevent electrical shock or equipment
damage.
   All wiring must comply with local electrical codes and
ordinances or in the absence of local codes with the
National Electrical Code ANSI C1-1981-NFPA 70.
Follow burner or furnace manufacturer’s instructions if
available; otherwise, see Fig. 10 and proceed as
follows.

IMPORTANT

   The slotted knockouts on the bottom of the case and
the strain relief bushing are provided to simplify the
installation procedure and to protect the wires.
   1. To remove the slotted knockout(s), use a
needlenose pliers as shown in Fig. 5 and pull straight
down.
   2. If cable is used, we recommend using a strain relief
bushing in the knockout (Fig. 6). Pass the wires through
bushing before connecting.

SWIVEL MOUNTING

   L4064 may also be swivel-mounted. The swivel
bracket requires a 1-9/16 in. (39.7 mm) hole in the
plenum (Fig. 2).
   1. Use bracket as a template to mark the location
of mounting holes in plenum. Drill or punch holes
for mounting screws.
   2. Fasten the brackets in place with furnished
screws. Start the screws but do not tighten.
   3. Insert element tube through bracket, straighten
controller, and fasten. Tighten the mounting screws
securely. It may be necessary to rotate the bracket
to tighten all screws securely.

Fig. 2 - Swivel mounting requires a 1-9/16 in. (39.7
mm) diameter mounting hole for element insertion.

The brass jumper is the breakaway type. It must be
removed when the limit is used in the low voltage
circuit. To remove jumper, break with a needlenose
pliers and remove completely, Once removed, it is
not replaceable. See Fig. 8 for location.

   L4064 may be mounted using a rigid bracket. The
rigid bracket requires a hole 13/16 in. (20.6 mm)
diameter for element insertion (Fig. 3).
   1. Use bracket as a template to mark the location of
mounting holes in plenum. Drill or punch holes for
mounting screws.
   2. Fasten bracket in place with furnished screws.
Tighten the screws securely.
   3. Insert element tube through bracket, straighten
controller and fasten by tightening setscrew. Be sure
screw strikes tube frame and does not strike sensing
element.
   4. For replacement installations with existing 1 in.
(25.4 mm) diameter hole. SUPER TRADELINE
models are supplied with split steel bushings and wire
snap ring. Follow the instructions below for using the
steel bushing adapter.

STEEL BUSHING ADAPTER

   1. Insert one-half of the split steel bushing (Fig. 4),
through the wire ring. It may be necessary to spread
the ring slightly.
   2. Insert the other half of the steel bushing into the
ring making sure tabs and ears are at the same ends.
   3. Place bushing assembly on element, ear end
first.
   4. Holding bushing at seams, push firmly to the
control end of element.

   When mounting control on bracket, setscrew must
strike tube frame 

not

 sensing element to prevent

bypassing the safety limit function.

   5. Insert element tube with adapter through bracket,
straighten controller and fasten. Tighten setscrew. Be sure
screw strikes bushing not coiled bimetal sensing element.

RIGID BRACKET MOUNTING

!

WARNING

50

100

150

200

250

ON/OFF

FAN LIMIT

DO NOT ROTATE HOLD 

DIAL WHEN SETTING 

CAUTION

FAN

LIMIT

PUSH MAN 

PULL AUTO

REMOVABLE 

BRASS 

JUMPER

STANDARD 

WIRE PUSH IN 

CONNECTORS 

(4)

FEMALE 

RECEPTACLE FOR 

CONNECTION OF 

1/4 IN. (6.4 MM) 

MALE SPADE 

TERMINAL (4)

WIRING GUARD

TO RELEASE 

STANDARD WIRE - 

PUSH SCREW 

DRIVER IN AND 

PULL WIRE OUT

STANDARD 

WIRE TO 

CONTROLLED 

EQUIPMENT

LEADWIRE WITH 1/4 

IN. (6.4 MM) MALE 
SPADE TERMINAL 

(FORCE SPADE TO 

BOTTOM OF CAVITY)

11,204B

REQUIRE 1-9/16 

IN. (39.7 MM) 

DIAMETER HOLE 

IN PLENUM

FURNACE  

PLENUM

32612A SWIVEL 

BRACKET

11,220

SETSCREW

FURNACE  

PLENUM

RIGID BRACKET

11,205

2696A

TAB

EAR

L4064
HELICAL ELEMENT

Summary of Contents for SUPER TRADELINE L4064B

Page 1: ...element temperature of 350O F 177O C Do not exceed these temperatures or the following electrical ratings amperes Pilot Duty 2 A at 24 Vac 0 25 A at 0 25 to 12 Vdc Maximum Combined Connected Load 2000 VA 75O C 167O F min field wiring required Wiring must conform to NEC Class 1 requirements WARNING CAUTION 120 Vac 240 Vac FAN LIMIT LIMIT FAN 14 84 8 48 7 4 42 54 Full Load Locked Rotor ng ore break ...

Page 2: ...eter mounting hole for element insertion The brass jumper is the breakaway type It must be removed when the limit is used in the low voltage circuit To remove jumper break with a needlenose pliers and remove completely Once removed it is not replaceable See Fig 8 for location L4064 may be mounted using a rigid bracket The rigid bracket requires a hole 13 16 in 20 6 mm diameter for element insertio...

Page 3: ...e pushed directly into terminal holes FOR FEMALE RECEPTACLES It is recommended that the female receptacles be used for wiring accessory equipment i e electronic air cleaner humidifier etc Connect wires to the receptacles as follows 1 Use Nos 14 to 18 size wire depending on electrical requirement 2 Attach 1 4 in 6 4 mm male flag connector to each wire Two male connectors with leadwires are supplied...

Page 4: ...IT SETTING ADJUSTMENT These controllers have a limit stop which prevents the limit indicator lever from being adjusted beyond the equipment manufacturer s specifications 1 Push the small end of Limit Adjust Tool 196722 through hole in scaleplate located at caution marking to depress the stop disc not more than 1 16 in 1 6 mm to release stop lock Fig 10 Stop disc is on back of scaleplate 2 While de...

Reviews: