18
Quick Start Installation Guide
Set URV
Set
Upper
Range
Value
ATTENTION:
Executing this
service will set the Upper
Range Value (URV) equal to
the input pressure
Press
↵
to
enter
menu
selection
↑ and ↓ to
select
entry.
↵
to enter
Damping
#. ##
Selection applies digital
filtering to suppress noise
effects on the PV.
The limits for this value are 0.0
to 102.0 seconds
NAMUR Output
Enabled
Disabled
Disabling sets the loop output
and burnout levels to the
Honeywell levels
DAC Zero Trim
Loop must be
removed from
Automatic Control
DAC
Zero
Trim
This selection allows the loop
zero output 4mA value to be
trimmed.
Note:
You must connect a
current meter to the transmitter
to monitor the loop output.
DAC Span Trim
Loop must be
removed from
Automatic Control
DAC
Span
Trim
This selection allows the loop
span output 20mA value to be
trimmed.
Note:
You must connect a
current meter to the transmitter
to monitor the loop output.
Loop Test
Loop must be
removed from
Automatic Control
Loop
Test
12.000
This selection allows the user
to force the DAC output to any
value between 3.8 and 20.8
mA.
Note: This selection will put the
DAC into Fixed Output Mode,
as indicated by the flashing
output value. Navigation away
from this menu item will return
the loop to Normal (Automatic)
Mode.
Alarm Type 1
None
PV High
PV Low
Critical Diagnostic
Redundant Input Active
Rate of Change*
Deviation*
(*Available only with
Advanced Diagnostics
Option).
Type of alarm.
Read Only
Parameter
Alarm Type 2