SmartLine Temperature Transmitter
Quick Start Installation Guide
17
Reset Sensor Cal
Confirm
Executing this selection Resets
the LRV, and URV Corrects
back to Factory values
Press
↵
to
enter
menu
selection
↑ and ↓ to
select
entry.
↵
to enter
Sensor CVD
(Applicable for
Pt50, Pt100, Pt200,
Pt500 and Pt1000
RTDs only)
Enabled,
Disabled
Callendar - Van Dusen RTD
coefficients for Sensor
Read Only
Parameter
Break Detect
Enable,
Disable
Enable or disable detection of
Input wire break
Press
↵
to
enter
menu
selection
↑ and ↓ to
select
entry.
↵
to enter
Latching
Enable,
Disable
When enabled, causes all
critical sensor input failures to
latch to the Critical Fault state.
The fault may only be cleared
by device reset. When
disabled, the critical sensor
input failure will be cleared if
the input recovers.
CJ Type
Internal,
Fixed
Determines the source of the
Cold Junction compensation
for thermocouple Sensor
types.
Fixed CJ Value
(Visible for TC input
only)
####.##
When CJ Type is Fixed,
specifies the Cold Junction
temperature value for
thermocouple Sensor types.
Degrees Celsius. Fixed CJ
temperatures below -50
degrees have no effect on
measured values.
LRV
URV
#. ##
#. ##
The limits are the Lower
Range Limit (LRL) and the
Upper Range Limit (URL) of
the selected Sensor 1 ID
Set LRV
Set
Lower
Range
Value
ATTENTION:
Executing this
service will set the Lower
Range Value (LRV) equal to
the input pressure