SmartLine Temperature Transmitter
12
Quick Start Installation Guide
EXPLOSION-PROOF CONDUIT SEAL
When installed as explosion proof in a Division 1 Hazardous Location, keep
covers tight while the Transmitter is energized. Disconnect power to the
Transmitter in the non-hazardous area prior to removing end caps for service.
When installed as non-incendive equipment in a Division 2 hazardous location,
disconnect power to the Transmitter in the non-hazardous area, or determine that
the location is non-hazardous before disconnecting or connecting the Transmitter
wires.
Transmitters installed as explosion proof in Class I, Division 1, Group A Hazardous
(classified) locations in accordance with ANSI/NFPA 70, the US National Electrical
Code, require a LISTED explosion proof seal to be installed in the conduit, within 18
inches (457.2 mm) of the Transmitter. Crouse-Hinds type EYS/EYD or EYSX/EYDX
are examples of LISTED explosion proof seals that meet this requirement.
Transmitters installed as explosion proof in Class I, Division 1, Group B, C or D
hazardous (classified) locations do not require that explosion proof seal be installed
in the conduit.
Step
Action
1
See
Figure 8
, above, for parts locations. Loosen the end cap lock
using a 1.5 mm Allen wrench.
2
Remove the end cap cover from the terminal block end of the
Electronics Housing
3
Feed loop power leads through one end of the conduit entrances on
either side of the Electronics Housing. The Transmitter accepts up to
16 AWG wire.
4
Connect the positive loop power lead to the positive (+) terminal and
the negative loop power lead to the negative (-) terminal.
Note
that the Transmitter is not polarity-sensitive.
5
Feed input sensor wires through the 2
nd
conduit entrance and
connect wire per wiring diagrams.
6
Replace the end cap, and
secure it in place