background image

SP970A, B, C AND D MANUAL AND MINIMUM POSITION PRESSURE REGULATORS 

SP970C and D: Four Port Switches 

These minimum position devices have a separate dead 

ended chamber connected to port 3 to receive an 
external signal. When the external signal is less than the 

spring load, the signal has no effect and functions similar 

PILOT 

CHAMBER 

PILOT 

BRANCH 

VENT 

MAIN 

SP970C,D 

A. BUILDING TO MINIMUM SETTING 

SP970C,D 

PILOT 

BRANCH 

VENT 

MAIN 

B. BALANCED AT MINIMUM SETTING 

to the SP970A, B as a pressure regulator. When the 
external signal is greater than the spring load, the spring 

load is isolated and the device duplicates the input 
signal. See Fig. 7. 

SP970C,D 

DISC 

PILOT 

BRANCH 

VENT 

MAIN 

C. PILOT BUILDING BRANCH ABOVE

 MINIMUM SETTING 

SP970C,D 

PILOT 

BRANCH 

VENT 

MAIN 

D. BALANCED AGAINST PILOT 

C4300 

Fig. 7. SP970C and D operation. 

Application 

Fig. 8A shows a typical manual position application using 

the three port SP970A, B. This control system manually 
positions a damper between OPEN and CLOSED. 

Turning the setpoint knob clockwise increases the 
branchline pressure to the damper actuator and opens 
the damper. Turning the position knob counterclockwise 

decreases the branchline pressure and closes the 
damper. 

The three port SP970A, B is also used with a controller 

for automatic damper positioning with minimum position. 
See Fig. 8B. When the external signal is less than the 

knob setting, the spring maintains the branchline 

pressure as previously described. When the external 
signal rises above the knob setting, air from the signal 

flows directly to the branch. During steady state 
conditions, the external automatic controller must be 
capable of exhausting the air flowing through the exhaust 

(pilot) port 4. 

Fig. 8C shows a typical four port SP970C, D application. 
The minimum position switch keeps the pneumatic 

actuator at a minimum position until the thermostat 
pressure is greater than the minimum position valve. The 

thermostat then controls the actuator. 

DAMPER 

DAMPER 

1  2 

DAMPER 

ACTUATOR 

ACTUATOR 

ACTUATOR 

SP970C OR D 

INSERTION 
THERMOSTAT 

3

BRANCH 

BRANCH 

EXH 

SP970A OR B 

CONTROLLER 

B. MINIMUM POSITION  

C. MINIMUM POSITION 

APPLICATION WITH 

APPLICATION 

CONTROLLER INPUT 

WITH THERMOSTAT 

C8279 

Fig. 8. Typical SP970 application. 

BRANCH 

EXH 

SP970A OR B 

A. MANUAL POSITION 

APPLICATION 

Automation and Control Solutions 

Honeywell 

Honeywell Limited-Honeywell Limitée 

1985 Douglas Drive North 

35 Dynamic Drive 

Golden Valley, MN  55422 

Scarborough, Ontario 
M1V 4Z9 

Printed in U.S.A. on recycled

95-7237EF    J.H. Rev. 2-02 

customer.honeywell.com 

paper containing at least 10% 
post-consumer paper fibers. 

Summary of Contents for SP907B

Page 1: ...inimum Position Pressure Regulators provide regulated pressure to a Figs 1 and 2 show approximate dimensions SP970A 3 1 2 89 SP970C 3 7 8 98 0 8 0 60 40 2 0 10 0 2 1 2 63 1 1 2 38 7 8 22 2 1 4 57 1 7 8 48 C4857 FRONT VIEW SIDE VIEW Fig 1 SP970A and C dimensions in in mm 3 1 2 89 0 8 0 60 40 2 0 10 0 3 1 4 83 2 1 16 62 1 9 16 40 1 25 7 8 4 1 2 114 FRONT VIEW 22 SIDE VIEW C4858 Fig 2 SP970B and D di...

Page 2: ...nished with SP970A and C Do not mount the knob during installation Refer to the Calibration section of this docu ment Surface Mounting Use the mounting bracket as a template and secure mounting bracket to surface See Fig 4 Screws are not provided Piping All connections are sharp barb 5 32 in 4 mm O D polyethylene tubing CAUTION Equipment Damage Hazard To prevent damage to the sharp barb connection...

Page 3: ... chamber for minimum pressure applications mounted on a sheet metal panel Selectable Spans for psi kPa See Table 2 Table 2 Selectable Spans Model Knob Rotationa 188 244 300 Small span 5 34 6 5 45 8 55 Large span 10 69 13 90 16 110 a The setpoint knob normally rotates 188 degrees Two breakaway stops on the knob allow rotation of 244 and 300 degrees Operating Pressure Switch and Pilot Range Normal M...

Page 4: ...es the damper The three port SP970A B is also used with a controller for automatic damper positioning with minimum position See Fig 8B When the external signal is less than the knob setting the spring maintains the branchline pressure as previously described When the external signal rises above the knob setting air from the signal flows directly to the branch During steady state conditions the ext...

Page 5: ...Les Fig 1 et 2 donnent l encombrement approximatif des servomoteurs pneumatiques de registres Ils servent à appareils SP970A 89 3 1 2 SP970C 98 3 7 8 0 8 0 60 40 2 0 10 0 63 2 1 2 38 1 1 2 22 7 8 57 2 1 4 48 1 7 8 CF4857 VUE DE FACE VUE DE PROFIL Fig 1 Encombrement des SP970A et C en mm po CF4858 89 3 1 2 0 8 0 60 40 2 0 10 0 83 3 1 4 62 2 1 16 40 1 9 16 25 1 22 7 8 114 4 1 2 VUE DE FACE VUE DE PR...

Page 6: ...t de l installation Consulter la section Étalon nage de la présente notice technique Montage en surface Utiliser le support de montage comme gabarit puis le fixer à la surface Voir la Fig 4 Les vis ne sont pas fournies Tuyaux Tous les raccords sont effectués avec des tuyaux à crans en polyéthylène de 4 mm 5 32 po de diam ext MISE EN GARDE Risque de dommage matériel Ne pas couper ni tirer les canal...

Page 7: ...ure en kPa psi voir le Tableau 2 Tableau 2 Choix d intervalles Gamme de pression de service commutation et pilote Canal princ normale 124 kPa 18 psi Canal sec 21 à 103 kPa 3 à 15 psi Pilote 21 à 103 kPa 3 à 15 psi Pression d air admissible maximale 207 kPa 30 psi Limites ambiantes de service Température 18 à 60 C 0 à 140 F Humidité relative 5 à 95 Débit d air SP970A B au dessus de la position mini...

Page 8: ...e la pression dans la canalisation secondaire et le registre se ferme Les appareils SP970A et B à trois orifices sont aussi utilisés avec des régulateurs pour positionner automatiquement un registre en position minimale Voir la Fig 8B Lorsque la pression du signal extérieur est inférieure à celle du réglage du bouton le ressort maintient la pression dans la canalisation secondaire comme il est déc...

Reviews: