SV9510/SV9520 SMARTVALVE™ SYSTEM CONTROLS
69-2014
2
Table 2. Model Number Suffix Letter Designation.
Prepurge Time (Factory-Set):
15 seconds.
Trial for Ignition (IAP+FRP):
7 or 9 seconds typical, depending on model.
Igniter Warmup Period:
See Table 1.
Automatic Restart Delay:
60 minutes, minimum.
Ignition Retries:
3 retries; 4 trials total before lockout.
Ignition Recycles:
4, then lockout.
Flame Failure Response Time:
2 seconds max. at 5 µA.
Capacity:
See Table 3.
Conversion:
Use conversion factors in Table 4 to convert capacities for
other gases.
Regulation Range (Btuh):
SV9510/SV9520 with 1/2 in. NPT Outlet:
Natural Gas:
Minimum: 20,000.
Maximum: 200,000.
LP Gas:
Minimum: 40,000.
Maximum: 200,000.
Natural-LP Gas Conversion Kits:
Natural Gas to LP:
393691 Conversion Kit.
LP to Natural Gas:
394588 Conversion Kit.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury or
death.
Always change the main burner orifices when
converting from natural to LP gas or from LP to
natural gas. Follow appliance manufacturer
specifications and instructions.
CAUTION
Equipment Damage Hazard.
Improper wiring can damage equipment.
Never apply a jumper across or short the
thermostat, 24V hot or 24V common terminal in
the SV9510/SV9520 wiring harness. This can
burn out the heat anticipator in the thermostat or
damage the system transformer.
IMPORTANT
Ignition system controls with step-opening
regulators (SV9510P/SV9520P) CANNOT be
field-converted to LP or natural gas.
Pipe Adapters:
Angle and straight adapters available for 3/8-, 1/2- and
3/4-in. pipe. See Table 8. Flange kits include one
flange with attached O-ring, four mounting screws, a 9/
64 in. hex wrench and instructions.
Table 3. Capacity
a
of SV9510/SV9520.
a
Capacity is reduced by 5 percent with the use of outlet screen.
b
Capacity based on 1000 Btu/feet
3
, 0.64 specific gravity natural gas at 1 in. wc pressure drop (37.3 MJ/meter
3
, 0.64
specific gravity natural gas at 0.25 kPa pressure drop).
c
Valves are guaranteed at only 77 percent of the rating.
Approvals:
CAS International: 158158-10592145.
Table 4. Gas Capacity Conversion Factor.
Model No. Suffix Letter
Ambient Temperature Range
Pressure Regulator Type
H
0°F to 175°F (-18°C to +79°C)
Slow-opening
K
-40°F to +175°F (-40°C to +79°C)
M
-40°F to +175°F (-40°C to +79°C)
Standard
Model
Size (Inlet and
Outlet) (in.)
Capacity (at 1 in. wc
pressure drop
b,c
)
Minimum Regulated
Capacity
Maximum Regulated
Capacity
SV9510/SV9520
1/2 x 1/2 NPT
150 ft
3
/hr (4.2 m
3
/hr)
20 ft
3
/hr (0.6 m
3
/hr)
200 ft
3
/hr(5.7 m
3
/hr)
Gas
Specific
Gravity
Multiply Listed
Capacity By
Manufactured
0.60
0.516
Mixed
0.70
0.765
Propane
1.53
1.62