62-0123—3
4
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Table 2. Thermostat Installer Setup Options (Continued).
(continued)
Installer Setup
Number
(Press
Unoccupied
Temp key
Factory-Setting
Other Choices
(Press
▲
or
▼
key to change)
Actual
Select
to change)
Display
Description
Display
Description
Setting
Cooling cycle
9
4
Stage 1—4 cph
3
3—3 cph
rate
10
4
Stage 2—4 cph
11
4
Stage 3—4 cph
System setting
adjustment
(models with
System key)
12
Depends
on model
System selection
0, 1 or 2
0—System setting key is
operational
1—Auto setting is disabled
2—Auto only setting
Degree tempera-
ture display
14
0
Temperature is
displayed in
°
F
1
Temperature is displayed in
°
C
Clock format
16
0
12-hour clock format
1
24-hour clock format
Intelligent Fan™
operation
17
2
Fan operates
continuously in
Occupied and
Recovery mode. Fan
operates with call for
heating or cooling in
Unoccupied mode.
0 or 1
0—Fan only operates with
calls for heating or cooling
in Occupied and
Unoccupied modes.
1—Fan operates
continuously in Occupied
mode. Fan operates with
calls for heating or cooling
in Unoccupied mode.
Auxiliary Contact
Operation
18
0
0—Time of day
contacts
1
1—Economizer contacts
—
Extended fan
operation in
heating
19
0
No extended fan
operation after the call
for heat ends
1
Fan operation is extended
90 seconds after the call for
heat ends.
Fan key
adjustment
(models with Fan
key only)
21
0
Fan setting key is
operational
1
Fan setting key is Auto only
Remote sensing 22
0
Remote sensing not
activated
1
Remote sensing activated
Keypad lockout
level (keypad
lockout is
enabled and
disabled by DIP
switch 1 on back
of thermostat)
25
0
No lockout
1 or 2, 3
1—Lockout all keys on
thermostat except system
and fan settings, temporary
setpoint, clock and day
adjustments
2—Lockout all keys except
Set Current Day/Time,
increase
▲
and decrease
▼
keys.
3—Lockout all keys except
Temporary Occupied, Set
Day and Clock keys
Duration of
temporary
override
26
3
3—Three hour
override
1, 8 or 12 1—One hour override
8—Eight hour override
12—Twelve hour override
Minimum off time
for the
compressor
33
4
4 minute minimum off
time for the
compressor
0, 1, 2, 3
or 5
Minimum number of minutes
(0 thru 5) the compressor will
be off between calls for the
compressor