44
MAN0530 Issue 10 - 11/09
Searchline Excel
2104M0506
(4)
Press
Enter
on the keypad and an initial set time display similar to the following
appears:
Time 09:26
09
The top line shows the current time and the second line shows the new hours setting.
(5)
Set the hour using the up and down keys on the keypad.
(6)
Press
Enter
on the keypad and the new minutes setting is now displayed on the second
line.
Time 09:26
09:26
(7)
Set the minutes using the up and down keys on the keypad.
(8)
Press
Enter
on the keypad and the display for setting the date now appears as
follows:
Date 20APR03
20
The second line shows the new day setting.
(9)
Set the day using the up and down keys on the keypad.
(10) Press
Enter
on the keypad and the new month setting is then displayed.
(11) Repeat the procedure to set the month and year.
(12) When complete press
Enter
on the keypad to return to the
Calibrate
menu.
Notes:
1.
The time and date will not be updated unless both are entered and accepted without
error.
2.
Pressing
esC
on the keypad at any time, aborts the current setting immediately and
returns to the previous setting or menu option.
Complete the alignment process
In this part of the procedure details about the gas detector must be entered so that the Interrogator
can then complete the commissioning of the gas detector using the correct data.
(1)
Select
Calibrate
from the
Main
menu.
Press the up and down keys on the keypad to navigate through the menu options.
(2)
Press
Enter
on the Interrogator keypad.
This displays the
Calibrate menu.
(3)
Select
Install
from the
Calibrate
menu.
(4)
Press
Enter
on the keypad.
3. INSTALLATION AND OPERATION
>
>
>
>
>
>